19 CSR 20-3.050
Sanitation and Safety Standards for Lodging Establishments
PURPOSE: This rule establishes sanitation
and safety standards pertaining to life safety,
fire safety, electrical wiring, fuel-burning
appliances,
plumbing
and
swimming
pools/spas for lodging establishments.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule
would be unduly cumbersome or expensive.
This material as incorporated by reference in
this rule shall be maintained by the agency at
its headquarters and shall be made available
to the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed
here.
(1) General.
(A) Definitions.
1. “Administrative authority” shall mean
local or state health department representative or local codes administrator/fire marshal, state fire marshal or his/her representative.
2. “Air break” shall mean a piping
arrangement in which a drain from a fixture,
appliance or device discharges indirectly into
another fixture, receptacle or interception at
a point below the flood level rim. The connection does not provide an unobstructed vertical distance and is not solidly connected but
precludes the possibility of backflow to a
potable water source.
3. “Air gap” shall mean the unobstructed vertical distance through the free atmosphere between the lowest opening from any
pipe or outlet supplying fixture, or other
device, and the flood level rim of the receptacle. The vertical physical separation shall
be at least two (2) times the inside diameter
of the water inlet pipe above the flood rim
level but shall not be less than one inch (1").
4. “Approved” shall mean acceptable to
the administrative authority having jurisdiction.
5. “Bed and breakfast” shall mean an
existing building(s) with no more than three
(3) occupiable stories, with at least five (5)
but no more than ten (10) guest rooms. The
building shall have interior corridors and be
provided with a kitchen; breakfast shall be
provided to guests and the owner must live in
or adjacent to the building.
6. “Dead-end corridor” shall mean a
corridor, aisle or passageway arranged without an exit access in two (2) directions.
7. “Equivalent code” shall mean any
code that is accepted by state regulatory
authorities and the industry that contains the
same definition or standard as the code referenced in this rule, including but not limited
to, fire alarm systems, wireless smoke detectors and supervised sprinkler systems.
8. “Existing lodging establishment”
shall mean a building, component or feature
that is operating as a licensed lodging establishment or has a current inspection conducted by or for the Missouri Department of
Health and Senior Services (DHSS) and is in
the process of obtaining a lodging license as
of the effective date of this rule.
9. “Exit” shall mean the portion of a
means of egress that is separated from all
other spaces of the building or structure by
construction or equipment required to provide a protected way of travel to the exit discharge. Exits include exterior exit doors, exit
passageways, horizontal exits, separated exit
stairs and separated exit ramps.
10. “Exit access” shall mean the portion
of a means of egress that leads to an exit.
11. “Exit discharge” shall mean the portion of a means of egress between the termination of an exit and a public way.
12. “Fire alarm system” is as described
in the National Fire Protection Association
72, National Fire Alarm Code 2002 Edition,
which is incorporated by reference in this
rule or equivalent code. Any interested person may view this material at the agency’s
headquarters or may purchase a copy from
the National Fire Protection Association, 11
Tracy Drive, Avon, MA 02322. This rule
does not incorporate any subsequent amendments or additions.
13. “Fire barrier” shall mean a structural element, either vertical or horizontal,
such as a wall or floor assembly, that is
designed and constructed with a specified fire
resistance rating to limit the spread of fire
and restrict the movement of smoke. Such
barriers may have protected openings.
14. “Fire resistance rating” shall mean
the length of time, in minutes or hours, that
materials or structural elements can withstand fire exposure.
15. “Flame resistant material” shall
mean the property of material or its structural
elements that prevents or retards the passage
of excessive heat, hot gases or flames under
conditions in which they are used.
16. “Furnace” shall mean a heating
device with forced air ductwork.
17. “Group of buildings” as referenced
in the lodging establishment definition, shall
mean any building, structure, facility, place,
bed and breakfast, or places of business,
including but not limited to, multiple, individual or multi-unit cabins and guest rooms
that are not attached to the main building but
receive the same services/amenities as those
guest rooms within the main building.
18. “Guest room” shall mean any room
or unit where sleeping accommodations are
regularly furnished to the public.
19. “Hardwired” shall mean wired
directly and permanently into the building’s
main electrical wiring system and/or a wireless system as described in the National Fire
Protection Association 72, National Fire
Alarm Code 2002 Edition or equivalent code.
20. “Hazardous areas” shall mean areas
of structures or buildings posing a degree of
hazard greater than normal to the general
occupancy of a building or structure, such as
areas used for the storage or use of combustibles or flammable, toxic, noxious or corrosive materials, or heat-producing appliances.
21. “Historic building” shall mean a
building that is listed individually in the
National Register of Historic Places or is
located in a registered historic district and
certified by the Secretary of the Interior as
contributing to the historic significance of the
district.
22. “Lodging establishment” shall
include any building, group of buildings,
structure, facility, place, or places of business
where five (5) or more guest rooms are provided, which is owned, maintained, or operated by any person and which is kept, used,
maintained, advertised or held out to the public for hire which can be construed to be a
hotel, motel, motor hotel, apartment hotel,
tourist court, resort, cabins, tourist home,
bunkhouse, dormitory, or other similar place
by whatever name called, and includes all
such accommodations operated for hire as
lodging establishments for either transient
guests, permanent guests, or for both transient and permanent guests. This definition
shall not apply to dormitories and other living or sleeping facilities owned or maintained
by public or private schools, colleges, universities, or churches unless made available to
the general public and not used exclusively
for students and faculty, school-sponsored
events, baseball camps, conferences, dance
camps, equitation camps, football camps,
learned professional society meetings, music
camps, retreats, seminars, soccer camps,
swimming camps, track camps, youth leadership conferences, or church-sponsored
events.
23. “Major renovation” shall mean a
physical change to a lodging establishment or
portion thereof, including the replacement or
upgrading of major systems, which extends
the useful life. Examples include, but are not
limited to, demolition of the interior or exterior of a building or portion thereof, including the removal and subsequent replacement
of electrical, plumbing, heating, ventilating
and air conditioning systems, fixed equipment and interior walls and partitions
(whether fixed or moveable). Replacement of
broken, dated or worn equipment/items,
including but not limited to, individual air
conditioning units, bathroom tile, shower
stalls that do not require any additional or
new plumbing, electrical, etc. shall not be
considered a major renovation.
24. “Means of egress” shall mean a continuous and unobstructed way of travel from
any point in a building or structure to a public way. A means of egress consists of three
(3) distinct parts, the exit access, the exit and
the exit discharge.
25. “New lodging establishment” shall
mean a building, component or feature that
begins operation as a lodging establishment
after the effective date of this rule or an existing lodging establishment that has ceased
operation for a time period of eighteen (18)
months or more and reopens as a lodging
establishment after the effective date of this
rule.
26. “Occupiable story” shall mean a
story available to guests.
27. “Potable water” shall mean water
which is safe for human consumption in that
it is free from impurities in amounts sufficient to cause disease or harmful physiological effects and, for the purpose of this rule,
must be approved by the Department of
Natural Resources (DNR) or the DHSS prior
to serving to the general public.
28. “Potentially hazardous food” shall
mean those foods that are referenced in 19
CSR
20-1.025
Sanitation
of
Food
Establishments.
29. “Prepackaged” shall mean bottled,
canned, cartoned, securely bagged or securely wrapped, whether packaged in a food
establishment or a food processing plant. It
does not include a wrapper, carryout box or
other nondurable container used to containerize food with the purpose of facilitating food
protection during service and receipt of the
food by the consumer.
30. “Primary means of egress” shall
consist of, but is not limited to, an enclosed
interior stair, an exterior stair, horizontal
exit, door, stairway, or ramp providing a
means of unobstructed travel without traversing any corridor or space exposed to an
unprotected vertical opening. The primary
means of escape shall lead outside of the
dwelling unit at street or ground level.
Stairways serving as part of the primary
means of egress shall be enclosed with fire
barriers (vertical), such as wall or partition
assemblies with a fire resistance rating of not
less than thirty (30) minutes. Such enclosures
shall be continuous from floor to floor.
Openings shall be protected as appropriate
for the fire resistance rating of the barrier.
31. “Private water supply” shall mean a
piped water supply having less than fifteen
(15) service connections or serving less than
twenty-five (25) people at least sixty (60)
days out of the year.
32. “Public water supply” shall mean a
piped water supply having fifteen (15) or
more service connections or serving twentyfive (25) or more people at least sixty (60)
days out of the year. It may be a community
water system, transient noncommunity water
system or nontransient noncommunity water
system.
33. “Public way” shall mean an area
such as a street or sidewalk that is open to the
outside and is used by the public for moving
from one (1) location to another.
34. “Remote exit or means of egress”
shall mean when two (2) exits or two (2) exit
access doors are required.
35. “Secondary means of egress” shall
consist of, but is not limited to, a door, outside window, stairway, passage, fire escape or
hall providing a way of unobstructed travel to
the outside of the dwelling at street or ground
level; a passage through an adjacent nonlockable space to any approved means of escape;
an outside window or door operable from the
inside without the use of tools, keys, or special effort and providing a clear opening of
not less than twenty inches (20") in width,
twenty-four inches (24") in height, and 5.7
square feet in area. The bottom of the opening shall not be more than forty-four inches
(44") above the floor. Such means of escape
shall be acceptable if the window is within
twenty feet (20') of grade or opens onto an
exterior balcony and is directly accessible to
fire department rescue apparatus as approved
by the local fire inspector or State Fire
Marshal’s office.
36. “Self-closing” shall mean to be
equipped with an approved device that will
ensure closing after having been opened.
37. “Sleeping room” shall mean the part
of the guest room where people sleep.
38. “Smoke proof enclosure” shall
AND SENIOR SERVICES
Public Health
mean a stair enclosure designed to limit the
movement of combustion products, produced
by a fire occurring in any part of the building,
into such enclosure.
39. “Spa” shall mean a pool designed
for recreational and/or therapeutic use and
not drained, cleaned and refilled for each
individual. It may include, but is not limited
to, hydrojet circulation, hot water, cold water,
mineral baths, air induction systems or any
combination thereof.
40. “Story” shall mean the portion of a
building located between the upper surface of
a floor and the upper surface of the floor or
roof next above.
41. “Supervised sprinkler system” is as
described in the National Fire Protection
Association 13, Standard for the Installation
of Sprinkler Systems 2002 Edition and the
National Fire Protection Association 13R,
Standard for the Installation of Sprinkler
Systems in Residential Occupancies up to and
Including Four Stories in Height 2002
Edition, which are incorporated by reference
in this rule or equivalent code. Any interested person may view this material at the agency’s headquarters or may purchase a copy
from
the
National
Fire
Protection
Association, 11 Tracy Drive, Avon, MA
02322. This rule does not incorporate any
subsequent amendments or additions.
42. “Wet location” shall mean a location
subject to saturation with water or other liquids, including but not limited to, bathtubs,
sinks and/or shower stalls.
(2) Requirements for Obtaining a Lodging
License (Existing, New and Renovated).
Lodging establishments shall be responsible
for providing any and all documentation related to inspections and evaluations required in
this rule, including but not limited to, fire
extinguishers, fire alarm systems, sprinkler
systems and smoke detectors.
(A) Existing lodging establishments shall:
1. Comply with Missouri laws and the
DHSS rules and regulations regarding lodging establishments;
2. Comply with Missouri laws and the
DNR rules and regulations regarding, but not
limited to, sewage treatment, drinking water
and backflow;
3. Comply with Missouri laws and the
Department of Public Safety (DPS) rules and
regulations regarding pressure vessels;
4. Be operated and maintained in compliance with any and all applicable ordinances and regulations; and
5. If listed as a historical building, the
owner must notify the DHSS. Upon notification, the DHSS will collaborate with the
DNR, State Historical Preservation Office, to
determine requirements for licensing.
(B) New lodging establishments shall:
1. Comply with Missouri laws and the
DHSS rules and regulations regarding lodging establishments;
2. Comply with Missouri laws and the
DNR rules and regulations regarding, but not
limited to, sewage treatment, drinking water
and backflow;
3. Comply with Missouri laws and the
DPS rules and regulations regarding pressure
vessels;
4. If built within a jurisdiction with
applicable local ordinance(s), be erected,
operated and maintained in compliance with
those ordinances and regulations, or if not
built within a jurisdiction with applicable
local ordinance(s), be erected, operated and
maintained in accordance with the 2002
Edition of a national code(s) regarding life
safety, structural, electrical, plumbing,
mechanical and architectural elements of the
establishment, unless otherwise specifically
stated in this rule;
5. If listed as a historical building, the
owner must notify the DHSS. Upon notification, the DHSS will collaborate with the
DNR, State Historical Preservation Office, to
determine requirements for licensing; and
6. Present an occupancy permit issued
by the regulating authority, or if not located
within a jurisdiction that issues occupancy
permits, certify to the DHSS that the establishment has been designed and erected in
accordance with the 2002 Edition of a national code(s) regarding life safety, structural,
electrical, plumbing, mechanical and architectural elements of the establishment.
Certification to these facts will be accepted
by a professional engineer, architect or the
general contractor responsible for the construction of the establishment being licensed.
(C) Lodging establishments undergoing a
major renovation shall:
1. Present an occupancy permit issued
by the regulating authority, or if not located
within a jurisdiction that issues occupancy
permits, certify to the DHSS that the addition
has been designed and erected in accordance
with the 2002 Edition of a national code(s)
regarding life safety, structural, electrical,
plumbing, mechanical and architectural elements of the establishment. Certification to
these facts will be accepted by a professional
engineer, architect or the general contractor
responsible for the construction of the establishment being licensed.
(3) Requirements for Operating a Lodging
Establishment.
(A) Drinking Water Supply. Water supplies
that serve lodging establishments shall provide safe drinking water. Bacteriological,
chemical and radiological contaminants shall
be within levels acceptable to the administrative authority. Supplies deemed unsafe by the
DHSS or DNR shall not be used as a potable
water supply.
1. Treatment equipment for community,
noncommunity public and private water supplies.
A. New or existing treatment equipment necessary to provide a safe drinking
water supply shall be installed, maintained
and operated according to manufacturer’s
specifications and the DHSS requirements as
defined in (3)(A)1.–7. or the DNR requirements.
B. Existing chlorinators and chlorinators required to be installed to provide safe
drinking water, after the effective date of this
rule, shall be a positive feed liquid chlorinator with thirty (30)-minute retention time
based on pump capacity and must maintain a
residual no less than 0.5 and no greater than
four (4) parts per million (ppm) free available
chlorine.
C. Equipment, approved by the
administrative authority, shall be available to
test the treatment system.
2. Community and noncommunity public water supplies:
A. Shall be in compliance with
Missouri laws and the DNR rules and regulations;
B. Noncommunity water supplies
shall have a valid DNR permit to dispense
water. A current copy of the DNR permit to
dispense water must be available for review
by the administrative authority.
3. Private water supplies:
A. Shall be regulated under the jurisdiction of the DHSS and constructed and
located according to 10 CSR 23-3.010–10
CSR 23-3.110 Missouri Well Construction
Code with the following aboveground construction components verified by inspection:
(I) Well casing shall extend a minimum of twelve inches (12") above grade; and
(II) The top of the well casing shall
be free of openings that may allow the entry
of contaminants;
B. Potentially influenced by surface
water or shallow groundwater (i.e. springs,
bored and dug wells) shall be equipped with
a treatment system that includes:
(I) Microfiltration using a filter
with a one (1) micron absolute or smaller
pore size; and
(II) A chlorinator as defined in
(3)(A)1.B.
4. Routine testing for transient noncommunity public and private water supplies.
A. Transient noncommunity public
water and private water supplies shall be in
compliance with all applicable testing mandated by the DHSS or DNR.
(I) During each inspection, but no
less than annually, a bacteriological water
sample shall be collected by the administrative authority and analyzed for the presence
of coliform bacteria; and
(II) A nitrate sample shall be collected when deemed necessary by the administrative authority and at least annually when
a chlorinator is present. Wells exceeding
nitrate levels of ten (10) ppm shall not be
used for drinking water; a permanent alternative water supply must be provided.
B. Water supplies with chlorinators
installed, after the effective date of this rule,
shall:
(I) Have a nitrate analysis conducted prior to installing a chlorinator;
(II) Provide two (2) consecutive
bacteriological sampling results, collected by
the administrative authority a minimum of
five (5) days apart, that are absent for total
coliform and/or E. coli; and
(III) Provide monthly bacteriological sampling results for twelve (12) months.
(a) If results are satisfactory for
twelve (12) consecutive months, the administrative authority shall determine future sampling frequencies.
(b) If bacteriological sampling
results continue to indicate the presence of
total coliform, the well may be deemed
unsafe by the DHSS.
(c) If two (2) water samples collected by the administrative authority within a
twelve (12)-month period separated by at
least thirty (30) days are E. coli positive, the
well shall be deemed unsafe by the DHSS,
unless immediate corrective actions can be
taken to provide safe drinking water. These
corrective actions must be approved by the
DHSS.
C. Private water supplies not meeting
satisfactory bacteriological water results shall
be placed under a Boil Water Order or Boil
Water Notice/Advisory. Private water supplies not meeting satisfactory chemical or
radiological water results shall be placed
under a Limit Use Order.
5. During a Boil Water Order (including
precautionary Boil Water Notice/Advisories)
or a Limit Use Order issued on a public
and/or private water supply, the operator
shall comply with the following intermediate
process(es) until permanent corrections have
been made to the water supply:
A. Notify guests, verbally and again
by written notice prominently placed in each
rented guest room, that the plumbed water is
not potable and only potable water should be
used for drinking and/or brushing of teeth.
Additional restrictions for water use may be
required by the DHSS;
B. Discard ice that may have been
made from or exposed to contaminated
water; and
C. Obtain a temporary, alternate supply of potable water using one of the following practices:
(I) Individual containers of commercially bottled water shall be placed in
each rented guest room and additional bottled
water shall be available upon request by
guests;
(II) Bulk water containers acceptable to the DHSS and which are filled from a
source acceptable to the DHSS or DNR may
be used. Such water shall be treated with an
appropriate concentration of residual disinfectant to effectively counteract potential
contamination that may be introduced
between the filling of the container(s) and the
dispensing of the water. This water shall be
transported and handled in a safe and sanitary
manner, which prevents contamination; or
(III) Other methods approved by
the DHSS or DNR.
D. Community and noncommunity
public water supplies shall comply with all
mandated requirements issued by the DNR,
local water district or utilities.
6. For a Boil Water Order to be lifted
on private water supplies, the operator shall
comply with one (1) of the following permanent corrections:
A. Provide a chlorinator and comply
with (3)(A)1.B. and (3)(A)4.B.(II);
B. Provide an alternate connection to
an adjacent plumbing source of water acceptable to the DHSS and/or DNR, which is protected from contamination and capable of
supplying a sufficient quantity of water; or
C. Other permanent disinfection process(es) or permanent corrective measure(s)
as authorized by the DHSS.
7. For a Limit Use Order to be lifted for
public and/or private water supplies, the
operator shall comply with one (1) of the following permanent corrections:
A. Provide an alternate connection to
an adjacent plumbing source of water acceptable to the DHSS and/or DNR, which is protected from contamination and capable of
supplying a sufficient quantity of water; or
B. Other permanent corrective measures that provide a safe water supply, as
approved by the DHSS.
(B) Wastewater Handling. Sewage and
Wastewater Treatment and Disposal Systems.
1. On-site sewage treatment and disposal systems which generate three thousand
(3,000) gallons or less of wastewater per day
and are maintained in a subsurface treatment
and disposal system shall be regulated by the
DHSS.
A. Any on-site wastewater treatment
system installed after January 1, 1996 shall
be constructed according to 19 CSR 20-3.060
Minimum Construction Standards for OnSite Sewage Disposal Systems or applicable
local ordinance.
B. On-site wastewater treatment systems shall be operated and maintained to preclude surfacing or discharging effluent, production of odors or the creation of a habitat
for insect breeding, contamination of surface
water or groundwater or creation of a nuisance or health hazard.
C. Malfunctioning systems shall be
renovated according to 19 CSR 20-3.060
Minimum Construction Standards for OnSite Sewage Disposal Systems or applicable
local ordinance.
2. Wastewater treatment and disposal
systems which generate more than three thousand (3,000) gallons of wastewater per day or
are connected into waste stabilization ponds,
or other alternative systems which discharge
shall be regulated by the DNR.
A. Any wastewater treatment system
installed after February 2002 shall have a
National Pollutant Discharge Elimination
System (NPDES) Permit, a General Permit
or Exemption Letter issued by the DNR.
B. Wastewater treatment systems shall
be operated and maintained to preclude the
production of odors or creation of a habitat
for insect breeding, growth of tall weeds or
trees on or in a lagoon or its berm, or creation of a nuisance or health hazard.
(C) Sanitation/Housekeeping. Lodging
establishments shall be kept in a clean and
sanitary condition, in good repair, and shall
be maintained and operated with strict regard
to the health and safety of the patrons. The
following items shall be held in compliance:
1. Walls, floors and ceilings of guest
rooms shall be kept clean and in good repair.
Furnishings, including draperies, beds, appliances, furniture and lamps, shall be kept
clean and in good repair;
2. Clean and proper housekeeping shall
be employed in guest rooms and related facilities;
A. A room in use shall be cleaned at
least each time a different guest rents the
room. If the same guest continuously occupies a room, the room shall be cleaned at
least weekly.
B. Clean towels and washcloths shall
be provided in the guest room each day that
guest room is occupied by a different guest.
C. Clean bed linens shall be provided
in the guest room each day that guest room is
AND SENIOR SERVICES
Public Health
occupied by a different guest. If the same
guest continuously occupies a room, bed
linens shall be changed at least weekly.
Bedspreads shall be clean and maintained in
good repair.
D. Mattresses and boxsprings shall be
clean and in good repair. The sleeping surfaces of a mattress in use shall be completely
covered by a sheet. Excessively damaged or
soiled mattresses and/or boxsprings shall be
replaced.
E. Single-service drinking glasses
and/or utensils, if provided in guest rooms,
shall be prepackaged.
F. Insects, rodents, and other pests
shall be controlled to minimize their presence
on the premises by routinely inspecting the
premises for evidence of pests, eliminating
harborage conditions and using methods, if
pests are found, such as trapping devices or
other means of pest control. If rodenticides
and/or pesticides are used and/or stored on
the premises, they shall be stored away from
areas containing food and not accessible to
guests.
G. Ice provided for guests and
patrons’ use shall be from a commercial
source or made from a potable water supply
approved by the DHSS or DNR. The ice
shall be protected from contamination, which
shall include the following:
(I) Ice machines, dispensers or
chests shall be sheltered from the weather,
kept in good repair and the ice compartment
shall be kept clean and free of mold, rust,
debris, foreign objects or other contaminants.
Existing establishments operating before
February 2002 may continue to use existing
chest type ice machines and dispensers. All
establishments that replace or add a new selfservice ice machine for guest use shall only
provide dispensing type self-service ice
machines;
(II) Ice machines and ice trays
within guest refrigerators shall be kept clean
and sanitary. Ice shall be removed from the
ice bin and ice trays each time a different
guest rents the room;
(III) An approved scoop with a handle that is seamless and without cracks shall
be provided for each bin-type ice machine or
chest. The scoop may be stored in a holster
in the ice compartment, in a smooth nonabsorbent holder outside the ice machine or
chest, or in another manner acceptable to the
administrative authority; and
(IV) Individual ice buckets or containers, if provided, shall be kept clean, in
good repair, and constructed of a smooth,
non-absorbent, food-grade material.
(a) If a food-grade single service
liner is provided, the individual ice buckets/containers shall be washed, rinsed and
sanitized as needed. Reuse of the food-grade
single service liner is forbidden.
(b) If a food-grade single service
liner is not provided, the individual ice buckets/containers shall be washed, rinsed and
sanitized at least each time a different guest
rents the room.
H.
Ice
buckets/containers
and
reusable glasses and utensils, if provided,
shall not be located within the room housing
the toilet unless approved by the administrative authority.
I. Ice buckets/containers, reusable
glasses and utensils, if provided, shall be
washed, rinsed and sanitized using one (1) of
the following practices. Exception: Guest
rooms provided with kitchenettes—
(I) A sink with at least three (3)
compartments shall be provided for manually
washing, rinsing, and sanitizing the reusable
items. Sink compartments shall be large
enough to accommodate immersion of the
largest piece of equipment and utensil;
(II) A mechanical dishwasher that
meets the requirements for washing, rinsing
and sanitizing as outlined in 19 CSR 201.025 Sanitation of Food Establishments; or
(III) Other methods approved by
the administrative authority.
J. The guest rooms, buildings and
premises shall be kept neat and free of refuse
and debris.
(I) Garbage and refuse shall be
stored in a covered durable, leak-proof and
vermin-proof non-absorbent container. If
there is evidence of vermin or a creation of a
nuisance or health hazard, outdoor trash containers shall be stored on a smooth, hard surface such as concrete or machine-laid asphalt
that is sloped to drain, or other methods
approved by the administrative authority.
(II) Garbage and refuse shall be
disposed of on a routine basis.
(III) Plant growth or other items in
close proximity to the lodging establishment
and its attendant facilities shall be maintained
so as not to create a nuisance through harborage (cover) for pests such as rodents, vermin,
reptiles and other small animals.
(IV) Items creating harborage for
insects or vermin, or creating a health or
safety hazard, shall be removed;
3. Lodging establishments that store,
prepare, package, serve, vend or otherwise
provide food(s), other than prepackaged nonpotentially hazardous food, for human consumption directly or indirectly to a consumer,
where consumption is on or off the premises
and regardless of whether there is a charge
for the food, shall be considered a food establishment and shall be regulated according to
19 CSR 20-1.025 Sanitation of Food
Establishments or applicable local ordinance;
4. Lodging establishments that offer
only commercially prepared, individuallyportioned prepackaged foods that are nonpotentially hazardous and/or whole-uncut fresh
fruits and vegetables and/or only prepare coffee for guest use shall not be considered a
food establishment, and shall comply with
the following requirements:
A. Food shall be of sound condition,
free from spoilage, filth or other contamination and shall be safe for human consumption;
B. Condiments served shall be provided in individual packages;
C. Single service articles shall be
stored, handled and dispensed in a manner
that prevents contamination of surfaces,
which may come into contact with food or
with the mouth of the user;
D. Food serving areas and food contact surfaces shall be smooth, free of breaks,
open seams, cracks, chips and similar imperfections;
E. Food shall be stored and presented
in such a way as to be protected from crosscontamination; and
F. Employees shall observe good
hygienic practices during all working periods
of food service. Employees shall wash their
hands prior to beginning work, during work,
and as often as necessary to keep them clean,
and after using the toilet, smoking, eating
and drinking; and
5. Coffeemakers and coffeepots used by
the lodging establishment for preparing coffee to the guests or provided in guest rooms,
shall not be located within the room housing
the toilet unless approved by the administrative authority and shall be washed, rinsed and
sanitized using one (1) of the following methods and/or equipment:
A. A sink with at least three (3) compartments shall be provided for manually
washing, rinsing, and sanitizing the coffeemakers and coffeepots. Sink compartments shall be large enough to accommodate
immersion of the largest piece of equipment
and utensil;
B. A mechanical dishwasher that
meets the requirements for washing, rinsing
and sanitizing as outlined in 19 CSR 201.025 Sanitation of Food Establishments;
C. A clean-in-place method shall be
designed so that cleaning and sanitizing solutions circulate throughout the fixed system
and contact all interior food contact surfaces;
the system shall be self-draining or capable of
being completely drained of cleaning and
sanitizing solutions, and the cleaning and sanitizing solutions used are intended for food
contact surfaces; or
D. Other methods approved by the
administrative authority.
(D) Life Safety. The lodging establishment
shall be constructed, operated and maintained
with strict regard to health and safety.
1. Operation and maintenance requirements are as follows:
A. Combustibles, whether solid, liquid or gaseous, shall be properly used and
stored so that they do not present a hazard to
health or life safety;
B. Toxic, corrosive, oxidizing or other
hazardous materials shall be properly used,
stored, and disposed of in such a manner that
they do not present a hazard to health or life
safety;
C. All guards placed on the sides of
open face stairs shall be attached to the stair
in a sturdy manner and maintained in good
repair. All railings for balconies shall be
attached to the balcony in a sturdy manner
and maintained in good repair;
D. There shall be no storage on stairs
or landings;
E. Stairways, walks, ramps and
porches shall be kept free of ice and snow;
F. If the administrative authority suspects that defects are present with regard to
the integrity of the structure or electrical system of the lodging establishment, that authority may require the owner to retain the services of a professional engineer to certify the
lodging establishment for building safety;
G. Buildings must be adequately
maintained to assure safe and sanitary conditions;
H. All repairs, additions and maintenance must be conducted in a manner that
produces safe and sanitary conditions; and
I. Facilities using fuel-fired equipment or appliances that pose a potential carbon monoxide risk, including facilities with
attached parking garages or wood burning
fireplaces, shall install a carbon monoxide
detector(s). Carbon monoxide detectors shall
be installed according to manufacturer’s
specifications and should not be placed within five feet (5') of gas-fueled appliances or
near cooking or bathing areas. Exception:
carbon monoxide detectors installed prior to
the effective date of this rule.
(I) Carbon monoxide detectors
shall not be required to be installed in the
attached parking garage area.
(II) Carbon monoxide detectors
shall be required in rooms adjoining or sharing a common ventilation system with the
attached parking garage.
(III) Carbon monoxide detectors
shall be in good working condition. If the
battery-operated detector is routinely not
operational, the owner shall install a detector
that is hardwired with battery backup.
(IV) By September 2010, all carbon monoxide detectors shall be hardwired
with battery backup. All additional carbon
monoxide detectors shall be maintained and
in good working condition.
(V) Carbon monoxide detectors
shall be tested at least monthly or as needed
to ensure they are operating properly and batteries shall be changed as needed.
2. Electrical. Installation and maintenance of electrical components shall be in
compliance with local codes when applicable.
In the absence of local codes, the following
requirements shall be met:
A. New lodging establishments having electrical outlets installed within five feet
(5') of wet locations or outdoors are required
to be fitted with ground-fault circuit interrupters. Existing lodging establishments
undergoing a major renovation or rewiring
shall be required to install ground-fault circuit interrupters in electrical outlets located
within five feet (5') of wet locations or outdoors;
B. Electrical switches, outlets and
junction boxes must be covered and properly
protected from physical damage at all times;
C. All appliances must be grounded
to design specifications;
D. Wire splices shall be located in
covered junction boxes at all times;
E. Bare or frayed wiring is prohibited;
F. Three (3)-prong receptacles must
be
properly
grounded
at
all
times.
Nongrounded three (3)-prong receptacles in
existing lodging establishments shall be
replaced with two (2)-prong receptacles or
properly grounded;
G. Public hallways, stairways, landings, and foyers shall be sufficiently illuminated at all times to prevent tripping or other
injuries to persons;
H. Exit signs shall be provided when
guest room doors open to an interior corridor
and where guest room doors open to the outside but not directly at grade level;
I. Exit signs shall be maintained in a
clean and legible condition and shall be illuminated at all times that the building is occupied. For new construction, supplemental
directions signs, when necessary, shall be
installed indicating the direction and way of
egress;
J. All emergency lighting shall be
maintained in good working condition.
(I) Emergency lighting shall be provided when guest room doors open to an interior corridor and where guest room doors
open to the outside but not directly at grade
level;
K. Temporary wiring and flexible
cords shall not be used in place of fixed
wiring.
(I) Use of extension cords longer
than six feet (6') shall be prohibited unless
provided with over-current protection or
rated with properly sized wire. No more than
two (2) extension cords per room may be
used;
L. Wattage of light bulbs shall not
exceed the wattage rating of corresponding
light fixtures;
M. Empty light sockets are prohibited;
N. Circuit boxes shall be protected
from physical damage and maintained in
good condition. Storage of items that obstruct
the vision of or access to circuit boxes is prohibited; and
O. Access to electrical panels shall be
unobstructed; fuses and circuits must be
labeled for identification.
(E) Fire Safety.
1. Operation and maintenance requirements for existing and new lodging establishments.
A. All facilities shall comply with all
local building codes, fire codes and ordinances.
B. Housekeeping practices that ensure
fire safety shall be maintained daily.
C. No fresh-cut Christmas trees shall
be used unless they are treated with a flame
resistant material. Documentation of the
treatment shall be on file at the facility.
D. No door in any means of egress
shall be locked against egress when the building is occupied.
(I) Delayed egress locks shall be
permitted in buildings provided with a fire
alarm system and/or an approved supervised
automatic sprinkler system. No more than
one (1) such device may be located in any one
(1) egress path, and the door lock must
unlock upon loss of power to the building,
upon actuation of the fire alarm system, or
upon actuation of the approved supervised
automatic sprinkler system in the building.
E. Every bathroom door shall be
designed to allow opening from the outside
during an emergency when locked.
F. Doors serving a single dwelling
unit shall be permitted to be provided with a
lock, however, a key operation shall be
allowed, providing that the key cannot be
removed when the door is locked from the
side from which egress is made.
G. Textile materials having a napped,
tufted, looped, woven, nonwoven or similar
surface shall not be applied to walls or ceilings unless they are treated with a flame
AND SENIOR SERVICES
Public Health
resistant material. Documentation of the
treatment shall be on file at the facility.
H. Foam plastic materials or other
highly flammable or toxic material shall not
be used as an interior wall, ceiling or floor
finish unless approved by the administrative
authority.
I. Hangings or draperies shall not be
placed over exit doors or located to conceal
or obscure any exit.
J. Mirrors shall not be placed on exit
doors or adjacent to any exit that may confuse
the direction of exit.
K. Portable fire extinguishers (5
pound, 2A-10BC) shall be required for the
protection of all guests and located in the
hallways, mechanical room(s), laundry
area(s) and all other hazardous areas.
(I) The maximum travel distance to
a fire extinguisher from a guest room door
that opens into an interior corridor or a guest
room door that opens to the outside but not
directly at grade level shall be no greater than
seventy-five feet (75') and accessible to the
guest.
(II) All fire extinguishers shall be
maintained in a fully charged and operable
condition and inspected annually by a fire
extinguisher company, fire department representative or other entity approved by the
administrative authority.
(III) Fire extinguishers having a
gross weight not exceeding forty (40) pounds
shall be installed so that the top of the extinguisher is not more than five feet (5') above
the floor. Extinguishers having a gross
weight more than forty (40) pounds shall be
installed so that the top of the extinguisher is
not more than three and one-half feet (3 1/2')
above the floor. In no case shall the clearance between the bottom of the extinguisher
and the floor be less then four inches (4").
L. There shall be no louvers or other
air passages penetrating the wall except properly installed heating and utility installations.
M. Guest room doors shall be provided with room latches or other mechanisms
suitable for keeping the doors closed.
N. Guest room doors shall be selfclosing or provided with a closing device that
closes the door automatically upon detection
of smoke. Door-closing devices shall not be
required in buildings protected throughout by
an approved, automatic sprinkler system or
when the guest room door opens directly to
the outside of the dwelling unit at or to grade
level.
O. Smoke detectors shall be installed
in all sleeping rooms, cooking areas/kitchens,
hallways, laundry rooms, mechanical rooms,
hazardous areas and where specifically stated
within this rule. Heat sensing devices may be
installed in cooking areas in lieu of a smoke
detector(s).
(I) Smoke detectors and heat sensing devices shall be maintained in good operating condition.
(II) If a wireless system is used, the
system shall be designed, installed and maintained in accordance with the National Fire
Protection Association 72, National Fire
Alarm Code 2002 Edition or equivalent code.
(III) Smoke detectors shall be tested at least monthly or as needed to ensure
they are operating properly and batteries shall
be changed as needed.
(IV) All hardwired-interconnected
smoke detectors shall be tested and approved
annually by a sprinkler company, fire alarm
company, fire department representative or
other entity approved by the administrative
authority.
(V) The administrative authority
may require the installation of additional
smoke detectors at any time.
P. All fire alarm systems and sprinkler systems shall be tested and approved
annually by a fire alarm company, sprinkler
company, fire department representative or
other entity approved by the administrative
authority.
Q. Individual fire sprinklers plumbed
into a potable water line over gas water
heaters and/or furnaces shall not be required
to be tested and approved annually unless
required by local ordinance.
R. An evacuation route diagram
reflecting the actual floor or exterior doors
that lead outside of the dwelling unit at street
or ground level arrangement, exit locations,
and room identification shall be posted in a
location and manner acceptable to the administrative authority in every guest room or
immediately adjacent to every guest room
door. Guest room doors leading directly to
the outside of the dwelling unit at grade level
are not required to post an evacuation route
diagram.
S. A copy of an emergency evacuation
plan and employee instruction guide shall be
kept on file that is accessible by all staff. All
staff shall be able to demonstrate knowledge
of the emergency evacuation plan.
T. Fire safety information shall be
available so that guests may make an
informed decision as to evacuate to the outside, evacuate to an area of refuge, remain in
place, or employ any combination of the three
(3) options.
2. Existing lodging establishments shall
also meet the following requirements:
A. All facilities that use stairs as a
component in the means of egress shall comply with the following:
(I) All open face stairs shall have
guards placed on the sides. Guards shall be
placed so that a four inch (4") diameter
sphere cannot pass through them;
(II) Handrails for stairs shall not be
less than thirty-four inches (34") and not
more than thirty-eight inches (38") above the
surface of the tread, measured vertically to
the top of the rail from the leading edge of the
tread;
(III) Railings for balconies shall not
be less than forty-two inches (42") in height.
Guards shall be placed so that a four inch
(4") diameter sphere shall not pass through
them; and
(IV) Existing handrails, railings
and guards for stairs may continue to be used
subject to approval of the administrative
authority;
B. All facilities that use ramps as a
component in the means of egress shall comply with the following:
(I) Ramps shall have a minimum
width of forty-four inches (44") in all facilities;
(II) Ramps shall have a slip resistant surface;
(III) Ramps that are greater than six
inches (6") in height shall have handrails and
guards placed on each side. The handrails
and guards shall comply with the stair
requirements in (3)(E)2.A.(I)–(IV); and
(IV) Existing ramps may continue
to be used subject to approval of the administrative authority;
C. Floors that separate stories in a
building shall be maintained as a smoke barrier to provide a basic degree of compartmentation;
D. Openings through floors, such as
hoistways for elevators, shaftways used for
light, ventilation or building services; or
expansion joints and seismic joints used to
allow structural movements shall be enclosed
with fire barriers (vertical), such as wall or
partition assemblies whose fire resistance rating is not less than thirty (30) minutes. Such
enclosures shall be continuous from floor to
floor. Openings shall be protected as appropriate for the fire resistance rating of the barrier;
E. Service openings such as laundry
chutes, dumbwaiters and inclined and vertical
conveyors shall be provided with closing
devices and must be kept closed when not in
active use. Outlet doors for trash or laundry
chutes shall open only to a separate room
designed exclusively for that purpose. This
room shall be provided with a one (1)-hour
fire rated door that is self-closing. Existing
installations may continue to be used upon
approval of the administrative authority.
(I) Service openings provided with
closing devices shall be self-closing, with a
positive-latching frame and door assembly of
one (1)-hour fire rating.
(II) Vertical conveyors and chutes
shall be separately enclosed by walls or partitions. Service openings shall not open to an
exit. Existing installations may continue to
be used upon approval of the administrative
authority;
F. All guest rooms shall have a means
of egress to the outside of the building at or
to grade level;
G. Egress routes that have been
approved prior to February 2002 shall not be
altered without prior approval by the administrative authority;
H. Dead-end corridors or hallways
shall not exceed fifty feet (50');
I. No door or path of travel in a
means of escape shall be less than twentyeight inches (28") wide. Bathroom doors
shall not be less than twenty-four inches
(24") wide;
J. All guest rooms opening into an
interior corridor(s) shall be separated by
walls and twenty (20)-minute fire protec-
tion-rated doors, forty-four millimeters
(44 mm) (one and three-fourths inch
(1 3/4")) solid-bonded wood-core doors,
steel-clad (tin-clad) wood doors, solid-core
steel doors with positive latch and closer, or
as approved by the administrative authority;
K. Existing transoms shall be permitted but must be permanently fixed in the
closed position;
L. Smoke detectors and heat sensing
devices should be installed on the ceiling,
preferably in the center, but no less than four
inches (4") from the wall of the sleeping area
or on a sleeping room wall between four and
twelve inches (4"–12") from the ceiling or as
otherwise approved by the administrative
authority;
M. If a battery-operated detector is
routinely not operational, the owner shall
install a detector that is hardwired with a battery backup;
N. By September 2010, all smoke
detectors and heat sensing devices shall be
hardwired with battery backup; and
O. Existing fire alarm systems and
sprinkler systems shall be maintained in good
working order.
3. New lodging establishments shall
meet these additional requirements. In addition to the required certification that the
establishment has been designed and erected
in accordance with the 2002 Edition of a
national code(s), the DHSS has outlined minimum requirements for the maintenance of
fire safety components and the installation of
smoke detectors, fire alarm systems, sprinkler systems, and fire extinguishment to provide adequate life safety protection to ensure
the safety of the occupants.
A. Lodging establishments meeting
the definition of a bed and breakfast may
have two (2) secondary means of egress that
are independent and remote from one another in lieu of a primary means of egress.
B. Smoke detectors and/or heat sensing devices shall be installed on the ceiling,
preferably in the center, but no less than four
inches (4") from the wall of the sleeping area
or on a sleeping room wall between four and
twelve inches (4"–12") from the ceiling.
(I) All smoke detectors and/or heat
sensing devices shall be hardwired with battery backup.
C. A fire alarm system shall be
installed and maintained in accordance with
the National Fire Protection Association 72,
National Fire Alarm Code 2002 Edition or
equivalent code and maintained in good
working order. Exception 1: Single story
buildings with guest room doors that open
directly to the outside at grade level.
Exception 2: Buildings with no more than
three (3) occupiable stories and with no more
than four (4) guest rooms per building with
guest room doors that lead directly outside at
or to grade level.
(I) When a fire alarm system is
required, all smoke detectors and/or heat
sensing devices shall be interconnected,
except those located in sleeping rooms.
D. All buildings shall be protected
throughout by an approved, supervised automatic sprinkler system in accordance with the
National Fire Protection Association 13,
Standard for the Installation of Sprinkler
Systems 2002 Edition or the National Fire
Protection Association 13R Standard for the
Installation
of
Sprinkler
Systems
in
Residential Occupancies up to and Including
Four Stories in Height 2002 Edition or equivalent code.
(I) Bed and breakfasts and buildings with no more than three (3) occupiable
stories, where all guest rooms have a door
that opens directly to the outside at or to
grade level or to an exterior exit access are
not required to be protected throughout by an
approved, supervised automatic sprinkler system.
(F) Swimming Pools/Spas. Design, maintenance and operation of swimming pools,
spas, and other bathing facilities shall be in
accordance with the following requirements:
1. New swimming pools and swimming
pools undergoing a major renovation, such as
installing a diving board or slide, shall be
designed by a professional engineer and certified by a professional engineer, architect or
other qualified professional approved by the
administrative authority. The design must
comply with a national swimming pool code;
2. Requirements regarding the general
safety of swimming pools are as follows:
A. Swimming pools shall be protected by a fence, wall, building or other enclosure that is at least four feet (4') in height.
The enclosure shall be made of a durable
material. Artificial barriers shall be constructed so as to afford no external handholds, footholds, or opening large enough to
pass a four inch (4") diameter sphere
through. Existing installations may continue
to be used upon approval of the administrative authority;
B. Gates shall be equipped with a
self-closing and positive self-latching closure
mechanism. The latch shall be installed as
high as possible, but no greater than four feet
(4'), to preclude access of a toddler;
C. Doors leading into an indoor pool
area shall be installed with self-closing and
positive self-latching closure mechanism(s).
The closure mechanism shall be installed as
high as possible, but no lower than four feet
(4') in height. Other means of precluding the
access of a toddler into the indoor pool area
must be approved by the administrative
authority;
D. All natural barriers, hedges, swimming pool covers, or other protective devices
must be approved by the administrative
authority;
E. Depth of water shall be plainly
marked with four inch (4")-high numbers, of
a contrasting color to the pool background
color, at or above the water surface on the
vertical pool wall and on the edge of the
deck, at maximum and minimum points of
break between the deep and shallow portions,
and at intermediate increments of depth,
spaced at not more than twenty-five feet (25')
intervals measured peripherally.
(I) Markings shall be on both sides
and ends of the swimming pool.
(II) Where depth markings cannot
be placed on the vertical walls above the
water level, other means shall be used so that
the markings will be plainly visible to persons in the swimming pool;
F. Lifesaving equipment, consisting of
both a throwable device and a reaching
device, shall be provided for all swimming
pools. Swimming pools over two thousand
(2,000) square feet and up to four thousand
(4,000) square feet of water surface area shall
have two (2) throwable and reaching devices.
AND SENIOR SERVICES
Public Health
Approval by the administrative authority shall
be required for swimming pools in excess of
four thousand (4,000) square feet of water
surface area.
(I) A throwable device shall be a
U.S. Coast Guard approved device, fitted
with a one-quarter inch (1/4")-diameter line
with a length of 1.5 times the maximum
width of the swimming pool or fifty feet
(50'), whichever is less and a reaching device
shall be a life pole or shepherd’s crook type
of pole, having blunted ends with a minimum
length of twelve feet (12') or as approved by
the administrative authority. This equipment
shall:
(a) Be mounted in conspicuous
places, distributed around the pool deck;
(b) Be kept in good repair and
ready condition; and
(c) Be kept in an established
location and shall be used only for its intended purpose;
G. Whenever the swimming pool area
is less than two thousand (2,000) square feet
of water surface area and is opened for use
and no lifeguard service is provided, warning
signs shall be placed in plain view of the
entrances and inside the pool area which state
“WARNING—NO
LIFEGUARD
ON
DUTY” with plainly legible letters;
H. Swimming pools having two thousand (2,000) square feet of water surface area
or greater shall have a certified lifeguard present at all times the pool is available for use.
In swimming pools with two thousand
(2,000) square feet of water surface area or
more, one (1) additional certified lifeguard
shall be provided for each additional two
thousand (2,000) square feet of water surface
area;
I. A first aid kit must be readily available to lodging employees for pool use at all
times. The first aid kit shall be stored in an
easily accessible location (such as the front
office);
J. No glass containers shall be used in
the swimming pool area;
K. The swimming pool and pool deck
shall be kept clean of sediment, floating
debris, visible dirt and algae; free of cracks,
peeling paint and tripping hazards. Pools
shall be refinished when the pool surface cannot be maintained in a safe and sanitary condition;
L. Rooms that house a gaseous chlorine introduction system shall be located on
the opposite side of the pool from the direction of the prevailing winds and must provide
the following features:
(I) A respiratory protective device
suitable to provide protection during exposure to chlorine gas. This device shall be
housed in a convenient location outside the
chlorine room, which is quickly and readily
accessible;
(II) An airtight duct at a maximum
of eight inches (8") above the floor that terminates at a safe point of discharge to the outside away from the pool deck;
(III) A ventilating fan, capable of
one (1) air change per minute and operated
from a switch located outside the chlorine
room door in conjunction with the airtight
duct;
(IV) A louvered air intake near the
ceiling;
(V) Adequate lighting with the light
switch located outside the chlorine room,
adjacent to the chlorine room door; and
(VI) A plastic bottle of ammonia
for leak detection; automatic chlorine detectors are recommended;
M. Chlorine and chlorinating equipment shall be housed in a separate room.
This room shall have no openings to other
interior openings; and
N. Chlorine-feeding devices shall be
designed to automatically terminate gas feed
when the water supply flow is interrupted.
The release of chlorine gas shall be terminated when the recirculation pump is shut off;
3. Requirements regarding the water
quality of swimming pools and spas are as
follows:
A. Swimming pools and spas shall be
designed and maintained to provide for continuous disinfection of the water with a chemical or process which is an effective disinfectant and which imparts an easily measurable,
active residual;
B. The disinfecting materials and
methods shall not be dangerous to public
health, create objectionable physiological
effects, or impart toxic properties to the
water;
C. An easily adjustable, automatic
disinfection feeder shall be provided for the
continuous application of disinfectant to the
pool and/or spa water. The concentration of
disinfectant in the pool and/or spa water must
be maintained at the following levels:
(I) When chlorine is the disinfectant, a free chlorine residual of at least one
part per million (1.0 ppm) shall be maintained throughout the pool. When bromine is
the disinfectant, a minimum residual between
three and five (3–5) ppm shall be maintained
throughout the spa; and
(II) Other disinfecting materials or
methods are subject to approval of the administrative authority and may only be used
when it has been demonstrated that they provide a satisfactory residual which is easily
measured and operated according to the manufacturer’s specifications;
D. An appropriate test kit shall be
provided and capable of properly measuring
disinfectant and pH residual;
E. The pH of the swimming pool and
spa water shall be maintained at a level
between 7.2 and 7.8; and
F. Swimming pool water shall have
sufficient clarity that the main drain cover is
readily visible at the deepest point of the pool
when viewed from the side of the pool;
4. Requirements regarding the maintenance and operation of swimming pools and
spas are as follows:
A. A boundary line between the shallow and deep water shall be marked at the
point where the swimming pool slope begins,
or at the five foot (5') depth, by a line of contrasting color on the floor and walls of the
pool, and by a safety rope and floats
equipped with float keepers;
B. Steps, ladders or stairs shall be
provided at the shallow end (less than five
feet (5') and steps or ladders shall be provided in the deep end (greater than five feet (5').
If the pool is over thirty feet (30') wide, such
steps, ladders or stairs shall be installed on
each side.
(I) Pool steps, ladders, and stairs
shall be easily cleanable, corrosion-resistant
and equipped with non-slip treads.
(II) All ladders shall be designed so
as to provide a handhold. Where steps or ladders are provided, there shall be a handrail at
the top of each side thereof extending over the
coping of the edge of the deck. When stairs
are provided, there shall be a handrail provided.
(III) Pool steps, ladders, stairs and
handrails shall be maintained in good repair
at all times;
C. Daily operating records shall be
maintained and be available upon request.
The residual concentration of the disinfectant
used in the pool and/or spa, pH, water temperature and the date and time the information was collected shall be recorded;
D. Indoor pool areas and chemical
storage rooms shall be vented directly to the
exterior or vented to a room that is vented
directly to the exterior;
E. Any chemical applied in swimming pools and/or spas shall be used, handled, stored and labeled in accordance with
the manufacturer’s specifications;
F. Main drain grates shall be whole
and openings shall not be over one-half inch
(1/2") wide. Main drain grates shall be in
good repair, firmly affixed at all times and
designed and maintained to prevent user
entrapment;
G. All pool and spa equipment shall
be kept clean and in good repair at all times;
H. Diving boards and slides shall be
maintained in good repair at all times;
I. A cleaning system shall be provided to remove dirt from the bottom of the
pool;
J. Surface skimmers, strainer baskets
and perimeter overflow systems shall be kept
clean and in good repair;
K. Water shall be maintained at the
overflow level; and
L. Discharged pool water shall conform to the DNR regulations;
5. Requirements regarding the lighting
and electrical systems for swimming pools
and spas are as follows:
A. Artificial lighting shall be provided at swimming pools used at night or which
do not have adequate natural lighting so that
all portions of the pool, including the bottom,
are readily seen without glare;
B. All lighting shall be maintained in
good repair at all times;
C. All receptacles on the property
shall be located at least ten feet (10') from the
inside walls of a pool. One (1) receptacle to
provide power for a recirculating pump motor
on permanently installed swimming pools
shall be permitted not less than five feet (5')
from the inside walls of the pool provided the
receptacle is single, of the locking and
grounding types and protected by a groundfault circuit interrupter;
D. All receptacles located within
twenty feet (20') of the inside walls of a pool
shall be protected by a ground-fault circuit
interrupter;
E. Switching devices on the property
shall be located at least five feet (5') from the
inside walls of a pool unless separated from
the pool by a solid fence, wall or other permanent barrier; and
F. Swimming pool areas over which
utility-owned, operated and maintained supply lines, service drops, electrical lines and
communication lines (i.e., telephone, cable
TV) pass shall be approved in writing by the
utility company;
6. The recirculation system serving the
swimming pool and/or spa shall operate continuously or in accordance with manufacturer’s specifications/recommendations or other
engineering criteria;
7. Spas shall meet the additional following requirements: Exemption—a spa used
under direct supervision of qualified medical
personnel is excluded:
A. The maximum water depth shall
be four feet (4') measured from the water
line. The maximum depth of any seat or sitting bench shall be two feet (2') measured
from the water line;
B. Water temperature controls shall be
provided to prevent water temperatures from
exceeding
one
hundred
four
degrees
Fahrenheit (104°F). The controls shall be
accessible only to the swimming pool operator;
C. Outlets shall be designed so that
each pumping system prevents user entrapment;
D. The agitation system shall be separate from the water treatment recirculation
system. The agitation system shall be connected to a timer; and
E. A legible sign visible from the spa
shall be provided. The sign shall contain
wording to the effect of:
(I) Caution. Any person having an
acute or chronic disease such that use of this
spa might adversely affect their health should
consult a physician before using this spa;
(II) Do not use the spa alone or
without supervision;
(III) Do not use the spa longer than
ten (10) minutes;
(IV) Children shall be accompanied
by an adult; and
(V) Additional precautionary information may be added as deemed necessary by
the lodging establishment or manufacturer.
(G) Plumbing/Mechanical. Installation and
maintenance of plumbing supply lines and
equipment shall be in compliance with local
codes when applicable. In the absence of
local codes the following requirements shall
be met:
1. General requirements are as follows:
A. Hot and cold running water shall
be available at all times;
B. Restrooms shall be provided with
adequate ventilation to prevent excessive condensation, mold or algae growth or odors.
New lodging establishments shall provide
mechanical ventilation;
C. Adequate venting of the drainage
system shall be provided and vents shall
extend above the roof;
D. All fixtures shall be adequately
and properly trapped;
E. Openings for the passage of
plumbing shall be vermin proof; and
F. No fitting, connection, device or
method of installation shall obstruct or retard
the flow of water, wastes, sewage or air in the
drainage or venting system;
2. Certification of Inspection by the
Missouri Division of Fire Safety shall be
required for the following water heaters, boilers and pressure vessels. Evidence of inspection and approval shall be posted on the
premises, as well as on file with the State Fire
Marshal’s Office, Division of Fire Safety;
A. Water heaters with heat input
greater than two hundred thousand British
thermal units per hour (200,000 Btu/hr) or
fifty-seven and six-tenths kilowatts (57.6 kW)
if electric;
B. All boilers; and
C. Hot water storage tanks greater
than one hundred twenty (120) gallon capacity, and water temperatures exceeding two
hundred ten degrees Fahrenheit (210°F), and
heat input greater than two hundred thousand
(200,000) Btu/hr or fifty-seven and six-tenths
(57.6) kW if electric;
3. Water heaters and pressure vessels
not required to be inspected and approved by
the Missouri Division of Fire Safety:
A. Shall be rated for a minimum
working pressure of one hundred twenty-five
pounds per square inch (125 psi). The maximum pressure allowed shall be permanently
marked on all water heating units and holding
tanks; and
B. A separate valve or switch shall be
provided to shut the fuel supply off to water
heating units;
4. Safety devices to prevent the excessive buildup of heat and/or pressure in the
vessel must be provided on water heaters and
other pressure vessels.
A. Temperature and pressure (T&P)
relief valves are required on or adjacent to
hot water holding tanks but cannot be separated from the tank by a check valve or shutoff valve.
B. Temperature and pressure (T&P)
relief valves are required on water heaters
and must be installed so that the sensing element extends into the tank and monitors the
temperatures in the top six inches (6") of the
tank.
(I)
Relief
valves
shall
bear
imprints, plates or tags to indicate the specifications of the valve.
(II) Btu rating of the temperature
component of the T&P relief valve must be
equal to or greater than the input Btu of the
vessel it serves.
(III) Pressure rating of the pressure
component of the T&P relief valve must be
equal to or less than the pressure rating of the
vessel it serves.
C. Relief valve discharge pipes shall
be made of rigid pipe approved for water distribution with a temperature rating of two
hundred ten degrees Fahrenheit (210°F) or
other materials approved by the manufacturer
to be used for this purpose and—
(I) Be the same diameter, or larger,
as the relief valve outlet;
AND SENIOR SERVICES
Public Health
(II) Be installed so as to drain by
gravity flow and shall have no more than one
(1) elbow or be installed according to manufacturer’s specifications;
(III) Valves shall not be connected
to the relief valve discharge pipe; and
(IV) Shall not discharge so as to be
a hazard or a potential cause of damage;
5. All backflow devices used must meet
10 CSR 60-11.010 Prevention of Backflow or
local codes. Potable water supplies shall be
protected from sources of potential contamination.
A. The following shall be protected
by reduced pressure principle backflow prevention assembly: boiler units, fire sprinkler
systems with chemical additives, lawn sprinklers with facilities for injection of pesticides,
herbicides or other chemicals and pumped or
repressurized cooling or heating systems.
B. The following shall be protected by
a double-check valve assembly: facility wide
fire sprinklers not using chemical additives
and lawn sprinklers without facilities for
injection of pesticides, herbicides or other
chemicals.
C. The following shall be protected by
vacuum breakers: threaded faucets, flush
valves and shower spray hoses. Commercial
dishwashers
and
commercial
laundry
machines shall be protected by either a vacuum breaker or an air gap.
D. The following shall be protected
by air gaps: relief valve discharge pipes from
water heaters and water holding tanks, makeup waterlines for cooling towers, potable
water inlets to all plumbing fixtures, water
softeners, condensation waterlines and discharge lines from commercial laundry
machines. Swimming pool feed lines shall be
protected by either an air gap or doublecheck valve assembly.
E. The following shall be protected by
air breaks: ice containers and ice machines.
F. Fire sprinklers plumbed into a
potable water line over gas water heaters
and/or furnaces shall not be required to
install a backflow device unless required by
local ordinance;
6. Liquid propane (LP) gas systems
shall be tested for leaks on a yearly basis.
(H) Heating, Venting and Air Conditioning
(HVAC) Equipment. Air conditioning, heating, ventilating ductwork and related equipment shall be installed using acceptable procedures in a safe manner and be in good
operating condition.
1. Unvented fuel-fired heaters, fireplaces or other appliances and portable electrical space heaters shall be prohibited from
use in all areas of the lodging establishment
unless approved in writing by the manufacturer for commercial use.
2. Existing unvented fireplace installations may continue to be used, upon approval
of the administrative authority, if the following conditions are met:
A. The appliance and installation
meet the National Fire Protection Association
54 ANSI 223.1-2002, 2002 Edition National
Fuel Gas Code requirements for residential
use;
B. The local gas company conducts
an inspection to assure the appliance and
installation meet the National Fire Protection
Association 54 ANSI 223.1-2002, 2002
Edition National Fuel Gas Code requirements
for residential use;
C. A carbon monoxide detector is
installed in accordance with (3)(D)1.I.(III)–
(V); and
D. The unvented fireplace is not the
primary source of heat.
3. Gas and electric heating equipment
shall be equipped with thermostatic controls.
4. Gas water heaters, gas furnaces and
other gas appliances shall be properly vented
to the outside, and the flue pipe shall be constructed of galvanized pipe or material recommended by the manufacturer. All galvanized pipe shall be secured by screws at every
joint in the pipe.
5. Joints in gas supply pipes shall be
located outside the furnace cabinet housing.
6. Gas shutoff valves shall be located
next to all gas appliances, gas furnaces and
gas water heaters.
7. Rooms containing gas water heaters
and/or gas furnaces shall have an automatic
sprinkler head installed off the domestic
water system with a hardwired smoke detector located directly outside the room or shall
be protected throughout by an approved,
supervised automatic sprinkler system or
designed in a manner to be fire resistant.
A. The sprinkler head should be rated
for one hundred sixty-five degrees Fahrenheit
(165°F) or appropriately rated for the specific location and installed according to manufacturer’s specifications or approved by the
administrative authority. Existing installations may continue to be used upon approval
of the administrative authority.
B. The sprinkler head should be
installed in a manner so the water spray will
encompass the gas water heater and/or furnace.
C. Pipes tying into the domestic water
line shall be one-half inch (1/2") or threefourths inch (3/4") copper pipe or chlorinated polyvinyl chloride (CPVC) pipe. Existing
installations may continue to be used upon
approval of the administrative authority.
D. CPVC pipe must meet National
Fire Protection Association 13 Standard for
the Installation of Sprinkler Systems 2002
Edition and National Fire Protection
Association 13R Standard for the Installation
of
Sprinkler
Systems
in
Residential
Occupancies up to and Including Four Stories
in Height 2002 Edition.
E. A smoke detector is not required to
be located directly outside the room if the
door to the gas water heater and/or furnace
room opens directly to the outside.
F. A smoke detector is not required to
be located directly outside the room if another smoke detector is already located within
ten feet (10') of the door.
G. A fire resistant room shall consist
of walls and ceilings designed to be fire resistant for a minimum of one (1) hour, with a
one (1)-hour fire rated door and doorjamb.
All openings into this room shall be designed
with one (1)-hour fire rated materials.
8. If a gas furnace or gas water heater is
located inside a garage, it shall be at least
eighteen inches (18") above the finished floor
and enclosed inside a fire resistant room.
9. Furnaces shall be equipped with an
electrical fused switch to protect the unit
from electrical overloading and to disconnect
the electrical supply.
10. Furnace rooms and rooms containing gas water heaters or any other fuel-fired
appliance shall be provided with vents or
other approved means to supply adequate
combustion air for the units.
A.
Except
as
specified
in
(3)(H)10.D. below, there shall be two (2)
combustion air vent openings in each room
containing gas or fuel-fired appliances.
(I) One (1) shall be located at the
lower level and the other at the upper level.
(II) One (1) combustion air vent
opening shall be permitted if the vent opening
extends directly to the outside of the structure. This opening shall be one (1) square
inch per three thousand (3,000) Btu input of
the total gas appliances located in the room.
B. The vent size openings for the
combustion air shall be:
(I) Measured at one (1) square inch
per one thousand (1,000) Btu input if the
combustion air is drawn from inside the
structure;
(II) Measured at one (1) square
inch per four thousand (4,000) Btu input if
the air is drawn from outside the structure.
C. Other means of venting furnace
rooms and rooms containing gas water
heaters or any other fuel-fired appliance may
be subject to approval from the administrative
authority; and
D. Furnace rooms and/or rooms containing gas or fuel burning appliances having
a volume of fifty (50) cubic feet per one thousand (1,000) Btu/hour shall not be required
to have additional venting.
(I) The sum of the required volume
shall be calculated for all the gas appliances
located within the space.
(II) Rooms communicating directly with the space in which the appliances are
installed through openings not furnished with
doors, and through combustion air openings
sized and located appropriately shall be considered a part of the required volume.
11. Gas appliances shall have a clearance around them of one inch (1") from the
sides and back and six inches (6") from the
front of the unit or be installed to manufacturer’s specifications.
AUTHORITY: sections 192.006 and 315.005–
315.065, RSMo 2000 and Supp. 2004.* This
rule was previously filed as 13 CSR 5066.010. Original rule filed as Missouri
Division of Health E 9.01 on Sept. 4, 1957,
effective Sept. 14, 1957. Rescinded and readopted: Filed June 28, 2001, effective Feb. 28,
2002. Rescinded and readopted: Filed May 2,
2005, effective Oct. 30, 2005.
*Original authority 192.006, RSMo 1993, amended 1995,
315.005–315.065, please see Revised Statutes of Missouri
and Revised Statutes of Missouri Supp. 2004.