10 CSR 20-8.150
Preliminary Treatment
PURPOSE: This rule specifies the minimum standards for the design of preliminary treatment units that are part of wastewater
collection and treatment systems. This rule is to be used with rules
10 CSR 20-8.110 through 10 CSR 20-8.210. It does not address all
aspects of design, and the design engineer may refer to other appropriate reference materials so long as these minimum standards
set forth in this rule are met.
Editor’s Note: The secretary of state has determined that the publication of this rule in its entirety would be unduly cumbersome
or expensive. The entire text of the material referenced has been
filed with the secretary of state. This material may be found at the
Office of the Secretary of State or at the headquarters of the agency
and is available to any interested person at a cost established by
state law.
(1) Applicability. Wastewater systems that utilize preliminary
treatment shall be designed based on criteria contained in this
rule, published standards, applicable federal and state requirements, standard textbooks, current technical literature, and applicable safety standards. In the event of any conflict between
the above criteria, the requirement in this rule shall prevail.
(A) This rule shall not apply to treatment units covered in 10
CSR 20-8.300.
(B) This rule shall not apply to treatment units covered in 10
CSR 20-8.500.
(2) General. All wastewater treatment facilities must have a
screening device, comminutor, or septic tank for the purpose
of removing debris and nuisance materials from the influent
wastewater.
(3) Grease Interceptors. Grease interceptors shall be provided
on kitchen drain lines from institutions, hospitals, hotels,
restaurants, schools, bars, cafeterias, clubs, and other establishments from which relatively large amounts of grease may
be discharged to a wastewater treatment facility owned by
the grease-producing entity. Grease interceptors are typically
constructed from fiberglass reinforced polyester, high density
polyethylene (HDPE), or concrete. For corrugated HDPE grease
interceptors, follow ASTM F2649 – 14 Standard Specification for
Corrugated High Density Polyethylene (HDPE) Grease Interceptor
Tanks, as approved and published September 1, 2014. For precast concrete grease interceptor tanks, follow ASTM C1613 – 17
Standard Specification for Precast Concrete Grease Interceptor
Tanks, as approved and published September 1, 2017. These
standards shall hereby be incorporated by reference into this
rule, as published by ASTM International, 100 Barr Harbor
Drive, PO Box C700, West Conshohocken, PA 19428-2959. This
rule does not incorporate any subsequent amendments or
additions.
(4) Screening Devices.
(A) General.
1. Freeze protection. All screening devices and screening
storage areas shall be protected from freezing.
2. Provisions shall be made for isolating or removing
screening devices from their location for servicing.
3. Safety.
A. Railings and gratings.
(I) Manually cleaned screen channels shall be protected by guard railings and deck gratings with adequate provisions for removal or opening to facilitate raking.
(II) Mechanically cleaned screen channels shall be
protected by guard railings and deck gratings. Give consideration to temporary access arrangements to facilitate maintenance and repair.
B. Mechanical devices.
(I) Mechanical screening equipment shall have adequate removal enclosures to protect facility personnel against
accidental contact with moving parts and to prevent dripping
in multi-level installations.
(II) A positive means of locking out each mechanical
device shall be provided.
(III) An emergency stop button with an automatic
reverse function shall be located in close proximity to the mechanical device.
C. Electrical Equipment, Fixtures, and Controls. Electrical
equipment, fixtures, and controls in screening area where hazardous gases may accumulate shall meet the requirements of
the electrical code referenced in 10 CSR 20-8.140(7)(B).
(B) Screens. Where two (2) or more mechanically cleaned
screens are used, the design shall provide for taking the largest
unit out-of-service without sacrificing the capability to handle
the average design flow. Where only one mechanically cleaned
screen is used, it shall be sized to handle the design peak instantaneous flow.
(5) Comminutors. Provisions for location and safety shall be in
accordance with screening devices, paragraph (4)(A)3. of this
rule.
(6) Grit removal facilities are required for wastewater treatment
facilities that—
(A) Utilize membrane bioreactors for secondary treatment;
(B) Utilize anaerobic digestion;
(C) Receive wastewater from combined sewers; or
(D) Receive wastewater from collection systems that receive
substantial amounts of grit.
AUTHORITY: section 644.026, RSMo 2016.* Original rule filed Aug.
10, 1978, effective March 11, 1979. Amended: Filed June 15, 2018,
effective Feb. 28, 2019.
*Original authority: 644.026, RSMo 1972, amended 1973, 1987, 1993.