10 CSR 26-2.031
Operation and Maintenance of Corrosion Protection
PURPOSE: This rule contains the requirements for corrosion protection systems.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed here.
(1) All owners and operators of metal underground storage tank (UST) systems with corrosion protection must comply with the following requirements to ensure that releases
due to corrosion are prevented until the system is permanently closed or has an out-ofuse site assessment conducted in accordance
with 10 CSR 26-2.060 through 10 CSR 262.064.
(A) All corrosion protection systems must
be operated and maintained to continuously
provide corrosion protection to the metal
components of that portion of the tank and
piping that routinely contain regulated substances and are in contact with an electrolyte,
including, but not limited to, soil, backfill,
and/or water.
(B) All UST systems equipped with
cathodic protection systems must be inspected for proper operation by a NACE
International certified, Steel Tank Institute
certified, or International Code Council
(ICC) appropriately certified cathodic protection tester in accordance with the following
requirements:
1. Frequency. To confirm that the system
is operating properly and providing adequate
protection, all cathodic protection systems
must be tested within six (6) months of installation and at least triennially after that, or
according to another reasonable time frame
established by the department; and
2. Inspection criteria. The criteria that
are used to determine that cathodic protection
(CP) is adequate as required by this section
must be in accordance with a code of practice
developed by a nationally-recognized association listed in section (2) of this rule.
A. Inspection reports must document
the testing method used, the testing standard
referenced, the CP tester, and the CP tester’s
qualifications.
B. Inspection reports must include a
site sketch, potential readings, and the location where the readings were made.
C. For impressed current systems, the
inspection report must document continuity
data and how voltage (IR) drops other than
those across the structure/electrolyte interface were considered or accounted for in
determining adequate protection.
(C) UST systems with impressed current
cathodic protection systems must also be
inspected every sixty (60) days to ensure the
equipment is running properly.
1. Rectifier log reports must include relevant system data, including, but not limited
to, amperage readings, voltage readings, hour
meter, and indicator light, where available.
2. Any indication of deviations from
previous rectifier logs or rectifier readings or
the most recent cathodic protection system
inspection of the rectifier or cathodic protection system, such as variances in current
reading or indicator light, must be appropriately investigated.
(D) For UST systems using cathodic protection, records of the operation of the
cathodic protection system must be maintained in accordance with 10 CSR 26-2.034
to demonstrate compliance with the performance standards in this rule. These records
must provide the following:
1. The results of the last three (3)
inspections required in subsection (1)(C) of
this rule; and
2. The results of testing from the last
two (2) inspections required in subsection
(1)(B) of this rule.
(2) The following codes and standards may be
used to comply with this rule:
(A) NACE International RP 0285-2002,
Corrosion Control of Underground Storage
Tank Systems by Cathodic Protection, revised
2002. This document is incorporated by reference without any later amendments or modifications. To obtain a copy, contact NACE
International, Box 218340, Houston, TX
77218-8340, (713) 492-0535, www.nace.org;
(B) NACE International TM0101-2001,
Standard
Test
Method,
Measurement
Techniques Related to Criteria for Cathodic
Protection on Underground or Submerged
Metallic Tank Systems, 2001 edition. This
document is incorporated by reference without any later amendments or modifications.
To
obtain
a
copy,
contact
NACE
International, Box 218340, Houston, TX
77218-8340, (713) 492-0535, www.nace.org;
(C) NACE International SP-0169-2007,
Control of External Corrosion on Submerged
Metallic Piping Systems, revised 2007. This
document is incorporated by reference without any later amendments or modifications.
To
obtain
a
copy,
contact
NACE
International, Box 218340, Houston, TX
77218-8340, (713) 492-0535, www.nace.org;
(D) NACE International TM0497-2012,
Measurement Techniques Related to Criteria
for Cathodic Protection on Underground or
Submerged Metallic Piping Systems, revised
2012. This document is incorporated by reference without any later amendments or modifications. To obtain a copy, contact NACE
International, Box 218340, Houston, TX
77218-8340, (713) 492-0535, www.nace.org;
(E) Steel Tank Institute Cathodic Protection
Testing Procedures for sti-P3 USTs, R051,
January 2006. This document is incorporated
by reference without any later amendments or
modifications. To obtain a copy, contact the
Steel Tank Institute, 944 Donata Court, Lake
Zurich,
IL
60047,
(708)
438-8265,
www.steeltank.com;
(F) Steel Tank Institute Recommended
Practice for the Addition of Supplemental
Anodes to sti-P3 USTs, R972, December
2010. This document is incorporated by reference without any later amendments or
modifications. To obtain a copy, contact the
Steel Tank Institute, 944 Donata Court, Lake
Zurich,
IL
60047,
(708)
438-8265,
www.steeltank.com; or
(G) Steel Tank Institute Recommended
Practice
for
Corrosion
Protection
of
Underground Piping Networks Associated with
Liquid Storage and Dispensing Systems, R892,
Revised January 2006. To obtain a copy, contact the Steel Tank Institute, 944 Donata
Court, Lake Zurich, IL 60047, (708) 4388265, www.steeltank.com.
(3) If cathodic protection is being used to
protect all or part of a UST system from corrosion, and the electric system energizing the
cathodic protection has been off, unhooked,
or damaged for more than ninety (90) days,
the owner/operator must—
(A) Conduct a tank integrity test, documenting adequate tank shell integrity and
thickness, as required in 10 CSR 262.021(3)(B); and
(B) Have a corrosion expert or design
engineer re-evaluate the UST system, cathodic protection system, and surrounding structures and design and/or make changes to the
existing cathodic protection system to meet
the standards in 10 CSR 26-2.020(1)(A)2.B.–
D.;
(C) Replace metal piping components;
(D) The owner/operator may request an
additional ninety (90) days to repair the systems by submitting a request, including the
justification for the extension; or
(E) Permanently close the tank, in accordance with 10 CSR 26-2.060 through 10 CSR
26-2.064.
(4) If a cathodic protection system test indicates that the system is not operating properly
or does not provide adequate protection, as
defined by the testing method used, and the
system is not repaired or does not pass a retest within ninety (90) days, or if a required
Substance Storage Tanks
cathodic protection system test is not conducted, the owner/operator must comply with
the requirements outlined in section (3) of
this rule.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* This rule originally
filed as 10 CSR 20-10.031. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011. Amended: Filed Aug.
15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.