R 325.10602
R 325.10602 Maximum contaminant levels (MCLs) for microbiological contaminants.
Cite as Mich. Admin. Code R 325.10602
Rule 602. (1) Beginning April 1, 2016, a community or noncommunity water supply is in
compliance with the MCL for E. coli for samples taken under R 325.10704a to
R 325.10704k unless 1 or more of the following conditions occur:
(a) The supply has an E. coli-positive repeat sample following a total coliform-positive
routine sample.
(b) The supply has a total coliform-positive repeat sample following an E. coli-positive
routine sample.
(c) The supply fails to take all required repeat samples following an E. coli-positive
routine sample.
(d) The supply fails to test for E. coli when a repeat sample tests positive for total
coliform.
Note to this subrule: For purposes of the public notification requirements in R 325.10401a
to R 325.10409, violation of the MCL may pose an acute risk to health.
(2) Beginning April 1, 2016, a supply shall determine compliance with the MCL for E.
coli in subrule (1) of this rule for each month in which it is required to monitor for total
coliforms.
(3) The best technology, treatment techniques, or other means available for achieving
compliance with the maximum contaminant level for total coliforms in subrule (5) of this
rule until March 31, 2016 and for achieving compliance with the maximum contaminant
level for E. coli in subrule (1) of this rule beginning April 1, 2016 are all of the following:
(a) Protection of wells from fecal contamination by appropriate placement and
construction.
(b) Maintenance of a disinfectant residual throughout the distribution system.
(c) Proper maintenance of the distribution system including appropriate pipe replacement
and repair procedures, main flushing programs, proper operation and maintenance of
storage tanks and reservoirs, cross connection control, and continual maintenance of
positive water pressure in all parts of the distribution system.
(d) Filtration and disinfection of surface water, as described in the surface water treatment
provisions of R 325.10611 to R 325.10611n, R 325.10720 to R 325.720e, and
R 325.10722, or disinfection of groundwater, as described in the groundwater provisions
of R 325.10612 to R 325.10612b and R 325.10739 to R 325.10739b, using strong oxidants
such as chlorine, chlorine dioxide, or ozone.
(e) For supplies using ground water, compliance with the requirements of an EPA-
approved state Wellhead Protection Program developed and implemented under section
1428 of the federal act.
(4) The technology, treatment techniques, or other means available identified in subrule
(3) of this rule are considered affordable technology, treatment techniques, or other means
available to supplies serving 10,000 or fewer people for achieving compliance with the
maximum contaminant level for total coliforms in subrule (5) of this rule until March 31,
2016 and for achieving compliance with the maximum contaminant level for E. coli in
subrule (1) of this rule beginning April 1, 2016.
(5) Until March 31, 2016 all of the following apply:
(a) The total coliform MCL is based on the presence or absence of total coliforms in a
sample, rather than coliform density. Either of the following applies to the total coliform
MCL:
(i) For a supply that collects at least 40 samples per month, if no more than 5.0 percent
of the samples collected during a month are total coliform-positive, the supply is in
compliance with the MCL for total coliforms.
(ii) For a supply that collects fewer than 40 samples per month, if no more than one
sample collected during a month is total coliform-positive, the supply is in compliance with
the MCL for total coliforms.
(b) A fecal coliform-positive repeat sample or E. coli-positive repeat sample, or a total
coliform-positive repeat sample following a fecal coliform-positive or E. coli-positive
routine sample, constitutes a violation of the MCL for total coliforms. For purposes of the
public notification requirements in R 325.10401a to R 325.10409, this is a violation that
may pose an acute risk to health.
(c) A supply shall determine compliance with the MCL for total coliforms in this subrule
for each month in which it is required to monitor for total coliforms.