R 336.1605
R 336.1605 Storage of organic compounds having true vapor pressure of 11 or more psia in existing stationary vessels of more than 40,000-gallon capacity.
Cite as Mich. Admin. Code R 336.1605
Rule 605. (1) After April 30, 1981, it is unlawful for a person to store any organic compound
having a true vapor pressure of 11 or more psia at actual storage conditions in any existing
stationary vessel of more than 40,000-gallon capacity, unless 1 of the following conditions is met:
(a) The vessel is a pressure tank capable of maintaining working pressures sufficient to prevent
organic vapor or gas loss to the atmosphere at all times, except under emergency conditions.
(b) The vessel is equipped and maintained with a vapor recovery system, or other control system
approved by the department, which recovers not less than 90%, by weight, of the uncontrolled
organic vapor that would otherwise be emitted into the atmosphere.
(2) All openings in any stationary vessel subject to the provisions of this rule shall be equipped
with covers, lids, or seals so that the covers, lids, or seals are in a closed position at all times,
except when in actual use.