R 325.10611l
R 325.10611l Enhanced treatment for Cryptosporidium; microbial toolbox; additional filtration toolbox components.
Cite as Mich. Admin. Code R 325.10611l
Rule 611l. (1) Bag and cartridge filters is an additional filtration toolbox component.
Subpart H supplies that are subject to R 325.10611d receive Cryptosporidium treatment
credit of up to 2.0-log for individual bag or cartridge filters and up to 2.5-log for bag or
cartridge filters operated in series. To be eligible for this credit, supplies shall report the
results of challenge testing that meets the requirements of subdivisions (b) to (i) of this
subrule to the department. The filters shall treat the entire plant flow taken from a surface
water or GWUDI source. All of the following apply to bag and cartridge filters as an
additional filtration toolbox component:
(a) The Cryptosporidium treatment credit awarded to bag or cartridge filters shall be based
on the removal efficiency demonstrated during challenge testing that is conducted
according to the criteria in subdivisions (b) to (i) of this subrule. A factor of safety equal
to 1-log for individual bag or cartridge filters and 0.5-log for bag or cartridge filters in
series shall be applied to challenge testing results to determine removal credit. Subpart H
supplies may use results from challenge testing conducted before January 5, 2006 if the
prior testing was consistent with the criteria specified in subdivisions (b) to (i) of this
subrule.
(b) Challenge testing shall be performed on full-scale bag or cartridge filters, and the
associated filter housing or pressure vessel, that are identical in material and construction
to the filters and housings the supply will use for removal of Cryptosporidium. Bag or
cartridge filters shall be challenge tested in the same configuration that the supply will use,
either as individual filters or as a series configuration of filters.
(c) Challenge testing shall be conducted using Cryptosporidium or a surrogate that is
removed no more efficiently than Cryptosporidium. The microorganism or surrogate used
during challenge testing is referred to as the challenge particulate. The concentration of the
challenge particulate shall be determined using a method capable of discreetly quantifying
the specific microorganism or surrogate used in the test. Gross measurements such as
turbidity may not be used.
(d) The maximum feed water concentration that can be used during a challenge test shall
be based on the detection limit of the challenge particulate in the filtrate, that is filtrate
detection limit, and shall be calculated using the following equation:
Maximum Feed Concentration = 1 x 10[superscript]4 x (Filtrate Detection Limit)
(e) Challenge testing shall be conducted at the maximum design flow rate for the filter as
specified by the manufacturer.
(f) Each filter evaluated shall be tested for a duration sufficient to reach 100% of the
terminal pressure drop, which establishes the maximum pressure drop under which the
filter may be used to comply with the requirements of R 325.10611d to R 325.10611n and
R 325.10720b to R 325.10720e.
(g) Removal efficiency of a filter shall be determined from the results of the challenge
test and expressed in terms of log removal values using the following equation:
LRV = LOG10(Cf)-LOG10(Cp)
Where:
LRV = log removal value demonstrated during challenge testing; Cf = the feed
concentration measured during the challenge test; and Cp = the filtrate concentration
measured during the challenge test. In applying this equation, the same units shall be used
for the feed and filtrate concentrations. If the challenge particulate is not detected in the
filtrate, then the term Cp shall be set equal to the detection limit.
(h) Each filter tested shall be challenged with the challenge particulate during all of the
following periods over the filtration cycle:
(i) Within 2 hours of start-up of a new filter.
(ii) When the pressure drop is between 45 and 55% of the terminal pressure drop.
(iii) At the end of the cycle after the pressure drop has reached 100% of the terminal
pressure drop. Note to subdivision (h) of this subule: An LRV shall be calculated for each
of these challenge periods for each filter tested. The LRV for the filter (LRVfilter) shall be
assigned the value of the minimum LRV observed during the 3 challenge periods for that
filter.
(i) If fewer than 20 filters are tested, the overall removal efficiency for the filter product
line shall be set equal to the lowest LRVfilter among the filters tested. If 20 or more filters
are tested, the overall removal efficiency for the filter product line shall be set equal to the
10th percentile of the set of LRVfilter values for the various filters tested. The percentile
is defined by (i/(n+1)) where i is the rank of n individual data points ordered lowest to
highest. If necessary, the 10th percentile may be calculated using linear interpolation.
(j) If a previously tested filter is modified in a manner that could change the removal
efficiency of the filter product line, challenge testing to demonstrate the removal efficiency
of the modified filter shall be conducted and submitted to the department.
(2) All of the following apply to membrane filtration as an additional filtration toolbox
component:
(a) Subpart H supplies receive Cryptosporidium treatment credit for membrane filtration
that meets the criteria of this subrule. Membrane cartridge filters that meet the definition
of membrane filtration in R 325.10106 are eligible for this credit. The level of treatment
credit a supply receives is equal to the lower of the values determined under both of the
following:
(i) The removal efficiency demonstrated during challenge testing conducted under the
conditions in subdivision (b) of this subrule.
(ii) The maximum removal efficiency that can be verified through direct integrity testing
used with the membrane filtration process under the conditions in subdivision (c) of this
subrule.
(b) Challenge testing demonstrates removal efficiency. The membrane used by the
subpart H supply shall undergo challenge testing to evaluate removal efficiency, and the
supply shall report the results of challenge testing to the department. Challenge testing shall
be conducted according to all of the criteria in paragraphs (i) to (vii) of this subdivision.
Subpart H supplies may use data from challenge testing conducted before January 5, 2006
if the prior testing was consistent with all of the criteria in paragraphs (i) to (vii) of this
subdivision.
(i) Challenge testing shall be conducted on either a full-scale membrane module, identical
in material and construction to the membrane modules used in the supply's treatment
facility, or a smaller-scale membrane module, identical in material and similar in
construction to the full-scale module. A module is defined as the smallest component of a
membrane unit in which a specific membrane surface area is housed in a device with a
filtrate outlet structure.
(ii) Challenge testing shall be conducted using Cryptosporidium oocysts or a surrogate
that is removed no more efficiently than Cryptosporidium oocysts.The organism or
surrogate used during challenge testing is referred to as the challenge particulate. The
concentration of the challenge particulate, in both the feed and filtrate water, shall be
determined using a method capable of discretely quantifying the specific challenge
particulate used in the test. Gross measurements such as turbidity may not be used.
(iii) The maximum feed water concentration that can be used during a challenge test is
based on the detection limit of the challenge particulate in the filtrate and shall be
determined according to the following equation:
Maximum Feed Concentration = 3.16 x 10[superscript]6 x (Filtrate Detection Limit)
(iv) Challenge testing shall be conducted under representative hydraulic conditions at the
maximum design flux and maximum design process recovery specified by the
manufacturer for the membrane module. Flux is defined as the throughput of a pressure
driven membrane process expressed as flow per unit of membrane area. Recovery is
defined as the volumetric percent of feed water that is converted to filtrate over the course
of an operating cycle uninterrupted by events such as chemical cleaning or a solids removal
process, that is, backwashing.
(v) Removal efficiency of a membrane module shall be calculated from the challenge test
results and expressed as a log removal value according to the following equation:
LRV = LOG10(Cf)-LOG10(Cp)
Where:
LRV = log removal value demonstrated during the challenge test; Cf = the feed
concentration measured during the challenge test; and Cp = the filtrate concentration
measured during the challenge test. Equivalent units shall be used for the feed and filtrate
concentrations. If the challenge particulate is not detected in the filtrate, the term Cp is set
equal to the detection limit for the purpose of calculating the LRV. An LRV shall be
calculated for each membrane module evaluated during the challenge test.
(vi) The removal efficiency of a membrane filtration process demonstrated during
challenge testing shall be expressed as a log removal value (LRVC-Test). If fewer than 20
modules are tested, then LRVC-Test is equal to the lowest of the representative LRVs
among the modules tested. If 20 or more modules are tested, then LRVC-Test is equal to
the 10th percentile of the representative LRVs among the modules tested. The percentile is
defined by (i/ (n+1)) where i is the rank of n individual data points ordered lowest to
highest. If necessary, the 10th percentile may be calculated using linear interpolation.
(vii) The challenge test shall establish a quality control release value (QCRV) for a
nondestructive performance test that demonstrates the Cryptosporidium removal capability
of the membrane filtration module. This performance test shall be applied to each
production membrane module used by the supply that was not directly challenge tested in
order to verify Cryptosporidium removal capability. Production modules that do not meet
the established QCRV are not eligible for the treatment credit demonstrated during the
challenge test.
(viii) If a previously tested membrane is modified in a manner that could change the
removal efficiency of the membrane or the applicability of the nondestructive performance
test and associated QCRV, additional challenge testing to demonstrate the removal
efficiency of, and determine a new QCRV for, the modified membrane shall be conducted
and submitted to the department.
(c) Direct integrity testing demonstrates removal efficiency. Subpart H supplies shall
conduct direct integrity testing in a manner that demonstrates a removal efficiency equal
to or greater than the removal credit awarded to the membrane filtration process. A direct
integrity test is defined as a physical test applied to a membrane unit in order to identify
and isolate integrity breaches for example, 1 or more leaks that could result in
contamination of the filtrate. The direct integrity testing shall meet all of the following
requirements:
(i) The direct integrity test shall be independently applied to each membrane unit in
service. A membrane unit is defined as a group of membrane modules that share common
valving that allows the unit to be isolated from the rest of the system for the purpose of
integrity testing or other maintenance.
(ii) The direct integrity method shall have a resolution of 3 micrometers or less, where
resolution is defined as the size of the smallest integrity breach that contributes to a
response from the direct integrity test.
(iii) The direct integrity test shall have a sensitivity sufficient to verify the log treatment
credit awarded to the membrane filtration process by the department, where sensitivity is
defined as the maximum log removal value that can be reliably verified by a direct integrity
test. Sensitivity shall be determined using the approach in either of the following as
applicable to the type of direct integrity test the supply uses:
(A) For direct integrity tests that use an applied pressure or vacuum, the direct integrity
test sensitivity shall be calculated according to the following equation:
LRVDIT = LOG10 (Qp / (VCF x Qbreach))
Where:
LRVDIT = the sensitivity of the direct integrity test; Qp = total design filtrate flow from
the membrane unit; Qbreach = flow of water from an integrity breach associated with the
smallest integrity test response that can be reliably measured, and VCF = volumetric
concentration factor. The volumetric concentration factor is the ratio of the suspended
solids concentration on the high pressure side of the membrane relative to that in the feed
water.
(B) For direct integrity tests that use a particulate or molecular marker, the direct integrity
test sensitivity shall be calculated according to the following equation:
LRVDIT = LOG10 (Cf)-LOG10 (Cp)
Where:
LRVDIT = the sensitivity of the direct integrity test; Cf = the typical feed concentration of
the marker used in the test; and Cp = the filtrate concentration of the marker from an
integral membrane unit.
(iv) Supplies shall establish a control limit within the sensitivity limits of the direct
integrity test that is indicative of an integral membrane unit capable of meeting the removal
credit awarded by the department.
(v) If the result of a direct integrity test exceeds the control limit established under
paragraph (iv) of this subdivision, the supply shall remove the membrane unit from
service. Supplies shall conduct a direct integrity test to verify the repairs, and may return
the membrane unit to service only if the direct integrity test is within the established control
limit.
(vi) Supplies shall conduct direct integrity testing on each membrane unit at a frequency
of at least once each day that the membrane unit is in operation. The department may
approve less frequent testing, based on demonstrated process reliability, the use of multiple
barriers effective for Cryptosporidium, or reliable process safeguards.
(d) Indirect integrity monitoring is required on membrane units. Supplies shall conduct
continuous indirect integrity monitoring on each membrane unit according to all of the
criteria in this subdivision. "Indirect integrity monitoring" is defined as monitoring some
aspect of filtrate water quality that is indicative of the removal of particulate matter. A
supply that implements continuous direct integrity testing of membrane units under the
criteria in subdivision (c)(i) to (v) of this subrule is not subject to the requirements for
continuous indirect integrity monitoring. Supplies shall submit a monthly report to the
department summarizing all continuous indirect integrity monitoring results triggering
direct integrity testing and the corrective action that was taken in each case. All of the
following apply to continuous indirect integrity monitoring on each membrane unit:
(i) Unless the department approves an alternative parameter, continuous indirect integrity
monitoring shall include continuous filtrate turbidity monitoring.
(ii) Continuous monitoring shall be conducted at a frequency of at least once every 15
minutes.
(iii) Continuous monitoring shall be separately conducted on each membrane unit.
(iv) If indirect integrity monitoring includes turbidity and if the filtrate turbidity readings
are above 0.15 NTU for a period greater than 15 minutes, that is, 2 consecutive 15-minute
readings above 0.15 NTU, direct integrity testing shall immediately be performed on the
associated membrane unit as specified in subdivision (c)(i) to (v) of this subrule.
(v) If indirect integrity monitoring includes a department-approved alternative parameter
and if the alternative parameter exceeds a department-approved control limit for a period
greater than 15 minutes, direct integrity testing shall immediately be performed on the
associated membrane units as specified in subdivision (c)(i) to (v) of this subrule.
(3) Second stage filtration is an additional filtration toolbox component. Subpart H
supplies receive 0.5-log Cryptosporidium treatment credit for a separate second stage of
filtration that consists of sand, dual media, GAC, or other fine grain media following
granular media filtration if the department approves. To be eligible for this credit, the first
stage of filtration shall be preceded by a coagulation step and both filtration stages shall
treat the entire plant flow taken from a surface water or GWUDI source.A cap, such as
GAC, on a single stage of filtration is not eligible for this credit. The department shall
approve the treatment credit based on an assessment of the design characteristics of the
filtration process.
(4) Slow sand filtration, as secondary filter, is an additional filtration toolbox component.
Subpart H supplies may receive 2.5-log Cryptosporidium treatment credit for a slow sand
filtration process that follows a separate stage of filtration if both filtration stages treat
entire plant flow taken from a surface water or GWUDI source and no disinfectant residual
is present in the influent water to the slow sand filtration process. The department shall
approve the treatment credit based on an assessment of the design characteristics of the
filtration process. This subrule does not apply to treatment credit awarded to slow sand
filtration used as a primary filtration process.