10 CSR 26-2.033
Repairs Allowed
PURPOSE: This rule describes methods for
repair of underground storage tank systems.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed here.
(1) Owners and operators of underground
storage tank (UST) systems must ensure that
repairs will prevent releases due to structural
failure or corrosion as long as the UST system is used to store regulated substances.
(2) The repairs must meet the following
requirements:
(A) Repairs to UST systems must be properly conducted in accordance with a code of
practice developed by a nationally-recognized
association or an independent testing laboratory.
1. The following codes and standards
may be used to comply with subsection
(2)(A) of this rule:
A. National
Fire
Protection
Association Standard 30, Flammable and
Combustible Liquids Code, revised 2008.
This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact the National
Fire Protection Association, 1 Batterymarch
Park, Box 9101, Quincy, MA 02269-9101,
(617) 770-3000, www.nfpa.org;
B. National
Fire
Protection
Association Standard 326, Standard for the
Safeguarding of Tanks and Containers for
Entry, Cleaning, or Repair, revised 2015.
This document is incorporated by reference
without any later amendments or modifications. To obtain a copy, contact the National
Fire Protection Association, 1 Batterymarch
Park, Box 9101, Quincy, MA 02269-9101,
(617) 770-3000, www.nfpa.org;
C. American Petroleum Institute
Publication 2200, Repairing Crude Oil,
Liquefied Petroleum Gas, and Product
Pipelines, revised 2001. This document is
incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the American Petroleum
Institute, 1220 L Street NW, Washington, DC
20005, (202) 682-8000, www.api.org/standards/;
D. American Petroleum Institute
Standard 1631, Interior Lining and Periodic
Inspection of Underground Storage Tanks,
revised 2001. This document is incorporated
by reference without any later amendments or
modifications. To obtain a copy, contact the
American Petroleum Institute, 1220 L Street
NW, Washington, DC 20005, (202) 6828000, www.api.org/standards/;
E. National
Leak
Prevention
Association Standard 631, Spill Prevention,
Minimum 10-Year Life Extension of Existing
Steel Underground Tanks by Lining Without
the Addition of Cathodic Protection, revised
1999. This standard may only be used for
interior lining application and inspection, not
for integrity testing of the steel shell. This
document is incorporated by reference without any later amendments or modifications.
To obtain a copy, contact the National Leak
Prevention Association, (815) 301-2785,
www.nlpa-online.org; and
F. Fiberglass Tank and Piping Institute
T-95-1, Remanufacturing of Fiberglass Plastic
(FRP) Underground Storage Tanks, Revised
1995. This document is incorporated by reference without any later amendments or modifications. To obtain a copy, contact the
Fiberglass
Tank
and
Piping
Institute,
http://www.fiberglasstankandpipe.com;
(B) Repairs to fiberglass-reinforced plastic
tanks may be made by the manufacturer’s
authorized representatives or in accordance
with a code of practice developed by a nationally-recognized association or an independent
testing laboratory;
(C) Metal pipe sections and fittings that
have released a regulated substance as a result
of corrosion or other damage must be
replaced. For cathodically protected metal
piping, the entire length of electrically-continuous metal pipe must be replaced. Noncorrodible pipes and fittings may be repaired
in accordance with the manufacturer’s specifications;
(D) Repairs must be done by a person who
is properly registered with the Missouri
Department of Agriculture and who has a
financial responsibility mechanism that complies with the requirements of 2 CSR 9030.085;
(E) Repaired tanks and/or piping must be
tightness tested in accordance with release
detection methods listed in 10 CSR 262.043(1)(D) and 10 CSR 26-2.044(1)(B)
within thirty (30) days following the date of
the completion of the repair, unless tested
using another method determined by the
department to be no less protective of human
health and the environment.
(F) Repairs of UST systems, or any portion
of a UST system, required to be doublewalled, must be tested to confirm the integrity of both walls of the repaired tank or piping
system within thirty (30) days following the
completion of any repair;
(G) Repairs to any required containment
sumps must be tested using a method specified in 10 CSR 26-2.035(1)(B) within thirty
(30) days following the completion of any
repair;
(H) Within thirty (30) days following any
repair to spill or prevention equipment, the
repaired spill or overfill prevention equipment must be tested in accordance with 10
CSR 26-2.030 to ensure it is operating properly;
(I) Within six (6) months following the
repair of any cathodically protected UST system, the cathodic protection system must be
tested with the methods of operation and
maintenance of corrosion protection in 10
CSR 26-2.031(1)(B) and (C) to ensure that it
is operating properly. Repair may include,
but is not limited to, adjustments, maintenance, replacement, or changes to cathodic
protection equipment and/or tank repairs;
(J) If a tank is repaired by installation of an
interior lining, the lining must be properly
maintained and inspected, in accordance with
10 CSR 26-2.021(3)(A), for the life of the
tank; and
(K) UST system owners and operators
must maintain records demonstrating compliance with this rule for each repair for the
remaining operating life of the UST system.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* This rule originally
filed as 10 CSR 20-10.033. Original rule filed
April 2, 1990, effective Sept. 28, 1990.
Moved and amended: Filed April 15, 2011,
effective Dec. 30, 2011. Amended: Filed Aug.
15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.