R 325.10611f
R 325.10611f Enhanced treatment for Cryptosporidium; treatment technique; additional Cryptosporidium treatment requirements.
Cite as Mich. Admin. Code R 325.10611f
Rule 611f. (1) Subpart H supplies are also considered "water supplies" or "supplies" in
this rule. Subpart H supplies that are subject to R 325.10611d shall provide the level of
additional treatment for Cryptosporidium specified in the following table based on their
bin classification as determined under R 325.10611e and according to the schedule in R
325.10611g:
If the supply
bin
classification
is …
And the supply uses the following filtration treatment in full compliance
with R 325.10611 to R 325.10611c, R 325.10720 to R 325.10720a, and
R 325.10722, as applicable, then the additional Cryptosporidium
treatment requirements are …
Conventional
filtration or
membrane filtration
treatment (including
softening)
Direct
filtration
Slow sand or
diatomaceous
earth filtration
Alternative
filtration
technologies
approved by
the department
under R
325.10611b (3)
Bin 1
No additional
treatment
No additional
treatment
No additional
treatment
No additional
treatment
Bin 2
1-log treatment
1.5-log
treatment
1-log treatment
Note 1
Bin 3
2-log treatment
2.5-log
treatment
2-log treatment
Note 2
Bin 4
2.5-log treatment
3-log
treatment
2.5-log
treatment
Note 3
Note 1: As determined by the department such that the total Cryptosporidium removal and
inactivation is not less than 4.0-log.
Note 2: As determined by the department such that the total Cryptosporidium removal and
inactivation is not less than 5.0-log.
Note 3: As determined by the department such that the total Cryptosporidium removal and
inactivation is not less than 5.5-log.
(2) All of the following provisions apply to microbial toolbox options:
(a) Supplies shall use 1 or more of the treatment and management options listed in R
325.10611h, termed the microbial toolbox, to comply with the additional Cryptosporidium
treatment required in subrule (1) of this rule.
(b) Supplies classified in Bin 3 and Bin 4 shall achieve not less than 1-log of the additional
Cryptosporidium treatment required under subrule (1) of this rule using either 1 or a
combination of the following: bag filters, bank filtration, cartridge filters, chlorine dioxide,
membranes, ozone, or UV, as described in R 325.10611i to R 325.10611m.
(3) Failure by a supply in any month to achieve treatment credit by meeting criteria in R
325.10611i to R 325.10611m for microbial toolbox options that is not less than equal to
the level of treatment required in subrule (1) of this rule is a violation of the treatment
technique requirement.
(4) If the department determines during a sanitary survey or an equivalent source water
assessment that after a supply completed the monitoring conducted under 40 CFR
§141.701(a) or 40 CFR §141.701(b), as adopted by reference in R 325.10720b, significant
changes occurred in the supply's watershed that could lead to increased contamination of
the source water by Cryptosporidium, the supply shall take actions specified by the
department to address the contamination. These actions may include additional source
water monitoring or implementing microbial toolbox options listed in R 325.10611h, or
both.