10 CSR 20-8.190
Disinfection
PURPOSE: This rule specifies the minimum standards for the
design of disinfection processes that are part of wastewater collection and treatment systems. This rule is to be used with rules
10 CSR 20-8.110 through 10 CSR 20-8.210. It does not address all
aspects of design, and the design engineer may refer to other appropriate reference materials so long as these minimum standards
set forth in this rule are met.
(1) Applicability. Wastewater systems that utilize disinfection
shall be designed based on criteria contained in this rule, published standards, applicable federal and state requirements,
standard textbooks, current technical literature, and applicable safety standards. In the event of any conflict between the
above criteria, the requirement in this rule shall prevail.
(A) This rule shall not apply to treatment units covered in 10
CSR 20-8.300.
(B) This rule shall not apply to treatment units covered in 10
CSR 20-8.500.
(2) General.
(A) Emergency Power. Disinfection and dechlorination processes, when used, shall be provided during all power outages.
For additional emergency power requirements, refer to the
provisions listed in 10 CSR 20-8.140(7).
(B) Secondary containment. Secondary containment shall
comply with the provisions listed in 10 CSR 20-8.140(9)(A)2.
(3) Chlorine Disinfection.
(A) Contact period. A minimum contact period of fifteen (15)
minutes at design peak hourly flow or maximum rate of pumpage shall be provided after thorough mixing.
(B) Gaseous Chlorine Housing.
1. Feed and storage rooms shall—
A. Have chlorine gas feed and storage rooms constructed of fire and corrosion resistant material;
B. Provide a gas-tight room to separate equipment from
any other portion of the building if gas chlorination equipment
or chlorine cylinders are to be in a building used for other
purposes;
C. Have smooth floor surfaces that are chemical resistant, impervious, and slip resistant. Floor drains are discouraged. Design floor drains, where provided, with the ability to
be plugged and sealed;
D. Have doors to this room that only open to the outside of the building, and are equipped with panic hardware.
Provide door locks to prevent unauthorized access, but do not
need a key to exit the locked room using the panic hardware;
E. Be well-lit with lights that are sealed so that they will
continue working during a chlorine leak. Comply with 10 CSR
20-8.140(7)(B), requirements for Class I, Division 2, Group D locations when selecting lighting and electrical equipment;
F. Be at ground level and permit easy access to all equipment;
G. Separate storage areas for one- (1-) ton cylinders from
the feed area; and
H. Have designated areas for “full” and “empty” cylinder
storage.
2. Heating and cooling.
A. Rooms containing disinfection equipment shall be
provided with a means of heating and cooling so that a temperature of at least sixty degrees Fahrenheit (60° F) and no
more than eighty-six degrees Fahrenheit (86°F) can be maintained.
B. Heating or air conditioning equipment provided for
the chlorinator room shall be separate from central heating
and air conditioning systems to prevent chlorine gas from entering the central system and central heating or cooling ducts
are not allowed to terminate or pass through a chlorinator
room.
3. Ventilation shall conform to the following:
A. Install forced mechanical ventilation to provide one
(1) complete fresh air change per minute when the chlorinator
room is occupied. Construct fans of chemical resistant materials and have chemical proof motors. Squirrel cage type fans
located outside the chlorinator room may be approved if the
fan housings and ducting are airtight and made of chlorine
and corrosion resistant material;
B. Locate the entrance to the air exhaust duct from the
room no more than twelve inches (12") off the floor. Locate the
point of discharge as not to contaminate the air inlet to any
buildings or present a hazard at the access to the chlorinator
room or other inhabited areas. Utilize louvers for air exhaust to
facilitate airtight closure;
C. Locate air inlets as to provide cross ventilation. Place
the outside air inlet at least three feet (3') above grade. Utilize
louvers for air inlets to facilitate airtight closure; and
D. Position the vent hose from the chlorinator to the
outside atmosphere above grade. Provide passive vent screens.
4. Electrical controls. Switches for fans and lights shall be
outside of the chlorinator room at the entrance.
5. Protective and respiratory gear. Where chlorine gas is
present the applicant shall comply with 10 CSR 20-8.140(9)(D)1.
(C) Alarm System. The applicant shall conform to 10 CSR 208.140(7)(C) and be responsible for specifying what the alarm
requirements are necessary to assure consistent disinfection in
compliance with the applicable bacteria limits and the disinfection residual limit in the effluent.
(D) Sampling Equipment. Sampling equipment shall be consistent with the requirements in 10 CSR 20-8.140(7)(F).
(4) Dechlorination.
(A) Containers. Dilution tanks and mixing tanks are required
when using dry compounds and may be necessary when using
liquid compounds to deliver the proper dosage.
(B) Mixing and Contact Requirements.
1. Mixing requirements. Solid dechlorination systems shall
not be located in the chlorine contact tank.
2. Contact time. A minimum of thirty (30) seconds for
mixing and contact time shall be provided at the design peak
hourly flow or maximum rate of pumpage.
(C) Housing Requirements.
1. Feed and storage rooms. The requirements for housing
sulfite gas equipment shall follow the same guidelines as for
chlorine gas. For specific details follow the provisions listed in
subsection (3)(B).
2. Protective and respiratory gear. See paragraph (3)(B)5.
of this rule.
(D) Alarm System. See subsection (3)(C) of this rule.
(E) Sampling Equipment. Sampling equipment shall be consistent with the requirements in 10 CSR 20-8.140(7)(F).
(5) Ultraviolet Disinfection.
(A) Dosage and System Sizing.
1. General. The UV dosage shall be based on the design
peak hourly flow, maximum rate of pumpage, or peak batch
flow.
2. Batch discharges. If no flow equalization is provided
for a batch discharger, the dosage shall be based on the peak
batch flow.
3. Bioassay. The UV system shall deliver the target dosage
based on equipment derating factors and, if needed, have the
UV equipment manufacturer verify that the scale up or scale
down factor utilized in the design is appropriate for the specific application under consideration.
4. The design delivered UV dosage for a wastewater treatment facility shall be a minimum of thirty thousand microwatt
seconds per centimeters squared (30,000 μW • s/cm2) based on
MS-2 phage inactivation.
(B) Design.
1. Open channel systems. The combination of the total
number of banks shall be capable of treating the design peak
hourly flow, maximum rate of pumpage, or peak batch flow.
2. Closed vessel systems. The combination of the total
number of closed vessels shall be capable of treating the design
peak hourly flow, maximum rate of pumpage, or peak batch
flow.
3. Cleaning. Closed vessel systems utilizing medium-pressure lamps shall be provided with an automatic cleaning system in order to prevent algae growth.
(C) Monitoring and Alarms.
1. The UV system must continuously monitor and display
at the UV system control panel the following minimum conditions:
A. The relative intensity of each bank or closed vessel
system;
B. The operational status and condition of each bank or
closed vessel system;
C. The ON/OFF status of each lamp in the system; and
D. The total number of operating hours of each bank or
each closed vessel system.
2. The UV system shall include an alarm system. Alarm
systems shall comply with 10 CSR 20-8.140(7)(C).
(D) Electrical Controls. For electrical controls, follow the
provisions listed in 10 CSR 20-8.140(7)(B) for electrical controls
requirements.
(E) Sampling Equipment. Sampling equipment shall be consistent with the requirements in 10 CSR 20-8.140(7)(F).
AUTHORITY: section 644.026, RSMo 2016.* Original rule filed Aug.
10, 1978, effective March 11, 1979. Amended: Filed June 15, 2018,
effective Feb. 28, 2019.
*Original authority: 644.026, RSMo 1972, amended 1973, 1987, 1993.
10
CSR
20-8.200
Wastewater
Treatment
Lagoons,
Wastewater Irrigation Alternatives, and Earthen Basins
PURPOSE: This rule specifies the minimum standards for the
design of lagoons and wastewater irrigation alternatives that are
part of wastewater collection and treatment systems. This rule is
to be used with rules 10 CSR 20-8.110 through 10 CSR 20-8.210. It
does not address all aspects of design, and the design engineer
may refer to other appropriate reference materials so long as these
minimum standards set forth in this rule are met.
PUBLISHER’S NOTE: The secretary of state has determined that
publication of the entire text of the material that is incorporated
by reference as a portion of this rule would be unduly cumbersome
or expensive. This material as incorporated by reference in this
rule shall be maintained by the agency at its headquarters and
shall be made available to the public for inspection and copying
at no more than the actual cost of reproduction. This note applies
only to the reference material. The entire text of the rule is printed
here.
(1) Applicability. Wastewater systems that utilize lagoons,
earthen basins, and wastewater irrigation alternatives shall be
designed based on criteria contained in this rule, published
standards, applicable federal and state requirements, standard
textbooks, current technical literature, and applicable safety
standards. In the event of any conflict between the above criteria, the requirement in this rule shall prevail.
(A) This rule shall not apply to treatment units covered in 10
CSR 20-8.300.
(B) This rule shall not apply to treatment units covered in 10
CSR 20-8.500.
(C) This rule shall not apply to lagoons or earthen basins built
to contain or control the release of stormwater only that does
not come in contact with process waste or process wastewater.
(D) This rule shall not apply to any earthen basin constructed
to retain and settle nontoxic, nonmetallic earthen materials
such as soil, silt, and rock.
(2) Alternative Design. The department may approve an alternative design, after public participation in accordance with 10
CSR 20-6.020, when it determines that the proposed alternative
design is as effective or more effective than the requirements
of this chapter and when compliance with the design requirements of this chapter would be unfeasible or impractical.
The owner of a project proposing an alternative design must
provide engineering justification to the department. The justification must—
(A) Be requested in writing;
(B) Be signed, sealed, and dated by a professional engineer
licensed in Missouri;
(C) Include an explanation of how compliance with a design
requirement of this chapter is unfeasible or impractical; and
(D) Include all pertinent facts, data, reports, and studies certifying the proposed alternative design will result in equivalent
or improved effectiveness compared to the minimum design
requirement in this chapter.
(3) Supplementary Field Data for the Facility Plan. The facility
plan shall contain pertinent information on location, geology,
soil conditions, area for expansion, and any other factors that
will affect the feasibility and acceptability of the proposed project, including the information required per 10 CSR 20-8.110. The
following information must be submitted:
(A) Lagoons and spray irrigation fields shall be located where
stormwater runoff from the watershed is minimized;
(B) Geohydrologic Evaluation. A geohydrologic evaluation
shall be requested from the department’s Missouri Geological
Survey on all new lagoons, lagoon major modifications,
earthen basins, earthen basin major modifications, new
wastewater irrigation sites, and subsurface absorption fields.
Supplemental information may be submitted for consideration
by the department.
1. Severe collapse potential. Lagoons and earthen basins
shall not be located in areas with a severe collapse potential
rating unless additional information supports an alternative
determination by the department for the proposed location;
(C) Soils Investigation. Detailed soils investigations and reports shall be submitted for facilities surface irrigating more
than twenty-four inches per year (24"/yr) and for all subsurface
absorption fields. Soils reports shall comply with 10 CSR 208.110(7);
(D) Where geosynthetic liners are used in storage or
treatment basins for wastewaters of an industrial nature, the
application shall—
1. Document that the liner or storage structure material is
capable of containing the wastewater for at least twenty (20)
years;
2. Specify repair or replacement procedures in the event of
leakage or damage to the seal; and
3. Include an evaluation of secondary containment or
leakage detection and collection devices for corrosive or
reactive wastewaters and for toxic materials.
(4) Basis of Design.
(A) Area and Loadings for Discharging Lagoons.
1. Lagoon design for BOD5 loadings shall not exceed thirtyfour pounds per day per acre (34 lbs/day/acre) at the three-foot
(3') operating depth in the primary cells.
2. Aerated lagoons. Aeration equipment shall be capable
of—
A. Maintaining the design level of dissolved oxygen
within a particular cell with one (1) unit in the cell out of
service;
B. Maintaining a minimum dissolved oxygen level of
two milligrams per liter (2 mg/L) in the lagoon at all times;
C. Delivering one and four-tenths pounds of oxygen per
pound of biochemical oxygen demand removed (1.4 lbs O2/1 lb
BOD); and
D. Delivering an additional four and sixth-tenths pounds
of oxygen per pound of ammonia nitrogen removal (4.6 lbs O2/1
lb NH3).
(B) Area and Loadings for Wastewater Irrigation Storage
Basins. Treatment prior to surface irrigation shall provide
performance equivalent to that obtained from a primary
wastewater lagoon cell designed and constructed in accordance
with section (5) of this rule, except that the lagoon depth may
be increased to include wastewater storage in addition to the
primary volume.
(5) Lagoon and Earthen Basin Construction Details.
(A) Embankments and Berms.
1. Berms shall be constructed of relatively impervious
material and compacted to at least ninety-five percent (95%)
maximum dry density test method to form a stable structure.
2. The minimum berm width shall be eight feet (8') to
permit access of maintenance vehicles.
3. Minimum freeboard shall be two feet (2').
4. An emergency spillway shall be provided that—
A. Prevents the overtopping and cutting of berms;
B. Is compacted and vegetated or otherwise constructed
to prevent erosion; and
C. Has the ability for a representative sample to be
collected, if discharging.
(B) Lagoon and Earthen Basin Bottom. Soil shall be compacted
with the moisture content between two percent (2%) below
and four percent (4%) above the optimum water content and
compacted to at least ninety-five percent (95%) maximum dry
density test method.
(C) Lagoon and Earthen Basin Seal.
1. The lagoon or earthen basin shall be sealed to ensure
that seepage loss is as low as possible and has a design
permeability not exceeding 1.0 x 10-7 cm/sec.
2. Soil seals. The minimum thickness of the compacted clay
liner must be twelve inches (12"). For permeability coefficients
greater than 1.0 × 10-7 cm/sec or for design average operating
depths over five feet (5'), such as an aerated lagoon system, the
following formula shall be used to determine minimum seal
thickness, Equation 200-1:
Equation 200-1
H × K
t = ______________________
5.4 × 10-7 cm/sec
where:
K = the permeability coefficient of the soil in question;
H = the design average operating depth of water in the lagoon
or earthen basin, excluding the inner berm depth; and
t = the thickness of the soil seal.
3. Synthetic liners. Synthetic seals thickness may vary
due to liner material, but the liner thickness shall be no less
than two-hundredths inch (.02") or twenty (20) mil and be the
appropriate material to perform under existing conditions.
4. Seep collars shall be provided on drainpipes where they
pass through the lagoon or earthen basin seal.
(D) Influent Lines.
1. Unlined corrugated metal pipe shall not be used due to
corrosion problems.
2. A manhole shall be installed with its invert at least six
inches (6") above the maximum operating level of the lagoon
or earthen basin, prior to the entrance into the primary cell,
to provide sufficient hydraulic head without surcharging the
manhole. For manhole installation, follow the provisions listed
in 10 CSR 20-8.120(4).
3. The influent line(s) shall be located along the bottom of
the lagoon or earthen basin so that the top of the pipe is just
below the average elevation of the lagoon or earthen basin
seal; however, there shall be an adequate seal below the pipe.
(6) Covers for Lagoon Retrofits.
(A) Lagoon covers shall be constructed with a minimum
thickness of two-thousandths inch (.002"), two (2) mil, or meet
the manufacturer’s recommendations, and be ultraviolet- and
weather-resistant.
(B) Trial seams shall be used to verify acceptable installation
techniques.
(C) The cover shall include a stormwater removal system that
conveys collected precipitation to sumps or includes drainage
areas in the membrane within the acceptable leakage rate to
allow stormwater to drain into the lagoon.
(7) Surface Irrigation of Wastewater.
(A) Site Considerations. For site considerations, follow the
provision in section (3) of this rule.
(B) Wetted Application Area. The wetted application area
is the land area that is normally wetted by wastewater
application. The wetted application area must be—
1. Located outside of flood-prone areas having a flood
frequency greater than once every ten (10) years;
2. Established—
A. At least one hundred fifty feet (150') from existing
dwellings or public use areas, excluding roads or highways;
B. At least fifty feet (50') inside the property line;
C. At least three hundred feet (300') from any sinkhole,
losing stream, or other structure or physiographic feature that
may provide direct connection between the ground water
table and the surface;
D. At least three hundred feet (300') from any existing
potable water supply well not located on the property.
Adequate protection shall be provided for wells located on the
application site;
E. One hundred feet (100') to wetlands, ponds, and
gaining streams (classified or unclassified; perennial or
intermittent); and
F. If an established vegetated buffer or the wastewater
is disinfected, the setbacks established in subsections (A)–(E)
of this section may be decreased if the applicant demonstrates
the risk is mitigated; and
3. Fenced, or if not fenced, provide in the construction
permit application or the facility plan, the—
A. Method of disinfection being utilized;
B. Suitable barriers in place; or
C. Details on how public access is limited and not
expected to be present.
(C) Preapplication Treatment. At a minimum, treatment
prior to irrigation shall provide performance equivalent to
that obtained from a primary wastewater lagoon cell designed
and constructed in accordance with sections (4) and (5) of this
rule, except that the lagoon depth may be increased to include
wastewater storage in addition to the primary volume.
1. The size of storage basins shall be based on the design
wastewater flows and net rainfall minus evaporation expected
for a one (1) in ten (10) year frequency for the storage period
selected and shall meet the minimum storage days listed
below.
A. Seventy-five (75) days for facilities located in Barry,
Barton, Bollinger, Butler, Cape Girardeau, Carter, Christian,
Dade, Dent, Douglas, Dunklin, Greene, Howell, Iron, Jasper,
Lawrence, Madison, McDonald, Mississippi, New Madrid,
Newton, Oregon, Ozark, Pemiscot, Perry, Reynolds, Ripley,
Scott, Shannon, Stoddard, Stone, Taney, Texas, Wayne, Webster,
and Wright counties.
B. Ninety (90) days for facilities located in Bates, Benton,
Camden, Cedar, Cole, Crawford, Dallas, Franklin, Gasconade,
Henry, Hickory, Jefferson, Laclede, Maries, Miller, Moniteau,
Morgan, Osage, Phelps, Polk, Pulaski, St. Charles, St. Clair, St.
Francois, St. Louis, St. Louis City, Ste. Genevieve, Vernon, and
Washington counties.
C. One hundred five (105) days for facilities located
in Audrain, Boone, Callaway, Carroll, Cass, Chariton, Clay,
Cooper, Howard, Jackson, Johnson, Lafayette, Lincoln, Monroe,
Montgomery, Pettis, Pike, Platte, Ralls, Randolph, Ray, Saline,
and Warren counties.
D. One hundred twenty (120) days for facilities located
in Adair, Andrew, Atchison, Buchanan, Caldwell, Clark, Clinton,
Daviess, DeKalb, Gentry, Grundy, Harrison, Holt, Knox, Lewis,
Linn, Livingston, Macon, Marion, Mercer, Nodaway, Putnam,
Schuyler, Scotland, Shelby, Sullivan, and Worth counties.
E. Seasonal facilities. For facilities that operate and
generate flows only from April through October season, a
minimum storage capacity of forty-five (45) days shall be
provided. For facilities that operate or generate flows only
from November through March, the minimum storage listed in
subsections (A)–(D) of this section is required.
(D) Application Rates and Soils Information. The application
rates for each individual site shall be based on topography, soils,
geology, hydrology, weather, agricultural practice, adjacent
land use, and application method. Application of wastewater
shall not be allowed during periods of ground frost, frozen soil,
saturated conditions, or precipitation events. In design of the
application rates, the following shall apply:
1. Do not exceed the hourly application rate at the design
sustained permeability rate except for short periods when
initial soil moisture is significantly below field capacity. Do
not exceed an hourly rate of one-half (1⁄2) the design sustained
permeability for slopes exceeding ten percent (10%);
2. Base the daily and weekly application rates on soil
moisture holding capacity, antecedent rainfall, and depth to
the most restrictive soil permeability.
A. For facilities applying at twenty-four inches per year
(24"/yr), the application rate cannot exceed one inch (1") per
day and three inches (3") per week.
B. For facilities applying above twenty-four inches per
year (24"/yr), the application rate cannot exceed the values
determined in the soils report and loading design. Follow the
provisions in 10 CSR 20-8.110(7), Soils Reports, for additional
information; and
3. Design the maximum annual application rate not
to exceed ten percent (10%) of the design sustained soil
permeability rate for the number of days per year when soils
are not frozen.
(E) The applicant shall defer the grazing of animals or
harvesting of forage crops, as listed below, following wastewater
irrigation, depending upon ambient air temperature and
sunlight conditions:
1. Fourteen (14) days from grazing or forage harvesting
during the period from May 1 to October 31 of each year; and
2. Thirty (30) days from grazing or forage harvesting
during the period from November 1 to April 30 of each year.
(F) Public Access Areas. Wastewater shall be disinfected prior
to irrigation (not storage) in accordance with 10 CSR 20-8.190.
1. The wastewater shall contain as few of the indicator
organisms as possible and in no case contain more than one
hundred twenty-six (126) Escherichia coliform colony forming
units per one hundred milliliters (126 cfu/100 ml);
2. The public shall not be allowed into an area when
irrigation is being conducted.
3. For golf courses utilizing wastewater, all piping and
sprinklers associated with the distribution or transmission of
wastewater shall be color-coded and labeled or tagged to warn
against the consumptive use of contents.
(G) Alarm System. An automatic notification alarm system
shall be installed on the pressure monitoring system, on each
pivot and pump system, and be capable of notifying an on-call
operator when a fault occurs in the system.
(8) Subsurface Absorption Systems.
(A) Site Restrictions.
1. Subsurface systems shall—
A. Exclude unstabilized fill and soils that have been
highly compacted and/or disturbed, such as old road beds,
foundations, or similar things;
B. Provide adequate surface drainage where slopes are
less than two percent (2%);
C. Provide surface and subsurface water diversion where
necessary, such as a curtain or perimeter drain; and
D. Have a ten-foot (10') buffer from the property line.
2. The vertical separation between the bottom of the drip
lines and/or the trench and a limiting layer, including but not
limited to bedrock, restrictive horizon, or seasonal high water
table, shall be no less than—
A. Twenty-four inches (24"); or
B. Twelve inches (12") for systems dispersing secondary
or higher quality effluent; or
C. Forty-eight inches (48") where karst features are
present.
(B) Preliminary treatment. Subsurface systems shall be, at a
minimum, preceded by preliminary treatment. For design of
a secondary treatment system, follow the provisions in 10 CSR
20-8.180 or section (4) of this rule.
(C) Loading rates shall not exceed the values assigned by the
site and soil evaluation.
(9) Low Pressure Pipe (LPP) Subsurface Systems.
(A) Design.
1. The LPP system shall be sized in accordance with the
following equations, Equation 200-2 and Equation 200-3:
Equation 200-2
Q
A = ______
LTAR
and Equation 200-3
A
L = ______
5 ft
where:
A = Minimum LPP soil treatment area (square feet (sq.ft))
L = Minimum total length of LPP trench (ft)
Q = Maximum daily wastewater flow (gallons per day (gpd))
LTAR = Long term acceptance rate (gpd/sq.ft). This is the lowest
reported LPP soil loading rate between the soil surface and
at least twelve inches (12") below the specified LPP trench
bottom, or as approved by the Missouri Department of Natural
Resources (department).
2. All network piping and low pressure distribution piping
and fittings with polyvinyl chloride (PVC) shall meet ASTM
Standard D 1785 Standard Specification for Poly(Vinyl Chloride)
(PVC) Plastic Pipe, Schedules 40, 80, or 120 as approved and
published August 1, 2015, or equivalent rated to meet or exceed
ASTM D2466 Standard Specification for Poly(Vinyl Chloride) (PVC)
Plastic Drain, Waste, and Vent Pipe and Fittings as approved and
published August 1, 2017. These standards are incorporated by
reference into this rule, as published by ASTM International,
100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA
19428-2959. This rule does not incorporate any subsequent
amendments or additions.
3. Manifold design shall address freeze protection while
assuring uniform distribution and to minimize drain down of
laterals into other laterals at a lower elevation between dosing
events.
(B) Dosage. The dosing frequency shall be based on the soils
report and the dosing volume in zoned systems.
(C) Orifices and Orifice Shielding.
1. The orifice number and spacing shall be designed to
provide a distribution of no more than six (6) square feet per
orifice with an orifice size of not less than one-eighth (1/8) inch.
2. The distal pressure shall be designed and maintained at
the end of each lateral to be no less than two feet (2 ft) (0.87
psi) when using three-sixteenth inch (3/16") or larger diameter
orifices, and no less than five feet (5 ft) (2.18 psi) when using
orifices smaller than three-sixteenth inch (3/16").
(10) Drip Dispersal Subsurface Systems.
(A) Design.
1. The location and size of the drains and buffers must
be factored into the total area required for the drip dispersal
system.
2. The drip dispersal system shall be sized with the
minimum soil treatment area and total length, in accordance
with the following equations, Equation 200-4 and Equation
200-5:
Equation 200-4
Q
A = ______
HLR
Equation 200-5
A
L = _____
2 feet
Where:
A = Minimum soil treatment area (square feet (sq. ft))
Q = Maximum daily wastewater flow (gallons per day (gpd))
HLR = Maximum hydraulic loading rate determined in the soils
report (gpd/sq.ft)
L = Minimum total length of drip dispersal lines (ft)
(B) Lines.
1. The drip dispersal lines shall be placed at a minimum
depth of six inches (6") below the surface.
2. Emitters and drip dispersal lines shall be placed at a
minimum on a two-foot (2') spacing to achieve even distribution of the wastewater and maximum utilization of the soil.
AUTHORITY: section 644.026, RSMo 2016.* Original rule filed Aug.
10, 1978, effective March 11, 1979. Amended: Filed June 15, 2018,
effective Feb. 28, 2019. Amended: Filed June 14, 2024, effective Jan.
30, 2025.
*Original authority: 644.026, RSMo 1972, amended 1973, 1987, 1993, 1995, 2000, 2012,
2014.