9 CSR 45-5.110
Fire Safety for Facility-based Day Habilitation and Employment Service Settings
PURPOSE: This rule establishes fire safety requirements for facilitybased day habilitation and employment service settings funded
through the Medicaid home and community-based waivers. The
department delegates its authority for fire safety inspections under
this rule to the Department of Public Safety, Division of Fire Safety.
(1) General Requirements.
(A) People participating in facility-based day habilitation and
employment service settings are restricted to using the floor of
the building that is at ground level exit discharge. Exception:
People participating in facility-based day habilitation and
employment services may use the floor below and above
the level of exit discharge if the entire building is protected
throughout with an approved automatic sprinkler system.
(B) No facility-based day habilitation and employment
service shall be located in the same building as a high hazard
occupancy.
(C) The staff of the facility shall conduct at least one (1) fire drill
at least once a month. In addition, a natural disaster drill will
be conducted at least twice per year. The staff shall maintain
a written record at the facility of the date, type of drill, time
required to evacuate the building, whether the evacuation
was completed, notation of any problems evacuating, and the
number of occupants present during the drill.
(D) Unscheduled drills shall be held at the Division of Fire
Safety inspector’s discretion.
(E) During severe weather, fire drills may be postponed.
(F) Each fire drill shall evacuate all persons from the building
and be conducted as follows:
1. Drills simulate an actual fire condition;
2. Occupants and staff members do not obtain clothing or
personal effects after the alarm has sounded;
3. The occupants and staff members proceed to a
predetermined point outside the building that is sufficiently
remote to avoid fire danger, or to a predetermined point inside
of the building to defend in place; and
4. Occupants and staff members remain in place until a
recall is issued or until they are dismissed.
(G) No window in a facility shall have bars or any other item
placed over it in a stationary manner that would impede a
rescue or evacuation attempt.
(H) All flammable/combustible liquids, matches, toxic
cleaning supplies, poisonous materials, medicines, or other
hazardous items shall be stored so as to be inaccessible to the
occupants.
(I) The building numbers shall be plainly visible from the
street in case of emergency: at least four (4) inches in height
and contrasting color with the building.
(J) Good housekeeping practices ensuring fire safety will be
maintained daily.
(K) Stairways, walks, ramps, and porches shall be kept free of
ice and snow.
(L) Fresh-cut Christmas trees shall not be used, unless they
are treated with a flame resistant material and documentation
of the treatment is on file at the facility and available for review
by the Division of Fire Safety inspector.
(M) The facility may use a cellular phone when all of the
following conditions are met:
1. The phone must always have a signal;
2. The phone must always be charged;
3. The phone must be able to make and receive normal
calls;
4. The phone must remain at the facility at all times; and
5. The emergency plan for the facility must address the use
of cellular phones.
(N) The facility shall notify the nearest fire department that
the facility is in operation and have required documentation
completed and signed by the local fire authority (fire
department notification form) on file at the facility and
available for review by the Division of Fire Safety inspector.
(O) Facilities served by a volunteer or membership fire
department shall be a member in good standing with the
fire department. A copy of the membership or receipt for
membership shall be on file at the facility and available for
review.
(P) The facility shall, as soon as possible, no later than the
following business day, report any fire in the facility to the
Division of Fire Safety and the Department of Mental Health.
(Q) The Division of Fire Safety may make additional
requirements that provide adequate life safety protection if it
is determined that the safety of the occupants is endangered.
Every building or structure shall be constructed, arranged,
equipped, maintained, and operated to avoid danger to the
lives and safety of its occupants from fire, smoke, fumes, or
resulting panic during the period of time necessary for escape
from the building.
(R) Prior to new construction, remodeling existing structures,
and any structural alterations to existing facilities, the provider
shall submit two (2) copies of plans and specifications prepared
to scale for review and approval. One (1) copy shall be
submitted to the Department of Mental Health’s Licensure
and Certification Unit; the second copy to the Division of
Fire Safety. The plans shall include a narrative indicating
the utilization of each area of the facility. The architect
or contractor shall certify in writing that the plans are in
compliance with these certification rules. The provider shall
not begin construction until the plans have been reviewed
and approved by the Division of Fire Safety. All plans for new
construction, remodeling, or additions shall comply with the
Americans with Disabilities Act, Accessibility Guidelines.
(S) During the construction or remodeling process, the
provider shall request a framing and wiring inspection and an
inspection for the rough-in wiring for the fire alarm system by
the Division of Fire Safety before the walls are enclosed. Failure
to request these inspections in a timely manner may result in
an unapproved fire inspection from the Division of Fire Safety.
(T) The ceiling height in all facilities shall be a minimum of
seven feet six inches (7'6"). An allowance will be made by the
Division of Fire Safety inspector for some areas that are below
seven feet six inches (7'6") for the installation of ductwork and
plumbing, with no part of the ceiling less than six feet eight
inches (6' 8").
(U) Facilities shall comply with all local building codes, fire
codes, and ordinances.
(V) The latest edition of the National Fire Protection
Association (NFPA), Chapter 101, Life Safety Code prevails in the
interpretation of these rules.
(W) Each facility-based day habilitation and employment
service setting shall be inspected at least once annually by a
Division of Fire Safety inspector. The Department of Mental
Health will initiate the fire safety inspection. If a facility
is found out of compliance with the fire safety rules, the
department will apply procedures for achieving compliance as
promulgated under 9 CSR 45-5.060.
(2) Means of Egress Requirements.
(A) Each floor occupied in the facility shall have not less
than two (2) remotely located means of egress. Each exit door
in existing approved facilities shall not be less than thirtytwo inches (32") wide. All exit doors in new construction and
facilities approved for service delivery after the effective date
of this rule shall be a minimum of thirty-six inches (36") wide.
(B) No door in the path of travel to the means of egress
shall be less than thirty-two inches (32") wide in an approved
existing facility.
(C) At no time shall the occupants of the facility exit through
a bathroom, storage room, furnace room, kitchen, garage,
or any other room deemed hazardous by the Division of Fire
Safety inspector.
(D) All exit doors shall swing in the direction of egress travel
and have door closures attached. In smaller facilities that care
for ten (10) or fewer individuals, the exit doors may swing
inward providing all of the individuals are ambulatory. Door
closures are not required in smaller facilities.
(E) Emergency lighting that has a battery backup shall be
installed to light the path of egress. The location and number
of emergency lights shall be determined by the Division of Fire
Safety. These lights shall be tested monthly and documentation
kept indicating what lights are tested and the date and name
of the person performing the test.
(F) Lighted exit signs with a battery backup shall be installed
above exit doors and as needed throughout the facility to
direct the occupants to the exits. Lighted exit signs shall be
tested monthly and documentation kept indicating what lights
are tested and the date and name of the person performing
the test.
(G) No locks that require a key or special knowledge to unlock
the lock from the inside shall be allowed. Delayed egress locks
complying with section 7.2.1.6.1 of the 2012 edition NFPA 101 are
permitted, provided that no more than one (1) such device is
located in any egress path.
(H) Overhead garage doors are not recognized as exit
doorways.
(I) Mirrors shall not be placed on exit doors or adjacent to any
exit in such a manner to confuse the direction of the exit. All
exit doors shall be readily recognizable.
(J) All hallways shall have a clear width of at least thirty-six
inches (36") wide and shall be kept free of all articles that might
impede the occupants’ evacuation from the home.
(K) Dead-end corridors/hallways shall not exceed twenty feet
(20').
(L) All facilities that have a set of stairs or use stairs as an
exterior fire escape shall be constructed as follows:
1. All stairs shall be at least thirty-six inches (36") wide. Fire
escapes shall be constructed of noncombustible materials;
2. A maximum rise of eight inches (8");
3. A minimum tread of nine inches (9");
4. A maximum height between landings of twelve feet
(12');
5. A minimum landing size of forty-four inches (44");
6. Handrails placed on both sides of sturdy construction
and positioned thirty-four to thirty-eight inches (34"–38")
above the tread;
7. An outside diameter of the handrails of at least one and
one-fourth inches (1 1/4") and no greater than two inches (2")
in size;
8. Handrails with a clearance of at least one and one-half
inches (1 1/2") between the handrail and the wall or upright to
which it is attached; and
9. Spiral staircase or winder is not permitted.
(M) Every ramp used in the component of the means of
egress shall be a minimum of forty-four inches (44") wide, and
have landings at the top and bottom being the same width as
the ramp. Ramp height shall comply with the following:
1. Ramps less than three inches (3”) in height have a slope
of one inch (1") per eight inches (8") of run;
2. Ramps with a height of three to six inches (3"–6") have a
slope of one inch (1") per ten inches (10") of run; and
3. Ramps with a height greater than six inches (6") have a
slope of one inch (1") per twelve inches (12") of run.
(N) All ramps shall have a slip-resistant surface and be
designed so that water or snow does not accumulate on their
surface.
(O) All ramps over ten inches (10") in height shall have
guardrails and handrails on both sides.
(3) Windows for Emergency Rescue and Ventilation.
(A) Every room or space greater than three hundred (300)
square feet used by individuals shall have at least one (1)
outside window for emergency rescue and ventilation. The
window shall comply with the following:
1. Is operable from the inside without the use of tools;
2. Provides a clear opening of at least twenty inches (20")
wide, twenty-four inches (24") in height, and has a total clear
opening space no less than 5.7 square feet in size;
3. The bottom of the window opening is no more than
forty-four inches (44") above the floor;
4. Any latching device is operated easily;
5. Provides a clear opening that is a rectangular solid, with
a minimum width and height that provides the required 5.7
square feet opening and a minimum depth of twenty inches
(20") to allow passage through the opening;
6. The windows shall be accessible by the fire department
and open into an area having access to a public way.
(B) Subsection (3)(A) does not apply in the following situations:
1. In buildings protected throughout by an approved,
supervised automatic sprinkler system;
2. When the room or space has a door leading directly to
the outside of the building; or
3. If it is an interior room greater than three hundred (300)
square feet in size and has two (2) remotely located means of
egress and the egress doors are a minimum of thirty-six inches
(36") wide and swings in the direction of egress.
(4) Travel Distance to Exits.
(A) The travel distance between any room door intended
as an exit access or an exit shall not exceed one hundred feet
(100').
(B) The travel distance between any point in a room and an
exit shall not exceed one hundred fifty feet (150').
(C) The travel distance in (A) and (B) above shall be permitted
to be increased by fifty feet (50') in buildings protected
throughout by a supervised automatic sprinkler system that is
approved by the Division of Fire Safety inspector, based on the
National Fire Protection Association Standards for Sprinkler
Systems.
(5) Protection.
(A) Any vertical openings and stairwells shall be enclosed
and protected with a one- (1-) hour fire barrier and self-closing
device attached to the door.
(B) All furnace rooms, rooms containing water heaters, boiler
rooms, laundry rooms, and storage rooms shall be separated
from the remainder of the building by construction having not
less than a one- (1-) hour fire resistance rating. All doors to these
rooms shall have a self-closing device attached and a one- (1-)
hour fire resistive rating. The one- (1-) hour rating required for
these rooms or areas are not required if the facility installs a
one and three quarters inch (1 3⁄4") thick solid core wood door or
a twenty (20) minute fire rated door with a self-closure device
installed and an automatic sprinkler head supplied by the
domestic water supply or has an approved automatic sprinkler
system. A fire alarm initiating device shall be installed in these
rooms or areas. Before approval of the sprinkler installation
using plastic pipe the provider must present documentation
the pipe (minimum 1⁄2 inch diameter) and fittings are tested
and approved to the 1881 or 1887 standard for use in sprinkler
applications. If the sprinkler option is chosen, the above
appliances must be enclosed in a smoke resistant enclosure.
The door to these rooms shall be a minimum of one and three
quarters inch (1 3⁄4") solid bonded wood core door with a self-
closing device or a twenty minute fire rated door. No open
penetrations including combustion air or return air vents are
allowed to penetrate these enclosures or doors. Louvers that
close on activation of the fire alarm or smoke detectors are
allowed.
(C) Facility-based day habilitation and employment service
settings shall be separated from other occupancies in the same
building in accordance with the following:
Use Group
Fire Wall Separation in Hours
Place of assembly
2
Business
1
Mercantile
2
Institutional restrained
1
Hotels or dormitories
2
(6) Interior Finish.
(A) Interior wall and ceiling finishes throughout shall be a
minimum Class B finish, as specified in the definition section
of these fire safety rules. Textile material having a napped,
tufted, looped, woven, non-woven, or similar surface shall not
be applied to walls or ceilings. Foam plastic materials or other
highly flammable or toxic materials shall not be used as an
interior wall, ceiling, or floor finish.
(B) All wall studs, ceiling joists, and floor joists shall be
covered with a minimum of Class B finish, and no exposed
studs or joists shall be allowed.
(C) Hangings or draperies shall not be placed over exit doors
or be located to conceal or obscure any exit. All other hangings
and draperies shall be treated with a flame retardant material
with verification to this effect on file for the Division of Fire
Safety inspector to review. An exception can be made for
window valances and shall be noted by the inspector on the
fire inspection survey.
(7) Detection, Alarms, Extinguishment.
(A) All facility-based day habilitation and employment
service settings programs serving forty-nine (49) people or
less shall have smoke detectors installed on each level, in all
occupied spaces, storage rooms, and throughout all corridors
and in all other locations as deemed necessary by the Division
of Fire Safety inspector. All smoke detectors shall be powered
by the building’s electrical system and have a nine- (9-) volt
battery backup and be interconnected. Smoke detectors shall
be installed and arranged so that the activation of any smoke
detector causes the operation of an alarm in all detectors
that is clearly audible throughout the building, including in
bathrooms, corridors, and activity rooms, and above the noise
of radios, televisions, and noises of normal activity.
(B) All facility-based day habilitation and employment service
settings programs serving fifty (50) people or more shall have a
full coverage electrical fire alarm system. Pull stations shall be
mounted at each exit door, and horns/strobes shall be installed
throughout the facility. Smoke detectors shall be installed
in all rooms, throughout all corridors, in all living spaces,
storage rooms, and offices. Additional smoke detectors may
be required by the Division of Fire Safety inspector as deemed
necessary. Heat detectors shall be installed in all mechanical
rooms, kitchens, laundry rooms, closets, and throughout the
attic. The battery backup control panel shall be Underwriters
Laboratories, Inc. (UL) or Factory Mutual (F.M.) listed and
installed on a dedicated circuit in the breaker box. The fire
alarm system shall be installed and maintained in accordance
with the NFPA 72 Fire Alarm Code and in good working order.
(C) The fire alarm system shall be monitored by a monitoring
company or transmitted directly to the fire department when
fifty (50) or more individuals are present.
(D) All facilities shall have the fire alarm system tested,
inspected, and approved annually by a fire alarm company in
accordance with the NFPA 72 Fire Alarm Code. A copy of the
test report and approved inspection report of the system shall
be kept on file at the facility for review by the Division of Fire
Safety inspector and the department.
(E) Occupant notification shall be provided automatically
without delay. Pre-signal systems shall be prohibited.
(F) Any facility that has hearing-impaired occupants shall
make adequate provisions so that the activation of any fire
alarm system shall notify the occupants of the building.
The Division of Fire Safety inspector may require additional
requirements for the hearing-impaired occupants to insure
adequate modification.
(G) All smoke detectors that are ten (10) years old or older shall
be replaced with new smoke detectors of the same style. The
new smoke detectors shall have the installation date written on
the side of the detector for the Division of Fire Safety inspector
to reference. All smoke detectors that are connected to a fire
alarm system shall be replaced after ten (10) years of service,
or recalibrated by the smoke detector’s manufacturer. If the
smoke detectors are recalibrated, temporary smoke detectors
shall be installed so that the fire alarm system continues
working properly and providing protection to the occupants
while the original smoke detectors are being serviced.
(H) Facilities using any equipment or appliances using
wood or fossil fuel that pose a potential carbon monoxide
risk, including facilities with attached garages, shall install a
carbon monoxide detector(s). The detector(s) shall be installed
according to the manufacturer’s instructions. The Division of
Fire Safety may require additional carbon monoxide detectors
if the Division of Fire Safety inspector determines that the
safety of the occupants is endangered.
1. Carbon monoxide detectors shall be in good operating
condition. If a battery-operated detector is not operational, the
facility shall install a detector that is powered by the building’s
electrical system with a battery backup.
2. If an elevated carbon monoxide level is detected during
a fire inspection, the facility shall have all gas-fired appliances
checked by a heating and air conditioning company to identify
the source of the carbon monoxide. Until the facility has
documentation on file at the facility verifying that all gas-fired
appliances were checked by a heating and air conditioning
company and are in safe working order, and the facility is
determined safe by the Division of Fire Safety inspector, the fire
inspection shall not be approved.
3. If a level of carbon monoxide is determined that
endangers the lives of the occupants in care, the Division of
Fire Safety inspector shall take measures necessary to protect
the occupants. This may include evacuation of the building or
closing the facility. The facility shall obtain and have on file at
the facility, documentation verifying all gas-fired appliances
were checked by a heating and air conditioning company and
are in safe working order. The facility shall be reinspected by
the Division of Fire Safety inspector and determined safe before
the occupants can return to the building or the facility can
reopen.
(I) At least one (1) portable (five pound (5 lb)) 2A–10B:C
fire extinguisher shall be required in all facilities. One (1)
fire extinguisher shall be located in the kitchen. Additional
fire extinguishers shall be placed throughout the facility,
with a travel distance no greater than seventy-five feet (75')
between fire extinguishers. Additional fire extinguishers may
be required by the Division of Fire Safety inspector depending
on the floor plan arrangement of space and the number of
levels used.
(J) Fire extinguishers shall be installed and maintained
according to the instructions of the Division of Fire Safety
inspector and inspected and approved annually by a fire
extinguisher company. Documentation of the inspection and
approval shall be on file at the facility and available for review
by the Division of Fire Safety inspector.
(8) Heating, Ventilating, Air Conditioning, and Mechanical
Equipment.
(A) Unvented fuel-fired room heaters, portable electric space
heaters and floor furnaces shall not be permitted for use.
(B) No facility shall be allowed to heat the facility with
a wood burning stove, fireplace, or wood burning furnace
located inside of the structure.
(C) All gas and electric heating equipment shall be equipped
with thermostatic controls. All water heaters, if gas fired, shall
have the exhaust properly vented with galvanized pipe with
screws at all joints or with a material recommended by the
manufacturer. All water heaters shall have a properly sized
pressure relief valve installed with a drip leg. The drip leg
pipe on the pressure relief valve shall extend to approximately
six inches (6") above the floor and shall be of rigid material
such as copper or black iron pipe. Chlorinated polyvinyl
chloride (CPVC) or PVC pipe can only be used if manufactured
specifically for use on drip legs. No drip leg may be reduced in
size from the opening of temperature and pressure valve.
(D) Facilities with a water heater two hundred thousand
British thermal units (200,000 Btus) per hour input or larger,
or that is heating with a boiler, shall have a valid permit from
the Division of Fire Safety posted on the premises. A copy of the
permit shall be kept on file at the Division of Fire Safety.
(E) All furnace rooms shall be properly vented. Furnace
flue pipes shall be constructed of galvanized pipe or material
recommended by the manufacturer. All galvanized pipe shall
be secured by screws at every joint in the pipe.
(F) All joints in the gas supply pipe shall be located outside of
the furnace cabinet housing.
(G) Gas shutoff valve shall be located next to all gas
appliances, furnaces, hot water heaters.
(H) All furnaces shall be equipped with an electrical fused
switch to protect the unit from electrical overloading and to
disconnect the electrical supply.
(I) If a furnace or water heater is located inside a garage, the
burner or ignition source shall be at least eighteen inches (18")
above the finished floor and enclosed inside a fire resistant
room having a fire rating of thirty (30) minutes. The door to
this room shall also have a fire rating of thirty (30) minutes and
have a door closure attached. Open penetrations, including
combustion air or return air vents, shall not be allowed to
penetrate these enclosures or doors. Louvers that close on
activation of the fire alarm or smoke detectors are allowed.
(J) All furnace rooms and rooms containing the water heater
shall have adequate combustion air for the units. The vent
size opening for the combustion air shall be measured at
one (1) square inch per one thousand (1,000) Btus input if the
combustion air is drawn from inside the structure and one
(1) square inch per four thousand (4,000) Btus input if the air
is drawn from outside of the structure. There shall be two (2)
combustion air vent openings in each furnace room, one (1)
located at the lower level and the other at the upper level.
Combustion air or return air vents shall not penetrate the rated
or smoke enclosure.
(K) One (1) combustion air vent opening shall be permitted
if the vent opening communicates directly to the outside of
the structure. This opening shall be one (1) square inch per
three thousand (3,000) Btus input of the total gas appliances
located in this room. The gas appliances must be installed per
manufacturer’s instructions and have the proper clearance
around the unit or a minimum of one inch (1") from the sides
and back, and six inches (6") from the front of the unit.
(L) Air conditioning, heating, ventilating ductwork, and
related equipment shall be installed in a safe manner and be
in good operating condition as determined by the Division of
Fire Safety.
(M) All elevators shall be inspected bi-annually by a state
licensed elevator inspector and shall obtain an annual state
operating permit form from the Division of Fire Safety and post
it as required.
(N) If any combustibles are stored in a furnace room, they
must be enclosed in a metal container.
(9) Electrical Services.
(A) Electrical wiring shall be installed and maintained in
good working order. If the Division of Fire Safety inspector
considers the wiring to be unsafe for the occupants or it is
installed improperly, an inspection by a licensed electrician
may be required prior to fire safety approval. The inspection
by the licensed electrician shall be based on National Fire
Protection Association, Chapter 70, National Electrical Code.
(B) No electrical extension cords will be allowed, unless
approved in writing by the Division of Fire Safety inspector.
(10) Equivalency Concepts. Nothing in this rule is intended to
prevent the use of systems, methods, or devices of equivalent
or superior quality, strength, fire resistance, effectiveness,
durability, and safety as alternatives required by this rule. These
alternatives may be used only if technical documentation to
demonstrate equivalency and the system, method, or device is
submitted and approved by the Missouri Division of Fire Safety.
AUTHORITY: section 630.655, RSMo 2016.* Original rule filed Sept.
5, 2003, effective April 30, 2004. Amended: Filed March 20, 2018,
effective Nov. 30, 2018.
*Original authority: 630.655, RSMo 1980.