R 408.16246
R 408.16246 Dielectric sealing.
Cite as Mich. Admin. Code R 408.16246
Rule 6246. (1) An electrical power pack or oscillator cabinet shall have the access
doors interlocked in a manner which will cut the power when the doors are opened and
shall have a mechanical shorting bar which will automatically ground out the residual
energy.
(2) An employee shall be protected by an interlocked and grounded shield that is
constructed to block the direct passage of the stray currents moving out of the
intended path.
(3) The point of operation shall also be guarded as prescribed by the provisions of
R 408.16245(1). The movable or fixed barrier and the shield required in subrule (2) of
this rule may be the same if it accomplishes both purposes.