9 CSR 45-5.130
Fire Safety for Group Homes Serving 4–9 People
PURPOSE: This rule establishes fire safety requirements for group
homes serving four to nine (4–9) people funded through the
Medicaid home and community-based waiver. This rule does
not apply to individual supported living in private residences.
The department delegates its authority for fire safety inspections
under this rule to the Department of Public Safety, Division of Fire
Safety.
(1) General Requirements.
(A) The staff shall conduct at least one (1) fire drill per month
and one (1) natural disaster drill per quarter, with a minimum of
one (1) fire and one (1) natural disaster drill per year conducted
while the individuals are sleeping. A drill must be conducted
within one (1) week of the arrival of a new individual. The
staff shall maintain a written record at the facility of the date,
type of drill, time required to evacuate the building, whether
the evacuation was completed, notation of any problems
evacuating, and number of occupants present during the drill.
(B) Unscheduled drills shall be held at the Division of Fire
Safety inspector’s discretion.
(C) During severe weather, fire drills may be postponed.
(D) Each fire drill shall evacuate all persons from the
building, or evacuate to an area of refuge and defend in place
and each fire drill shall be conducted as follows:
1. Drills simulate an actual fire condition;
2. Occupants (referred to hereafter as “individuals”) and
staff members do not obtain clothing or personal effects after
the alarm has sounded;
3. The individuals and staff members proceed to a
predetermined point outside the building that is sufficiently
remote to avoid fire danger, or in case of natural disaster drill
to a predetermined point inside of the building; and
4. Individuals and staff members remain in place until a
recall is issued or until they are dismissed.
5. Exception. If there is potential harm to residents during
drills because a resident is medically fragile, the provider may
arrange the drill to not involve the medically fragile. However,
all individuals who are medically fragile must participate in
a drill at least once per year. This must be documented in the
home.
(E) No window in a facility shall have bars or any other item
placed over them in a stationary manner that would impede a
rescue or evacuation.
(F) All flammable/combustible liquids, matches, toxic
cleaning supplies, poisonous materials, or other hazardous
items shall be stored so as to be inaccessible to the occupants
if the occupants cannot handle the materials safely. If there
are firearms and/or ammunition on the premises, they shall be
kept in a locked space without access by individuals.
(G) Clothes dryers shall be vented to the outside or as
recommended by the manufacturer and maintained properly.
(H) The house numbers shall be plainly visible from the street
in case of emergency, at least four inches (4") in height and a
contrasting color with the building.
(I) Good housekeeping practices ensuring fire safety will be
maintained daily.
(J) Stairways, walks, ramps, and porches shall be kept free of
ice and snow.
(K) Fresh-cut Christmas trees shall not be used unless they
are treated with a flame resistant material and documentation
of the treatment is on file at the facility and available for review
by the Division of Fire Safety inspector.
(L) Candles and other devices that have an open flame shall
not be used indoors. However, short-term supervised use of
candles for special occasions or dinners is permitted.
(M) The facility may use a cellular phone when all of the
following conditions are met:
1. The phone must always have a signal;
2. The phone must always be charged;
3. The phone must be able to make and receive normal
calls;
4. The phone must remain at the facility at all times; and
5. The emergency plan for the facility must address the use
of cellular phones.
(N) The facility shall notify the nearest fire department that
the facility is in operation and have required documentation
completed and signed by the local fire authority (fire
department notification form) on file at the facility and
available for review by the Division of Fire Safety inspector.
(O) Facilities served by a volunteer or membership fire
department shall be a member in good standing with the
fire department. A copy of the membership or receipt for
membership shall be on file at the facility and available for
review.
(P) The facility shall, as soon as possible but no later than
the following business day, report any fire in the facility to the
Division of Fire Safety and the Department of Mental Health.
(Q) The Division of Fire Safety may make additional
requirements that provide adequate life safety protection if it
is determined that the safety of the occupants is endangered.
Every building or structure shall be constructed, arranged,
equipped, maintained, and operated to avoid danger to the
lives and safety of its occupants from fire, smoke, fumes, or
resulting panic during the period of time necessary for escape
from the building.
(R) Prior to new construction, remodeling existing structures,
and any structural alterations to existing facilities, the provider
shall submit two (2) copies of plans and specifications prepared
to scale for review and approval. One (1) copy shall be
submitted to the Department of Mental Health’s Licensure
and Certification Unit, the second copy to the Division of
Fire Safety. The plans shall include a narrative indicating
the utilization of each area of the facility. The architect
or contractor shall certify in writing that the plans are in
compliance with these certification rules. The provider shall
not begin construction until the plans have been reviewed
and approved by the Division of Fire Safety. All plans for new
construction, remodeling, or additions shall comply with the
Americans with Disabilities Act, Accessibility Guidelines.
(S) During the construction or remodeling process, the
provider shall request a framing and wiring inspection and an
inspection for the rough-in wiring for the fire alarm system by
the Division of Fire Safety before the walls are enclosed. Failure
to have these inspections constitutes cause for disapproval by
the Division of Fire Safety.
(T) Facilities that were certified and areas approved for care
prior to the effective date of this rule shall have ceilings at
least seven feet (7') in height. Facilities initially certified and
areas initially approved for care on or after the effective date of
this rule shall meet all the requirements of this rule and shall
have ceilings at least seven feet, six inches (7'6”) in height. If
structural alterations are made in facilities certified prior to
the effective date of this rule, those facilities shall meet all
the requirements of this rule and shall have ceilings at least
seven feet, six inches (7'6") in height in the altered space.
Allowance will be made by the Division of Fire Safety inspector
for the installation of ductwork and plumbing. No more than
forty percent (40%) of the ceiling in each room shall be below
minimal height, with no portion of the ceiling lower than six
feet, eight inches (6' 8").
(U) Facilities shall comply with all local building codes, fire
codes, and ordinances.
(V) The latest edition of the National Fire Protection
Association (NFPA), Chapter 101, Life Safety Code prevails in the
interpretation of these rules.
(W) Each group home shall be inspected at least once
annually by a Division of Fire Safety inspector. The Department
of Mental Health will initiate the fire safety inspection. If a
facility is found out of compliance with the fire safety rules, the
department will apply procedures for achieving compliance as
promulgated under 9 CSR 45-5.060.
(2) Means of Egress Requirements.
(A) Each floor occupied in the home shall have not less than
two (2) remotely located means of egress. Required means of
egress shall not be a window. Each exit door shall not be less
than thirty inches (30") wide, except that newly constructed
doorways shall be at least thirty-six inches (36") wide.
(B) Individual sleeping rooms in all new group homes
certified after the effective date of this rule shall have two (2)
means of egress, or a primary means of egress and a means of
escape.
(C) Wheelchairs, walkers, and other support equipment shall
not be stored in corridors.
(D) No door in the path of travel to the means of egress
shall be less than thirty inches (30") wide. Except that newly
constructed doorways shall be at least thirty-six inches (36").
(E) No primary means of escape or planned exit shall lead
through a bathroom, storage room, furnace room, garage,
or any other room deemed hazardous by the fire inspector.
Exception: Kitchens shall not be considered hazardous
unless they have commercial stoves without extinguishing
equipment or other features that lend themselves to rapid fire
development.
(F) All required outside exit doors shall swing in the direction
of egress travel if there are more than six (6) individuals living
in the home and one (1) or more person(s) is non-ambulatory.
In other words, if there are six (6) individuals or less and all are
ambulatory, the required exit doors do NOT have to swing in
the direction of egress travel.
(G) Emergency lighting that has a battery backup shall
be installed to light the path of egress. The Division of Fire
Safety inspector shall determine the location and number of
emergency lights. Emergency lights shall be tested monthly
and documentation indicating which lights were tested, the
date tested, and the name of the person performing the test
kept for review by the Division of Fire Safety.
(H) No locks that require a key or special knowledge to
unlock the lock from the inside shall be allowed. Delayed
egress locks complying with section 7.2.1.6.1 of the 2012 edition
NFPA 101 are permitted, provided that no more than one (1)
such device is located in any egress path.
(I) Overhead garage doors are not recognized as exit
doorways.
(J) Mirrors shall not be placed on exit doors or adjacent to any
exit in such a manner to confuse the direction of the exit. All
exit doors shall be readily recognizable.
(K) All hallways shall have a clear width of at least thirty-six
inches (36") wide and shall be kept free of all articles that might
impede the occupants’ evacuation from the home.
(L) Dead-end corridors/hallways shall not exceed twenty feet
(20').
(M) Facilities initially certified and areas initially approved
on or after the effective date of this rule, shall meet the
following requirements. All facilities that have a set of stairs or
use stairs as a fire escape shall be constructed as follows:
1. All stairs shall be at least thirty-six inches (36") wide.
New fire escapes shall be constructed of noncombustible
materials. Existing fire escapes shall be of sturdy construction
and, at the discretion of the Division of Fire Safety, may be
required to be load tested;
2. A maximum rise of eight inches (8");
3. A minimum tread of nine inches (9");
4. A maximum height between landings of twelve feet
(12');
5. A minimum landing size of forty-four inches by fortyfour inches (44" × 44");
6. Handrails placed on both sides of sturdy construction
and positioned thirty-four to thirty-eight inches (34"–38")
above the tread;
7. An outside diameter of the handrails of at least one and
one-fourth inches (1 1/4") and no greater than two inches (2")
in size;
8. Handrails with a clearance of at least one and one-half
inches (1 1/2") between the handrail and the wall or upright to
which it is attached;
9. Spiral staircases or winders are not permitted.
(N) Every ramp used in the component of the means of egress
shall be a minimum of forty-four inches (44") wide, and have
landings at the top and bottom being the same width as the
ramp. Ramp height shall comply with the following:
1. Ramps less than three inches (3") in height have a slope
of one inch (1") per eight inches (8") of run;
2. Ramps with a height of three to six inches (3"–6") have a
slope of one inch (1") per ten inches (10") of run;
3. Ramps with a height greater than six inches (6") have a
slope of one inch (1") per twelve inches (12") of run.
(O) All ramps shall have a slip-resistant surface and be
designed so that water or snow does not accumulate on their
surface.
(P) All ramps over ten inches (10") in height shall have
guardrails and handrails on both sides.
(3) Travel Distance to Exits.
(A) The travel distance between any room door intended as
an exit access and an exit shall not exceed one hundred feet
(100').
(B) The travel distance between any point in a room and an
exit shall not exceed one hundred fifty feet (150').
(C) The travel distance between any point in a sleeping room
and an exit access door in that room shall not exceed fifty
feet (50'). Exception: The travel distance in (A) and (B) of this
subsection shall be permitted to be increased by fifty feet (50')
in buildings protected throughout by a supervised automatic
sprinkler system that is approved by the Division of Fire Safety
inspector, based on the National Fire Protection Association,
Standards for Sprinkler Systems.
(4) Protection.
(A) Vertical openings shall be protected so that no primary
means of egress is exposed to an unprotected vertical opening.
The vertical opening shall be considered protected if the
opening is cut off and enclosed in a manner that provides
a fire-resisting capability of not less than one- (1-) hour and
resists the passage of smoke. All doors or openings shall have
fire- and smoke-resisting capability equivalent to that of the
enclosure and shall be self-closing or automatic closing.
(B) Exception. Specific residential facilities that were certified
prior to the effective date of this rule with or without twenty-
(20-) minute fire barriers in interior stairways as required by
subsection (4)(A) shall be considered in compliance with current
requirements, unless renovations or significant changes have
occurred in the way the building is being used or the number
of residents is increased.
(C) All furnace rooms, rooms containing water heaters,
boiler rooms, storage rooms, laundry rooms, and all other
rooms or areas deemed hazardous by the Division of Fire
Safety inspector shall be separated from the remainder of the
building by a construction having not less than a one- (1-) hour
fire resistance rating. Doors to these rooms must be closed at
all times. Doors to these rooms shall also have a one- (1-) hour
fire resistance rating. The door(s) shall also have door closure(s)
attached.
(D) Exception: Specific residential facilities that were certified
prior to the effective date of this rule shall be considered in
compliance with subsection (4)(C) of this rule if the facility
installs a sprinkler head off the domestic water supply or
has an approved automatic sprinkler system and a fire alarm
initiating device shall be installed in the high hazard area.
(E) Exception. The one- (1-) hour fire resistance rating required
for rooms or areas listed in subsection (4)(C) of this rule is not
required if the facility installs a sprinkler head off the domestic
water supply or has an approved automatic sprinkler system
and a fire alarm initiating device shall be installed in the
high hazard area, and a one and three-fourths inches (1 3/4")
thick solid core door or a twenty- (20-) minute fire rated door
is installed with a self-closing device attached to prevent the
passage of smoke. Before approval of the sprinkler installation
using plastic pipe the provider must present documentation
the pipe and fittings are tested and approved to the 1881 or
1887 standard for use in sprinkler applications. If the sprinkler
option is chosen, the above appliances must be enclosed in
smoke resistant enclosures. The door to these rooms shall be a
minimum of one and three-fourths inches (1 3/4") solid bonded
wood core door with a self-closing device or a twenty minute
fire rated door. No open penetrations including combustion
air or return air vents shall be allowed to penetrate these
enclosures or doors. Louvers that close on activation of the fire
alarm or smoke detectors are allowed.
(F) Every unoccupied attic space shall be subdivided by draft
stops having a one- (1-) hour fire rating, into areas not to exceed
three thousand (3,000) square feet. Exception: Subdivisions
described in this subsection are not required if the space is
protected throughout by an approved, automatic sprinkler
system.
(5) Interior Finish.
(A) Interior wall and ceiling finishes throughout shall be a
minimum Class B finish, as specified in the definition section
of these fire safety rules. Textile material having a napped,
tufted, looped, woven, non-woven, or similar surface shall not
be applied to walls or ceilings. Foam plastic materials or other
highly flammable or toxic materials shall not be used as an
interior wall, ceiling, or floor finish.
(B) All wall studs, ceiling joists, and floor joists shall be
covered with a minimum of Class B finish, and no exposed
studs or joists shall be allowed.
(C) Hangings or draperies shall not be placed over exit doors
or be located to conceal or obscure any exit. All other hangings
and draperies shall be treated with a flame retardant material
with verification to this effect on file for the Division of Fire
Safety inspector to review. Exception shall be made for small
window valances. These exceptions shall be noted on the fire
inspection survey.
(6) Detection, Alarms, Extinguishment.
(A) Smoke detectors shall be installed in all sleeping rooms,
throughout all corridors, in all living spaces, storage rooms,
offices, and any other areas that are deemed necessary by the
Division of Fire Safety inspector. Smoke detectors shall be in
good operating condition and functional at all times. Smoke
detectors may be battery powered. However, if smoke detectors
are not operational during two (2) separate inspections, the
facility will be required to install smoke detectors that are
powered by the home’s electrical system and have a battery
backup. These detectors shall be interconnected so that the
activation of one (1) detector will cause an alarm in all
detectors. Smoke detectors that are not operational must be
documented on inspection surveys. All new construction or
facilities licensed and approved after the date of these rules
shall have smoke detectors powered by the building’s electrical
system, have a battery backup, and be interconnected so
activation of a single smoke alarm causes alarm in all smoke
detectors.
(B) All smoke detectors that are ten (10) years old or older
shall be replaced with new smoke detectors of the same style.
The new smoke detectors shall have the installation date
written on the side of the detector for the Division of Fire Safety
inspector to reference.
(C) All smoke detectors that are connected to a fire alarm
system shall be replaced after ten (10) years of service, or
recalibrated by the smoke detector’s manufacturer. If the
smoke detectors are recalibrated, temporary smoke detectors
shall be installed so that the fire alarm system continues
working properly and providing protection to the occupants
while the original smoke detectors are being serviced.
(D) Any residence that has hearing-impaired occupants
shall make adequate provisions so that the activation of any
fire alarm system shall notify the occupants of the home.
The Division of Fire Safety inspector may require additional
requirements for the hearing-impaired occupants to insure
adequate notification.
(E) Occupant notification shall be provided automatically
without delay. Pre-signal systems shall be prohibited.
(F) All homes with fire alarm systems shall continue to have
the fire alarm system tested, inspected, and approved annually
by a fire alarm company and a copy of the test report and
approval of the system kept on file at the residence for review
by the Division of Fire Safety inspector.
(G) Residences using any equipment or appliances using
wood or fossil fuel that pose a potential carbon monoxide
risk, including facilities with attached garages, shall install a
carbon monoxide detector(s). The detector(s) shall be installed
according to the manufacturer’s instructions. The Division of
Fire Safety inspector may require additional carbon monoxide
detectors if the Division of Fire Safety inspector determines
that the safety of the occupants is endangered.
1. Carbon monoxide detectors shall be in good operating
condition. If a battery operated detector is not operational, the
facility shall install a detector that is powered by the home’s
electrical system with a battery backup.
2. If an elevated carbon monoxide level is detected
during a fire inspection, the residence shall have all gasfired appliances checked by a heating and air conditioning
company to identify the source of the carbon monoxide. Until
the residence has documentation on file at the home verifying
that all gas-fired appliances were checked by a heating and air
conditioning company and are in safe working order, and the
facility is determined safe by the Division of Fire Safety, the fire
inspection shall not be approved.
3. If a level of carbon monoxide is determined that
endangers the lives of the occupants, the Division of Fire
Safety inspector shall take measures necessary to protect the
occupants. This may include evacuation of the home or closing
the residence. The residence shall obtain and have on file at the
home, documentation verifying that all gas-fired appliances
were checked by a heating and air conditioning company and
are in safe working order. The residence shall be reinspected
by the Division of Fire Safety inspector and determined safe
before the occupants can return to the home or the residence
can reopen.
(H) At least one (1) portable (five pound (5 lb)) 2A-10B:C
fire extinguisher shall be required in all homes. One (1) fire
extinguisher shall be located in the kitchen. Additional fire
extinguishers shall be placed throughout the home and the
travel distance shall be no greater than seventy-five feet (75')
between fire extinguishers. Additional fire extinguishers may
be required by the Division of Fire Safety depending on the
floor plan arrangement of space and the number of levels used.
(I) Fire extinguishers shall be installed and maintained
according to the instructions of the Division of Fire Safety
and inspected and approved annually by a fire extinguisher
company. Documentation of the inspection and approval shall
be on file at the facility and available for review by the Division
of Fire Safety inspector.
(J) Homes shall meet the following requirements of subsections
(6)(J) and (6)(K) of this rule. Homes using a commercial stove,
deep fryer, or two (2) home type ranges placed side by side,
shall be equipped with a range hood and extinguishing system
with an automatic cutoff of the fuel supply and exhaust system
in case of fire. The hood and hood extinguishment system shall
be inspected by a qualified technician to insure they are in
good working condition and installed/maintained correctly.
The technician shall base this inspection on National Fire
Protection Association, Chapter 96, Standard for Fire Protection
of Commercial Cooking Operations. Exceptions: 1) Home type
ranges separated by an eighteen inch (18") cabinet shall not
be required to have an extinguishing system installed above
them. 2) Facilities that cook on a home type range with no
more than four (4) burners and/or grill, does not need to install
a fire extinguishing system above the range.
(K) The range hood fire extinguishment system shall be
connected to the control panel of the fire alarm system. The
activation of the range hood fire extinguishment system
shall cause the fire alarm system to activate throughout the
building.
(7) Heating, Ventilating, Air Conditioning, and Mechanical
Equipment.
(A) Unvented fuel-fired room heaters, portable electric space
heaters and floor furnaces shall not be permitted for use.
(B) No facility shall be allowed to heat the home with a wood
burning stove, fireplace, or wood burning furnace located
inside of the structure as a primary source of heat. Fireplaces
need to be approved for use by the Division of Fire Safety
inspector. If the fireplace is approved for use all chimneys shall
be inspected annually and cleaned if necessary by a qualified
technician or company, with documentation kept for review
by the Division of Fire Safety.
(C) All gas and electric heating equipment shall be equipped
with thermostatic controls. All water heaters, if gas fired, shall
have the exhaust properly vented with galvanized pipe with
screws at all joints or with a material recommended by the
manufacturer. All water heaters shall have a properly sized
pressure relief valve installed with a drip leg. The drip leg
pipe on the pressure relief valve shall extend to approximately
six inches (6") above the floor and shall be of rigid material
such as copper or black iron pipe. Chlorinated polyvinyl
chloride (CPVC) or PVC pipe can only be used if manufactured
specifically for use on drip legs. No drip leg may be reduced in
size from the opening of temperature and pressure valve.
(D) Facilities with a water heater two hundred thousand
British thermal units (200,000 Btus) per hour input or larger, or
that are heating with a boiler, shall have a valid permit from
the Division of Fire Safety posted on the premises. A copy of the
permit shall be kept on file at the Division of Fire Safety.
(E) All furnace rooms shall be properly vented. Furnace
flue pipes shall be constructed of galvanized pipe or material
recommended by the manufacturer. All galvanized pipe shall
be secured by screws at every joint in the pipe.
(F) All joints in the gas supply pipe shall be located outside of
the furnace cabinet housing.
(G) A gas shutoff valve shall be located next to all gas
appliances, furnaces, and water heaters.
(H) All furnaces shall be equipped with an electrical fused
switch to protect the unit from electrical overloading and to
disconnect the electrical supply.
(I) If a furnace or water heater is located inside a garage, the
burner or ignition source shall be at least eighteen inches (18")
above the finished floor and enclosed inside a fire resistant
room having a fire rating of thirty (30) minutes. The door to
this room shall also have a minimum thirty- (30-) minute fire
rating and have a door closure attached. Open penetrations,
including combustion air or return air vents, shall not be
allowed to penetrate these enclosures or doors. Louvers that
close on activation of the fire alarm or smoke detectors are
allowed.
(J) All furnace rooms and rooms containing the water heater
shall have adequate combustion air for the units. The vent
size opening for the combustion air shall be measured at
one (1) square inch per one thousand (1,000) Btus input if the
combustion air is drawn from inside the structure and one
(1) square inch per four thousand (4,000) Btus input if the air
is drawn from outside of the structure. There shall be two (2)
combustion air vent openings in each furnace room, one (1)
located at the lower level and the other at the upper level.
Combustion air or return air vents shall not penetrate the rated
or smoke enclosure.
(K) One (1) combustion air vent opening shall be permitted
if the vent opening communicates directly to the outside of
the structure. This opening shall be one (1) square inch per
three thousand (3,000) Btus input of the total gas appliances
located in this room. The gas appliances must be installed per
the manufacturer’s instructions with proper clearance or have
a minimum clearance of one inch (1") from the sides and back,
and six inches (6") from the front of the unit.
(L) Air conditioning, heating, ventilating ductwork, and
related equipment shall be installed in a safe manner and be
in good operating condition as determined by the Division of
Fire Safety inspector.
(M) Any furnace or air handling equipment that has airflow
of two thousand (2,000) cubic feet per minute or more, shall
have a fan shutdown switch that is interconnected with the
fire alarm system.
(N) All elevators shall be inspected bi-annually by a state
licensed elevator inspector and shall obtain an annual state
operating permit form from the Division of Fire Safety and post
it as required.
(O) If any combustibles are stored in a furnace room, they
must be enclosed in a metal container.
(8) Electrical Services.
(A) Electrical wiring shall be installed and maintained in
good working order. If the Division of Fire Safety considers
the wiring to be unsafe for the occupants or it is installed
improperly, an inspection by a licensed electrician may be
required prior to fire safety approval. The inspection by the
licensed electrician shall be based on National Fire Protection
Association, Chapter 70, National Electrical Code.
(B) No electrical extension cords will be allowed, unless
approved in writing by the Division of Fire Safety inspector.
Extension cords shall not be permanently affixed to the
structure or replace permanent wiring. Exception: The use
of Underwriters Laboratories, Inc. (UL) approved fused power
surge strips is acceptable.
(9) Equivalency Concepts. Nothing in this rule is intended to
prevent the use of systems, methods, or devices of equivalent
or superior quality, strength, fire resistance, effectiveness,
durability, and safety as alternatives required by this rule. These
alternatives may be used only if technical documentation to
demonstrate equivalency and the system, method, or device is
submitted and approved by the Missouri Division of Fire Safety.
AUTHORITY: section 630.655, RSMo 2016.* Original rule filed Sept.
5, 2003, effective April 30, 2004. Amended: Filed March 20, 2018,
effective Nov. 30, 2018.
*Original authority: 630.655, RSMo 1980.