R 325.10611m Enhanced treatment for Cryptosporidium; microbial toolbox; inactivation toolbox components.
Cite as Mich. Admin. Code R 325.10611m
Rule 611m. (1) Calculation of CT values is an inactivation toolbox component. All of the
following apply to CT calculation of subpart H supplies that are subject to R 325.10611d:
(a) CT is the product of the disinfectant contact time (T, in minutes) and disinfectant
concentration (C, in milligrams per liter). Subpart H supplies with treatment credit for
chlorine dioxide or ozone under subrule (2) or (3) of this rule shall calculate CT at least
once each day, with both C and T measured during peak hourly flow as specified in R
325.10605.
(b) Subpart H supplies with several disinfection segments in sequence may calculate CT
for each segment, where a disinfection segment is defined as a treatment unit process with
a measurable disinfectant residual level and a liquid volume. Under this approach, supplies
shall add the Cryptosporidium CT values in each segment to determine the total CT for the
treatment plant.
(2) CT values for chlorine dioxide and ozone is an inactivation toolbox component. Both
of the following apply to CT values:
(a) Subpart H supplies receive the Cryptosporidium treatment credit listed in the
following table by meeting the corresponding chlorine dioxide CT value for the applicable
water temperature, as described in subrule (1) of this rule:
CT Values in milligram-minutes per liter (mg-min/L) for Cryptosporidium Inactivation by
Chlorine Dioxide *
Log
credit
Water Temperature, in degrees Celsius
less than
or equal
to 0.5
1
2
3
5
7
10
15
20
25
30
(i) 0.25
159
153
140
128
107
90
69
45
29
19
12
(ii) 0.5
319
305
279
256
214
180
138
89
58
38
24
(iii) 1.0
637
610
558
511
429
360
277
179
116
75
49
(iv) 1.5
956
915
838
767
643
539
415
268
174
113
73
(v) 2.0
1275
1220
1117
1023
858
719
553
357
232
150
98
Log
credit
Water Temperature, in degrees Celsius
less than
or equal
to 0.5
1
2
3
5
7
10
15
20
25
30
(vi) 2.5
1594
1525
1396
1278
1072
899
691
447
289
188
122
(vii) 3.0
1912
1830
1675
1534
1286
1079
830
536
347
226
147
* Supplies may use this equation to determine log credit between the indicated values: Log
credit = (0.001506 x (1.09116)Temp) x CT.
(b) Subpart H supplies receive the Cryptosporidium treatment credit listed in the
following table by meeting the corresponding ozone CT values for the applicable water
temperature, as described in subrule (1) of this rule:
CT Values in milligram-minutes per liter (mg-min/L) for Cryptosporidium Inactivation by
Ozone *
Log credit
Water Temperature, in degrees Celsius
less than or
equal to 0.5
1
2
3
5
7
10
15
20
25
30
(i) 0.25
6.0
5.8
5.2
4.8
4.0
3.3
2.5
1.6
1.0
0.6
0.39
(ii) 0.5
12
12
10
9.5
7.9
6.5
4.9
3.1
2.0
1.2
0.78
(iii) 1.0
24
23
21
19
16
13
9.9
6.2
3.9
2.5
1.6
(iv) 1.5
36
35
31
29
24
20
15
9.3
5.9
3.7
2.4
(v) 2.0
48
46
42
38
32
26
20
12
7.8
4.9
3.1
(vi) 2.5
60
58
52
48
40
33
25
16
9.8
6.2
3.9
(vii) 3.0
72
69
63
57
47
39
30
19
12
7.4
4.7
* Supplies may use this equation to determine log credit between the indicated values: Log
credit = (0.0397 x (1.09757)Temp) x CT.
(3) Site-specific study is an inactivation toolbox component. The department may approve
alternative chlorine dioxide or ozone CT values to those listed in subrule (2) of this rule on
a site-specific basis. The department shall base this approval on a site-specific study a
subpart H supply conducts that follows a department-approved protocol.
(4) Ultraviolet light is an inactivation toolbox component. Subpart H supplies receive
Cryptosporidium, Giardia lamblia, and virus treatment credits for ultraviolet (UV) light
reactors by achieving the corresponding UV dose values shown in subdivision (a) of this
subrule. Supplies shall validate and monitor UV reactors as described in subdivisions (b)
and (c) of this subrule to demonstrate that they are achieving a particular UV dose value
for treatment credit. All of the following apply to UV:
(a) The following table is the UV dose table. The treatment credits listed in this table are
for UV light at a wavelength of 254 nanometers as produced by a low pressure mercury
vapor lamp. To receive treatment credit for other lamp types, subpart H supplies shall
demonstrate an equivalent germicidal dose through reactor validation testing, as described
in subdivision (b) of this subrule. The UV dose values in this table are applicable only to
post-filter applications of UV in supplies.
UV Dose Table for Cryptosporidium, Giardia lamblia, and Virus Inactivation Credit
Log credit
Cryptosporidium UV dose
in milli-joule per
centimeters squared (mJ/
cm2)
Giardia lamblia UV
dose (mJ/cm2)
Virus UV dose
(mJ/cm 2)
(i) 0.5
1.6
1.5
39
(ii) 1.0
2.5
2.1
58
(iii) 1.5
3.9
3.0
79
(iv) 2.0
5.8
5.2
100
(v) 2.5
8.5
7.7
121
(vi) 3.0
12
11
143
(vii) 3.5
15
15
163
(viii) 4.0
22
22
186
(b) Subpart H supplies shall use UV reactors that have undergone validation testing to
determine the operating conditions under which the reactor delivers the UV dose required
in subdivision (a) of this subrule, that is, validated operating conditions. These operating
conditions shall include flow rate, UV intensity as measured by a UV sensor, and UV lamp
status. All of the following provisions apply to reactor validation testing:
(i) When determining validated operating conditions, supplies shall account for all of the
following factors:
(A) UV absorbance of the water; lamp fouling and aging.
(B) Measurement uncertainty of on-line sensors.
(C) UV dose distributions arising from the velocity profiles through the reactor.
(D) Failure of UV lamps or other critical system components.
(E) Inlet and outlet piping or channel configurations of the UV reactor.
(ii) Validation testing shall include both of the following:
(A) Full scale testing of a reactor that conforms uniformly to the UV reactors used by the
supply.
(B) Inactivation of a test microorganism whose dose response characteristics have been
quantified with a low pressure mercury vapor lamp.
(iii) The department may approve an alternative approach to validation testing.
(c) Both of the following provisions apply to reactor monitoring:
(i) Supplies shall monitor their UV reactors to determine if the reactors are operating
within validated conditions, as determined under subdivision (b) of this subrule. This
monitoring shall include UV intensity as measured by a UV sensor, flow rate, lamp status,
and other parameters the department designates based on UV reactor operation. Supplies
shall verify the calibration of UV sensors and shall recalibrate sensors under a protocol the
department approves.
(ii) To receive treatment credit for UV light, supplies shall treat not less than 95% of the
water delivered to the public during each month by UV reactors operating within validated
conditions for the required UV dose, as described in subdivisions (a) and (b) of this subrule.
Supplies shall demonstrate compliance with this condition by the monitoring required
under paragraph (i) of this subdivision.