10 CSR 26-2.046
Alternative Methods of Release Detection for Field-Constructed Tanks
PURPOSE: This rule contains the new
options for release detection for the previously deferred field-constructed tanks and airport hydrant fuel distribution systems.
(1) Owners and operators of field-constructed
tanks with a capacity greater than fifty thousand (50,000) gallons may use one (1) or a
combination of the following alternative
methods of release detection:
(A) Conduct an annual tank tightness test
that can detect a one-half- (0.5-) gallon-perhour leak rate;
(B) Use an automatic tank gauging system
to perform release detection at least every
thirty (30) days that can detect a leak rate less
than or equal to one (1) gallon-per-hour.
This method must be combined with a tank
tightness test that can detect a two-tenths-
(0.2-) gallon-per-hour leak rate performed at
least every three (3) years;
(C) Use an automatic tank gauging system
to perform release detection at least every
thirty (30) days that can detect a leak rate less
than or equal to two (2) gallons-per-hour.
This method must be combined with a bulk
tank tightness test that can detect a twotenths- (0.2-) gallon-per-hour leak rate performed at least every two (2) years;
(D) Perform vapor monitoring, with an
added tracer chemical, conducted in accordance with 10 CSR 26-2.043 subsection
(1)(F), capable of detecting a one-tenth- (0.1-)
gallon-per-hour leak rate at least every two
(2) years;
(E) Perform inventory control, conducted
in accordance with Department of Defense
Directive 4140.25; ATA Airport Fuel Facility
Operations and Maintenance Guidance
Manual, at least every thirty (30) days that
can detect a leak equal to or less than onehalf percent (0.5%) of flow-through. When
using this method, the following must also be
met:
1. Perform a tank tightness test that can
detect a one-half- (0.5-) gallon-per-hour leak
rate at least every two (2) years; or
2. Perform vapor monitoring or groundwater monitoring in accordance with 10 CSR
26-2.043 subsection (1)(F) or (G), respectively, at least every thirty (30) days; and
(F) Another method approved by the department if the owner and operator can demonstrate that the method can detect a release as
effectively as any of the methods allowed in
subsections (A) through (C) of this section. In
comparing methods, the department shall consider the size of release that the method can
detect and the frequency and reliability of
detection. If the method is approved, the
owner and operator must comply with any
conditions imposed by the department on its
use.