10 CSR 26-2.020
Performance Standards for New Underground Storage Tank Systems
PURPOSE: This rule sets the standards for
tanks, piping, spill and overfill prevention
equipment, installation, and certification of
installation that new underground storage
tanks must meet.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed here.
(1) In order to prevent releases due to structural failure, corrosion, or spills and overfills
for as long as the underground storage tank
(UST) system is used to store regulated substances, all owners and operators of new UST
systems must meet the following requirements:
(A) Tanks. Each tank must be properly
designed and constructed, and any portion
underground that routinely contains a regulated substance must be protected from corrosion, in accordance with a code of practice
developed by a nationally-recognized association or independent testing laboratory as
specified in paragraphs 1. through 5. of this
subsection. In addition, all new or replaced
tanks where installation began on or after
July 1, 2017, must be double-walled in accordance with paragraph 5. of this subsection—
1. The tank is constructed of fiberglassreinforced plastic and complies with—
A.
Underwriters’
Laboratories
Standard 1316, Standard for Glass-FiberReinforced Plastic Underground Storage Tanks
for Petroleum Products, Alcohol and AlcoholGasoline Mixtures, revised 2006. This document is incorporated by reference without any
later amendments or modifications. To obtain a
copy, contact the Underwriters’ Laboratories,
333 Pfingsten Road, Northbrook, IL 600622096, (847) 272-8800, www.ul.com; or
B. Other standards or publications
approved by the department; or
2. The tank is constructed of steel and
cathodically protected in the following manner:
A. The tank is coated with a suitable
dielectric material;
B. Field-installed cathodic protection
systems are designed by a corrosion expert;
C. Impressed current systems are
designed to allow determination of current
operating status as required in 10 CSR 262.031(1)(C);
D. Cathodic protection systems are
operated and maintained in accordance with
10 CSR 26-2.031 or according to guidelines
established by the department; and
E. The following codes and standards
may be used to comply with paragraph
(1)(A)2. of this rule:
(I) Steel Tank Institute Specification
for STI-P3 System of External Corrosion
Protection of Underground Steel Storage
Tanks, revised 2010. This document is incorporated by reference without any later amendments or modifications. To obtain a copy,
contact the Steel Tank Institute, 944 Donata
Court, Lake Zurich, IL 60047, (708) 4388265, www.steeltank.com;
(II) Steel Tank Institute Standard
F841, Standard for Dual Wall Underground
Steel Storage Tanks, revised 2006. This document is incorporated by reference without
any later amendments or modifications. To
obtain a copy, contact the Steel Tank Institute,
944 Donata Court, Lake Zurich, IL 60047,
(708) 438-8265, www.steeltank.com;
(III) Underwriters’ Laboratories
Standard 1746, Standard for External
Corrosion Protection Systems for Steel
Underground Storage Tanks, revised 2007.
This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact the
Underwriters’ Laboratories, 333 Pfingsten
Road, Northbrook, IL 60062-2096, (847)
272-8800, www.ul.com;
(IV) NACE International RP 02852002, Corrosion Control of Underground
Storage Tank Systems by Cathodic Protection,
revised 2002. This document is incorporated
by reference without any later amendments or
modifications. To obtain a copy, contact
NACE International, Box 218340, Houston,
TX
77218-8340,
(713)
492-0535,
Substance Storage Tanks
www.nace.org;
(V) Underwriters’ Laboratories
Standard 58, Standard for Steel Underground
Tanks for Flammable and Combustible
Liquids, revised 1998. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Underwriters’ Laboratories,
333 Pfingsten Road, Northbrook, IL 600622096, (847) 272-8800, www.ul.com; or
3. The tank is a composite tank with a
steel inner tank and a non-metallic external
thick film coating or the tank is a steel inner
tank constructed with a non-metallic external
jacket forming a secondary wall. Either of
these tanks shall comply with one (1) of the
following industry codes:
A. Underwriters’
Laboratories
Standard 1746, Standard for External
Corrosion Protection Systems for Steel
Underground Storage Tanks, revised 2007.
This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact the
Underwriters’ Laboratories, 333 Pfingsten
Road, Northbrook, IL 60062-2096, (847)
272-8800, www.ul.com;
B. Steel Tank Institute’s ACT-100,
Specification
for
External
Corrosion
Protection of FRP Composite Steel USTs
(F894), revised June 2010. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Steel Tank Institute, 944
Donata Court, Lake Zurich, IL 60047, (708)
438-8265, www.steeltank.com;
C.
Underwriters’
Laboratories
Standard 58, Standard for Safety for Steel
Underground Storage Tanks for Flammable
and Combustible Liquids, revised 1998. This
document is incorporated by reference without any later amendments or modifications.
To obtain a copy, contact the Underwriters’
Laboratories,
333
Pfingsten
Road,
Northbrook, IL 60062-2096, (847) 2728800, www.ul.com;
D. Steel Tank Institute’s ACT-100-U,
Specification
for
External
Corrosion
Protection of Composite Steel Underground
Storage Tanks, F961, June 2010. This document is incorporated by reference without
any later amendments or modifications. To
obtain a copy, contact the Steel Tank Institute,
944 Donata Court, Lake Zurich, IL 60047,
(708) 438-8265, www.steeltank.com; or
E. Steel Tank Institute’s Specification
F922, Steel Tank Institute Specification for
Permatank, revised 2013. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Steel Tank Institute, 944
Donata Court, Lake Zurich, IL 60047, (708)
438-8265, www.steeltank.com; or
4. The tank construction and corrosion
protection are determined by the department
to be designed to prevent the release or
threatened release of any stored regulated
substance in a manner that is no less protective of human health and the environment
than paragraphs (1)(A)1.–3. of this rule;
5. Tanks installed on or after July 1,
2017, must be double-walled.
(B) Piping. The piping that routinely contains regulated substances and is in contact
with an electrolyte, including, but not limited
to, soil, backfill, and/or water, must be properly designed, constructed, and protected
from corrosion as specified in paragraphs 1.
through 4. of this subsection. In addition, all
new piping systems where installation began
on or after July 1, 2017, must be doublewalled in accordance with paragraph 5. of
this subsection. If more than fifty percent
(50%) of any tank system’s piping is replaced
within any twelve (12) month period, the
entire piping run must be double-walled in
accordance with paragraph 5.
1. The piping is constructed of an
approved, non-corrodible material.
2. The following codes and standards
may be used to comply with paragraph
(1)(B)1. of this rule:
A. Underwriters’
Laboratories
Standard 971, UL Listed Nonmetallic
Underground Piping for Flammable Liquids,
revised 2006. This document is incorporated
by reference without any later amendments or
modifications. To obtain a copy, contact the
Underwriters’ Laboratories, 333 Pfingsten
Road, Northbrook, IL 60062-2096, (847)
272-8800, www.ul.com; and
B. Underwriters’
Laboratories
Standard
567,
Emergency
Breakaway
Fittings, Swivel Connectors and Pipe
Connection Fittings for Petroleum Products
and LP-Gas, revised 2003. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Underwriters’ Laboratories,
333 Pfingsten Road, Northbrook, IL 600622096, (847) 272-8800, www.ul.com.
3. After July 1, 2017, metal piping may
not be installed unless it is completely
enclosed within a containment sump, except
existing flexible connectors may be replaced
without a containment sump if the new flexible connector is protected from corrosion by
isolating it from the backfill using a manufacturer-approved isolation boot or protecting
the connector from corrosion in accordance
with this paragraph. For existing piping, the
piping is constructed of steel and cathodically
protected in the following manner:
A. The piping is coated with a suitable dielectric material;
B. Field-installed cathodic protection
systems are designed by a corrosion expert;
C. Impressed current systems are
designed to allow determination of current
operating status as required in 10 CSR 262.031(1)(C);
D. Cathodic protection systems are
operated, inspected, and maintained in accordance with 10 CSR 26-2.031; and
E. The codes and standards in 10
CSR 26-2.031(2) may be used to comply
with paragraph (1)(B)3. of this rule.
4. The piping construction and corrosion protection are determined by the department to be designed to prevent the release or
threatened release of any stored regulated
substance in a manner that is no less protective of human health and the environment
than the requirements in paragraphs (1)(B)1.–
3. of this rule.
5. After July 1, 2017, new or replaced
piping must be double-walled piping, except
for any single wall fittings or ends, which
must be open to a leak-tight containment
sump(s), except for safe suction piping that
meets the requirements of 10 CSR 262.041(1)(B)2.A. through E.;
(C) Spill
and
Overfill
Prevention
Equipment.
1. Except as provided in paragraph
(1)(C)2. of this rule, to prevent spilling and
overfilling associated with product transfer to
the UST system, owners and operators must
use the following spill and overfill prevention
equipment:
A. Spill prevention equipment that
will prevent release of product to the environment when the transfer hose is detached from
the fill pipe (for example, a spill catchment
basin). All delivery hose-fill pipe connections
must be tight, lock-on connections; and
B. Overfill prevention equipment that
will—
(I) Automatically shut off flow into
the tank when the tank is no more than ninety-five percent (95%) full;
(II) Alert the transfer operator with
a high-level alarm at least one (1) minute
before overfilling with an alarm audible in the
delivery area; or
(III) Alert the transfer operator
when the tank is no more than ninety percent
(90%) full by restricting flow into the tank.
(a) Ball float valves may only be
used in tank systems with gravity deliveries,
in suction systems if there are no check
valves, except those contained within a building, and the tank system is tight so that it
does not allow vapors to be released during a
delivery after the ball float valve has closed.
(b) Ball float valves are not
approved for use as overfill prevention equipment in new tank systems installed after
December 31, 2011.
(c) When an overfill prevention
device is replaced after July 1, 2017, a ball
float valve may not be used.
(IV) For pressurized deliveries,
overfill prevention equipment must be compatible and approved for use with pressurized
deliveries;
C. All spill and overfill prevention
equipment must be installed, inspected,
maintained, and replaced in accordance with
2. Owners and operators are not
required to use the spill and overfill prevention equipment specified in paragraph
(1)(C)1. of this rule if—
A. Alternative equipment is used that
is determined by the department to be no less
protective of human health and the environment than the equipment specified in subparagraph (1)(C)1.A. or B. of this rule; or
B. The owner or operator submits a
written explanation that the equipment cannot
be used for the UST system and their detailed
fuel-delivery plan, documenting that their
delivery procedures prevent spills and overfills; or
C. The UST system is filled by transfers of no more than twenty-five (25) gallons
at one (1) time;
(D) For new or replaced tanks or piping
installed after July 1, 2017, containment
sumps must be installed at each tank top suction piping or submersible turbine pump connection, each piping transition, ball valve or
single-walled fitting location, and under each
dispenser. The containment sump must be
liquid-tight on its sides, bottom, and at any
penetrations, with interstitial monitoring in
accordance with 10 CSR 26-2.043(1)(H) and
sump testing in accordance with 10 CSR 262.035;
(E) Dispenser Systems. Any new dispenser
system installed after July 1, 2017, must have
a containment sump beneath it.
1. A dispenser system is considered new
when both the dispenser and the equipment
needed to connect the dispenser to the underground storage tank system are installed or
replaced at a UST facility. The equipment
necessary to connect the dispenser to the
UST system includes check valves, shear
valves, unburied risers and flexible connectors, and other transitional components that
are underneath the dispenser and connect the
dispenser to the underground UST system
piping.
2. Under-dispenser containment must be
liquid-tight on its sides, bottom, and at any
penetrations and must comply with the annual walkthrough inspection requirements in 10
CSR 26-2.036 or be tested or monitored for
leaks from the dispenser system in accordance with 10 CSR 26-2.035.
(F) Installation. All tanks and piping must
be properly installed in accordance with a
code of practice developed by a nationally-recognized association or independent testing laboratory, in accordance with all manufacturers’
instructions, and in accordance with 10 CSR
26-2.019. Tank and piping system installation
practices and procedures described in the following codes of practice may be used to comply with the requirements of this rule:
1. American
Petroleum
Institute
Publication 1615, Installation of Underground
Petroleum Storage System, revised 2011. This
document is incorporated by reference without
any later amendments or modifications. To
obtain a copy, contact the American Petroleum
Institute, 1220 L Street NW, Washington, DC
20005, (202) 682-8000, www.api.org/standards/; or
2. Petroleum
Equipment
Institute
Publication RP100, Recommended Practices
for Installation of Underground Liquid Storage
Systems, revised 2011. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Petroleum Equipment
Institute, Box 2380, Tulsa, OK 74101-2380,
(918) 494-9696, www.pei.org.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* This rule originally
filed as 10 CSR 20-10.020. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011. Amended: Filed Aug.
15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.