R 408.10661 Horizontal exits.
Cite as Mich. Admin. Code R 408.10661
Rule 661. (1) A fire area or area of refuge with a horizontal exit shall have, in
addition to the horizontal exit or exits, at least 1 means of egress leading to the outside, or
have access to an adjacent fire area containing an outside means of egress.
(2) Where either side of a horizontal exit is occupied, the doors used in connection
with the horizontal exit shall be unlocked.
(3) The floor area on either side of a horizontal exit shall be sufficient to hold the
occupants of both floor areas allowing not less than 3 square feet clear floor area per
person.
(4) Where a horizontal exit serves areas on both sides of a wall, there shall be
adjacent openings with swinging doors at each, opening in opposite directions, with signs
on each side of the wall or partition indicating as the exit door which swings with the
travel from that side; or other approved arrangements providing doors always swinging
with any possible exit travel.