10 CSR 26-2.030
Spill and Overfill Control for In-Use Underground Storage Tank Systems
PURPOSE: This rule is designed to prevent
releases during routine filling of the underground storage tank with product.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed
here.
(1) Owners and operators must ensure that
releases due to spilling or overfilling do not
occur. The owner and operator must ensure
that the volume available in the tank is greater
than the volume of product to be transferred
to the tank before the transfer is made and
that the transfer operation is monitored constantly to prevent overfilling and spilling.
(2) The owner and operator must report,
investigate, and clean up any spills and overfills in accordance with 10 CSR 26-2.053.
(3) Owners and operators must meet one (1)
Substance Storage Tanks
of the following requirements to ensure their
spill prevention equipment is operating properly and will prevent releases to the environment:
(A) Have double-walled spill prevention
equipment and monitor the space between the
walls at least once every thirty (30) days; or
(B) The spill prevention equipment is tested at least triennially to ensure the spill prevention equipment is liquid tight by using
vacuum, pressure, or liquid testing in accordance with one (1) of the following:
1. Requirements developed by the manufacturer (Note: This option may only be
used if the manufacturer has developed testing requirements. Self-testing apparatus may
only be used if pre-approved by the department as a valid functionality test.); or
2. Interstitial test (for double-walled
spill basins only) or spill containment test
listed by the National Work Group on Leak
Detection Evaluations. To obtain copies of
equipment certifications, contact the National
Work Group on Leak Detection Evaluations,
www.nwglde.org; or
3. Petroleum Equipment Institute RP
1200-12, Recommended Practices for the
Testing and Verification of Spill, Overfill,
Leak Detection and Secondary Containment
Equipment at UST Facilities. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Petroleum Equipment
Institute, Box 2380, Tulsa, OK 74101-2380,
(918) 494-9696, www.pei.org; or
4. Other methods approved by the
department, which may include a code of
practice developed by a nationally recognized
association or independent testing laboratory,
determined to be no less protective of human
health and the environment than the requirements listed in paragraphs 1. through 3. of
this subsection.
(4) Spill basins may not be repaired with a
partial or spot, field-applied repair kit or
product. Repairs must either be a manufacturer-designed replacement insert or a complete factory-built, field-installed spill basin
repair kit. Other repairs may be approved by
the department if they are determined to be
no less protective of human health and the
environment.
(5) Owners and operators must ensure their
overfill prevention equipment is operating
properly and will prevent releases to the environment. Overfill prevention equipment must
be inspected or tested at least triennially. At a
minimum, the test or inspection must ensure
that overfill prevention equipment is set to
activate at the correct level specified in 10
CSR 26-2.020 and will activate when the regulated substance reaches that level. Tests or
inspections must be conducted in accordance
with one (1) of the following criteria:
(A) Requirements developed by the manufacturer, but only if the test or inspection confirms that all portions of the overfill device
are intact and functional. (Note: This option
may be used if the manufacturer has developed testing requirements. Self-testing apparatus may only be used if approved by the
department as a valid functionality test); or
(B) Petroleum Equipment Institute RP
1200-12, Recommended Practices for the
Testing and Verification of Spill, Overfill,
Leak Detection and Secondary Containment
Equipment at UST Facilities. This document
is incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Petroleum Equipment
Institute, Box 2380, Tulsa, OK 74101-2380,
(918) 494-9696, www.pei.org; or
(C) Other methods approved by the department, which may include a code of practice
developed by a nationally recognized association or independent testing laboratory, determined to be no less protective of human
health and the environment than the requirements listed in subsections (A) or (B) of this
section.
(6) The first test of the spill equipment and
the first test or inspection of the overfill prevention equipment required by this rule is due
no later than January 1, 2020.
(7) If a tank has been out of use for more than
twelve (12) months, equipment must be confirmed operational with a test of the spill prevention equipment and an inspection or test
of the overfill prevention equipment, prior to
bringing it back in-use.
(8) Owners and operators must maintain the
following records, in accordance with 10
CSR 26-2.034, for spill and overfill prevention equipment:
(A) Test and/or inspection records must be
maintained for three (3) years; and/or
(B) When using interstitial monitoring,
records must be maintained for twelve (12)
months.
(9) Guidance on spill and overfill prevention
appears in the—
(A) American
Petroleum
Institute
Publication 1621, Recommended Practice for
Bulk Liquid Stock Control at Retail Outlets,
revised 2001. This document is incorporated
by reference without any later amendments or
modifications. To obtain a copy, contact the
American Petroleum Institute, 1220 L Street
NW, Washington, DC 20005, (202) 6828000, www.api.org/standards/;
(B) National Fire Protection Association
Standard 30, Flammable and Combustible
Liquids Code, revised 2008. This document
is incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the National Fire Protection
Association, 1 Batterymarch Park, Box 9101,
Quincy, MA 02269-9101, (617) 770-3000,
www.nfpa.org;
(C) Petroleum Equipment Institute RP
1200-12, Recommended Practices for the
Testing and Verification of Spill, Overfill,
Leak Detection and Secondary Containment
Equipment at UST Facilities. This document
is incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Petroleum Equipment
Institute, Box 2380, Tulsa, OK 74101-2380,
(918) 494-9696, www.pei.org;
(D) National Fire Protection Association
Standard 385, Standard for Tank Vehicles for
Flammable and Combustible Liquids, revised
2012. This document is incorporated by reference without any later amendments or
modifications. To obtain a copy, contact the
National Fire Protection Association, 1
Batterymarch Park, Box 9101, Quincy, MA
02269-9101, (617) 770-3000, www.nfpa.org;
and
(E) American
Petroleum
Institute
Recommended Practice 1007, Loading and
Unloading of MC 306/DOT Cargo Tank
Motor Vehicles, revised 2011. This document
is incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the American Petroleum
Institute, 1220 L Street NW, Washington, DC
20005, (202) 682-8000, www.api.org/standards.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* This rule originally
filed as 10 CSR 20-10.030. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011. Amended: Filed Aug.
15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.