10 CSR 26-2.035
Testing of Containment Sumps
PURPOSE: This rule contains the requirements for testing the newly required containment sumps associated with underground
storage tank systems.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule would
be unduly cumbersome or expensive. This
material as incorporated by reference in this
rule shall be maintained by the agency at its
headquarters and shall be made available to
the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed here.
(1) Owners and operators of underground
storage tank (UST) systems with containment
sumps required by 10 CSR 26-2.020 and/or
10 CSR 26-2.021, must ensure the continued
integrity of required containment sumps by
meeting one (1) of the following requirements:
(A) The containment sump has at least two
(2) walls and an interstitial space and the
integrity of two (2) walls is interstitially monitored annually; or
(B) The containment sump primary wall is
tested at least triennially to ensure the equipment is liquid-tight by using vacuum, pressure, or liquid testing.
(2) The testing and/or monitoring required by
this rule must be conducted in accordance
with one (1) of the following:
(A) A tightness test developed and published by the manufacturer (Note: Owners
and operators may use this option only if the
manufacturer has developed testing requirements.);
(B) An interstitial test or containment
sump test listed by the National Work Group
on Leak Detection Evaluations. To obtain
copies of equipment listings, contact the
National Work Group on Leak Detection
Evaluations, www.nwglde.org; or
(C) Petroleum Equipment Institute RP
1200-12, Recommended Practices for the
Testing and Verification of Spill, Overfill,
Leak Detection and Secondary Containment
Equipment at UST Facilities. This document
is incorporated by reference without any later
amendments or modifications. To obtain a
copy, contact the Petroleum Equipment
Institute, Box 2380, Tulsa, OK 74101-2380,
(918) 494- 9696, www.pei.org; or
(D) Another method approved by department, including code(s) of practice developed
by a nationally recognized association(s) or
independent testing laboratory(ies), determined to be no less protective of human
health and the environment than the requirements listed in subsections (A) through (C) of
this section.
(3) Owners and operators must maintain
record(s) of the required containment sump
monitoring for twelve (12) months or test(s)
required by this rule until the next test is performed.
AUTHORITY: sections 319.105, 319.107, and
319.137, RSMo 2016.* Original rule filed
Aug. 15, 2016, effective May 30, 2017.
*Original authority: 319.105, RSMo 1989; 319.107, RSMo
1989, amended 1994; and 319.137, RSMo 1989, amended
1993, 1995, 2004.