10 CSR 20-8.180
Biological Treatment
PURPOSE: This rule specifies the minimum standards for the design of biological treatment that is part of wastewater collection
and treatment systems. This rule is to be used with rules 10 CSR
20-8.110 through 10 CSR 20-8.210. It does not address all aspects
of design, and the design engineer may refer to other appropriate
reference materials so long as these minimum standards set forth
in this rule are met.
Editor’s Note: The secretary of state has determined that the publication of this rule in its entirety would be unduly cumbersome
or expensive. The entire text of the material referenced has been
filed with the secretary of state. This material may be found at the
Office of the Secretary of State or at the headquarters of the agency
and is available to any interested person at a cost established by
state law.
(1) Applicability. Wastewater systems that utilize biological
treatment shall be designed based on criteria contained in this
rule, published standards, applicable federal and state requirements, standard textbooks, current technical literature, and applicable safety standards. In the event of any conflict between
the above criteria, the requirement in this rule shall prevail.
(A) This rule shall not apply to treatment units covered in 10
CSR 20-8.300.
(B) This rule shall not apply to treatment units covered in 10
CSR 20-8.500.
(2) Septic Tanks.
(A) A septic tank must have a minimum capacity of at least
one thousand (1,000) gallons.
(B) The septic tank shall be baffled.
(3) Recirculating Media Filters.
(A) Location. Recirculating media filters shall be located in
accordance with the minimum separation distances at 10 CSR
20-8.140(2)(C)(2).
(B) Filter Bed. A minimum of two (2) filter beds and a diversion box are required for all design flows.
(C) Dosing. Both timer and float switch controls are required;
timers are the primary method of operation and the float
switch control is a back-up.
(D) Loading. Hydraulic loading rate shall—
1. Follow the manufacturer’s recommendation for synthetic media filters; and
2. Not exceed three and one-half gallons per day per
square foot (3.5 gpd/sqft) for sand or rock filters.
(E) Media Characteristics. The media is any of a number of
physical structures whose sole purpose is to provide a surface
to support biological growth. Commonly used media includes
rock, gravel, and sand of various sizes, textile media, and peat.
Finely crushed limestone, dolomite, slag, any clay, limestone,
or appreciable amounts of organic material is not acceptable.
1. Rock, sand, and gravel media, when used shall–
A. Be a total of at least thirty-three inches (33") deep; and
B. Have at least twenty-four inches (24") of fine filtering
media.
(4) Trickling Filters.
(A) General. Trickling filters may be used for treatment of
wastewater amenable to treatment by aerobic biologic processes.
(B) Media.
1. Media depth shall—
A. Be a minimum depth of five feet (5') above the underdrains for rock filter media;
B. Be a minimum depth of ten feet (10') for manufactured filter media to provide adequate contact time with the
wastewater; and
C. Be no more than ten feet (10') for rock filter media.
2. Size and grading of rock and similar media shall—
A. Contain no more than five percent (5%) by weight
of pieces whose longest dimension is three (3) times the least
dimension;
B. Be free from thin elongated and flat pieces, dust, clay,
sand, or fine material; and
C. Conform to the following size and grading as shown
in Table 180-1, included herein, when mechanically graded
over vibrating screen with square openings.
3. Manufactured and synthetic media material shall—
A. Be used in accordance with all manufacturer’s recommendations;
B. Be insoluble in wastewater and resistant to flaking, spalling, ultraviolet degradation, disintegration, erosion,
aging, common acids and alkalis, organic compounds, and
biological attack;
C. Be evaluated to determine the suitability based on
experience with an installation treating wastewater under
similar hydraulic and organic loading conditions (include a
relevant case history involving the use of the synthetic media);
D. Have a structure able to support the synthetic media,
water flowing through or trapped in voids, and the maximum
anticipated thickness of the wetted biofilm;
E. Support the maintenance activities, unless a separate
provision is made for maintenance access to the entire top of
the trickling filter media and to the distributor; and
Table 180-1 Particle Size Distribution:
Screen Size
Percent Passing by Weight
4.5 inches
100%
3 inches
0-95%
2 inches
0-0.2%
1 inch
0 to 0.1%
F. Be placed with the edges matched as nearly as possible to provide consistent hydraulic conditions within the
trickling filter.
(C) Underdrainage System.
1. Hydraulic capacity. The underdrains shall be designed
with—
A. Slopes of at least one percent (1%);
B. Effluent channels that produce a minimum velocity of
two feet per second (2 fps) at average daily rate of application
to the filter;
C. Underdrainage system, effluent channels, and effluent pipe that permit free passage of air;
D. Drains, channels, and pipe so that not more than fifty
percent (50%) of their cross section area will be submerged
under the design peak hydraulic loading, including proposed
or possible future or recirculated flows.
(D) Forced Ventilation.
1. Forced ventilation for a trickling filter is required
when—
A. Designed for nitrification;
B. Designed with a media depth in excess of six feet (6');
or
C. Designed where seasonal or diurnal temperatures do
not provide sufficient difference between the ambient air and
wastewater temperatures to sustain passive ventilation.
2. Minimum design airflow rate to nitrify using a trickling
filter shall be the greater of—
A. Fifty pounds (50 lbs) of oxygen provided per pound
of oxygen demand at average organic loading, based on stoichiometry; or
B. Thirty pounds (30 lbs) of oxygen provided per pound
of oxygen demand at peak organic loading, based on stoichiometry.
(5) Activated Sludge.
(A) Basin lining. If using a synthetic liner, it shall be a minimum of thirty millimeters (30 mm) thick.
(B) Tank dimensions. Horizontally mixed aeration tanks shall
have a depth of not less than five and a half feet (5.5').
(C) High purity oxygen, when used and enclosed. An enclosed high purity oxygen exhaust system shall be provided to
collect and vent the reactor off-gases.
(6) Sequencing Batch Reactor (SBR).
(A) General. The minimum total basin volume shall be equal
to the design daily influent flow volume and either upstream
in-line or off-line storage is necessary to minimize influent flow
during settling and decanting.
(B) Design. A minimum of two (2) reactor basins shall be
installed.
(7) Membrane Bioreactor (MBR).
(A) General.
1. For wastewater treatment plants with a flow equal to or
greater than one hundred thousand gallons per day (100,000
gpd), the MBR process must be designed with a minimum of
two (2) membrane trains capable of treating the daily average
flow with one (1) membrane cassette out of service.
2. Design flux criteria must be satisfied with one (1) membrane module out-of-service (e.g., for external clean in place,
recovery cleaning, repair). For purposes of these criteria, a
membrane module is the smallest membrane unit capable of
separate removal from the tank while maintaining operation
of other membrane units in the same tank.
3. Membranes placed in the aeration basin(s) rather than a
separate membrane tank shall have—
A. Individual modules and individual diffusers that can
be removed separately for maintenance and repair; and
B. Aeration basin(s) volume sized for complete nitrification.
(B) Preliminary Treatment. Each system shall—
1. Be consistent with the membrane manufacturer recommendations;
2. Comply with 10 CSR 20-8.150(6) for grit removal;
3. Provide oil and grease removal when the levels in the
influent may cause damage to the membranes;
4. Provide a fine screen and high water alarm, designed to
treat peak hourly flow. Coarse screens followed by fine screens
may be used in larger facilities to minimize the complications
of fine screening; and
5. Comply with 10 CSR 20-8.150(4)(B) for reliability.
(C) Aeration. The aeration blowers must provide adequate air
for membrane scour and process demands.
(D) Redundancy. The facility shall have at least one (1) of the
following:
1. The ability to run in full programmable logic control
(PLC) or standby power mode in case of an automatic control
failure;
2. An operational battery backup PLC if manual control is
not possible; or
3. Sufficient standby power generating capabilities to provide continuous flow through the membranes during a power
outage (e.g., preliminary screening, process aeration, recycle/
RAS/permeate pumps, air scour, vacuum pumps) or an adequate method to handle flow for an indefinite period (e.g., private control of influent combined with contingency methods).
(E) Operations and Maintenance. The MBR design shall—
1. Include provisions to monitor membrane integrity;
2. Provide on-line continuous turbidity monitoring of
filtrate or an equivalent for operational control and indirect
membrane integrity monitoring for a treatment plant with
design average flow greater than or equal to one hundred
thousand gallons per day (100,000 gpd); and
3. Include provisions to remove membrane cassette for
cleaning considering the membrane cassette wet weight plus
additional weight of the solids accumulated on the membranes.
(8) Moving Bed Bioreactor (MBBR). A MBBR secondary treatment system shall provide upstream preliminary treatment
units capable of—
(A) Screening to reduce pass-through and suspended solids;
(B) Grit removal; and
(C) Oil and grease removal.
AUTHORITY: section 644.026, RSMo 2016.* Original rule filed Aug.
10, 1978, effective March 11, 1979. Amended: Filed June 15, 2018,
effective Feb. 28, 2019.
*Original authority: 644.026, RSMo 1972, amended 1973, 1987, 1993.