10 CSR 26-2.032
Compatibility
PURPOSE:
This rule prevents releases
caused by chemical action on the underground storage tank system by the stored regulated substance.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed here.
(1) Owners and operators must use an underground storage tank (UST) system made of or
lined with materials that are compatible with
the substance stored in the UST system. If a
lining is installed for compatibility purposes,
it must be maintained and inspected in accordance with 10 CSR 26-2.021(3)(A).
(2) Owners and operators must notify the
department at least thirty (30) days prior to
switching to a regulated substance containing
greater than ten percent (10%) ethanol and/or
greater than twenty percent (20%) biodiesel.
(3) Owners and operators may use one (1) or
more of the following methods to demonstrate UST system compatibility with the regulated substance stored:
(A) Certification or listing of UST system
components by a nationally recognized, independent testing laboratory for use with the
regulated substance stored; or
(B) Equipment or component manufacturer
approval. The manufacturer’s approval must
be in writing, indicate an affirmative statement of compatibility and functionality, specify the range of product blends with which
the component is compatible, and be from the
equipment or component manufacturer; or
(C) Another method determined by the
department to be no less protective of human
health and the environment than the methods
listed in subsection (A) or (B) of this section.
(4) Owners and operators storing alcohol
blends may use the following codes to comply
with this rule:
(A) American
Petroleum
Institute
Recommended Practice 1626, Storing and
Handling Ethanol and Gasoline-Ethanol
Blends at Distribution Terminals and Service
Stations, 2010 Edition with 2012 Addendum.
This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact the American
Petroleum Institute, 1220 L Street NW,
Washington, DC 20005, (202) 682-8000,
www.api.org/standards/; or
(B) Other standards or publications
approved by the department.
AUTHORITY: sections 319.105 and 319.137,
RSMo 2016.* This rule originally filed as 10
CSR 20-10.032. Original rule filed April 2,
1990, effective Sept. 28, 1990. Moved and
amended: Filed April 15, 2011, effective Dec.
30, 2011. Amended: Filed Aug. 15, 2016,
effective May 30, 2017.
*Original authority: 319.105, RSMo 1989 and 319.137,
RSMo 1989, amended 1993, 1995, 2004.