19 CSR 30-85.012
Construction Standards for New Intermediate Care and Skilled Nursing Facilities and Additions to and Major Remodeling of Intermediate Care and Skilled Nursing Facilities
PURPOSE: This rule establishes construction
standards for new intermediate care and
skilled nursing facilities and additions to and
remodeling of intermediate care and skilled
nursing facilities.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule
would be unduly cumbersome or expensive.
Therefore, the material which is so incorporated is on file with the agency who filed this
rule, and with the Office of the Secretary of
State. Any interested person may view this
material at either agency’s headquarters or
the same will be made available at the Office
of the Secretary of State at a cost not to
exceed actual cost of copy reproduction. The
entire text of the rule is printed here. This
note refers only to the incorporated by reference material.
PUBLISHER’S NOTE: All rules relating to
long-term care facilities licensed by the Division of Aging are followed by a Roman
Numeral notation which refers to the class
(either class I, II or III) of standard as designated in section 198.085.1, RSMo 1986.
(1) Plans and specifications shall be prepared
for the construction of all new intermediate
care and skilled nursing facilities and additions to and remodeling of existing facilities.
The plans and specifications shall be prepared in conformance with Chapter 327,
RSMo, by a duly registered architect or registered professional engineer. III
(2) The facility may submit schematic and
preliminary plans to the division showing the
basic layout of the building and the general
types of construction, mechanical and electrical systems. The facility may submit details
before the larger and more complicated working drawings and specifications so that necessary corrections can be easily made before
the final plans are submitted. The facility
shall prepare and submit working drawings
and specifications, complete in all respects,
for approval by the division. These plans
shall cover all phases of the construction project, including site preparation; paving; general construction; mechanical work, including plumbing, heating, ventilating and air
conditioning; electrical work; and all built-in
equipment, including elevators, kitchen
equipment and cabinet work. II/III
(3) Facilities shall begin construction only
after the plans and specifications have
received the written approval of the division.
Facilities shall then build in conformance
with the approved plans and specifications.
The facility shall notify the division within
five (5) days after construction begins. If
construction of the project is not started within one (1) year after the date of approval of
the plans and specifications are not completed within a period of three (3) years, the
facility shall resubmit the plans to the division for its approval and shall amend them, if
necessary, to comply with the then current
rules before construction work is started or
continued. II/III
(4) The facility shall be located on an allweather road and have easy access for vehicular traffic. III
(5) Facilities shall have access to local fire
protection. III
(6) The facility shall provide adequate roads
and walks within the lot lines to the main
entrance and service entrance. III
(7) In any new addition, an existing licensed
facility shall provide all required ancillary
service areas, proportional to the number of
new beds. However, for existing facilities,
these support service areas may be reduced
by the amount of existing areas that meet new
facility requirements. New support areas
required in this project, whether they are to
serve the new beds or the existing beds, shall
comply with the rules for new facilities. III
(8) Facilities shall have administrative and
public areas as listed: business office, administrator’s office (business office and administrator’s office may be combined); director of
nurses’ office; lobby and waiting room (may
be combined); public restrooms for each sex;
and public telephone. III
(9) The facility shall provide recreation,
occupational therapy, activity and residents’
dining space at a ratio of at least thirty (30)
square feet for each resident. II
(10) Facilities shall provide a bulk storage
area consisting of a locked room, shelving,
bins and large cans for storing long-term supplies of food and other dietary materials
above the floor in a dry room with adequate
ventilation, cool, but not freezing. The bulk
storage area shall be one (1) square foot per
bed, but in no case shall it be less than one
hundred (100) square feet. III
(11) Facilities shall have dry short-term storage areas for daily food supplies and other
dietary materials. The dry short-term storage
area may include the space required for bulk
storage. III
(12) A facility shall provide a preparation
area for wrapping removal, vegetable cleaning and peeling and meat cutting. III
(13) Facilities shall provide adequate cooking
and baking areas. III
(14) A facility shall have a salad and sandwich preparation area for the preparation of
cold foods. III
(15) Facilities shall provide a tray preparation
and loading area for preparing trays for residents’ food delivery and food cart loading. III
(16) A facility shall provide a pot and pan
washing area consisting of a three (3)-compartment sink with a double drainboard for
the washing of utensils during the food preparation period. III
(17) Facilities shall have a dishwashing area
provided with a soiled dish receiving counter,
space for scraping with a garbage grinder,
prerinse sink, counter for racking dishes,
dishwasher, clean dish counter, dish rack
storage and an exhaust fan. II/III
(18) A facility shall have a dish storage area
with shelves adjacent to the tray preparation
area. III
(19) Facilities shall provide refrigerators of
adequate capacity in all kitchens and other
preparation centers where perishable foods
will be stored. A minimum of two (2) separate sections or boxes shall be provided in the
main kitchen; one (1) for meat and dairy
products and one (1) for general storage. III
(20) The refrigerators’ compressors and evaporators shall have sufficient capacity to maintain temperatures of thirty-five degrees
Fahrenheit (35°F) in the meat and dairy
boxes and forty degrees Fahrenheit (40°F) in
the general storage boxes when the boxes are
being used for those purposes. II
(21) These compressors shall be automatically controlled. III
(22) Compressors, piping and evaporators
shall be tested for leaks and capacity. Certification of these tests shall be made available to
the division. III
(23) A facility shall have an office area for
planning menus and food purchases next to
the dietary area. III
(24) Kitchen shall have handwashing sinks.
III
(25) A facility shall have a janitor’s area,
exposed or in a closet, in or near the kitchen,
that contains a floor receptor or service sink.
III
(26) A garbage removal area with garbage
and trash cans located inconspicuously shall
be easily accessible from both the kitchen and
the service drive. III
(27) Housekeeping areas shall be provided as
listed: clean linen area, soiled linen area and
laundry area. II
(28) The facility shall have a designated physical therapy area large enough to give rehabilitative care to physically disabled residents.
This area shall be sized to accommodate all
equipment and activities in the facility’s proposed physical therapy program. In no case
shall this area be less than two hundred (200)
square feet. III
(29) The facility shall provide the following
elements: treatment areas and equipment as
dictated by the facility’s physical therapy program; a handwashing sink; an exercise area;
storage for clean linen, supplies and equipment; a toilet room located in the physical
therapy room or within the immediate area of
the physical therapy department; and an
office or sufficient space for the physical
therapy director’s desk and file. The physical
therapy area may be located adjacent to an
occupational therapy area and share any or all
of the required elements providing that the
sharing of elements conforms with the facility’s therapy programs. III
(30) If there is a designated occupational
therapy area, it shall be large enough to
accommodate all the equipment and activities
in the facility’s proposed occupational therapy program. When the facility locates physical therapy and occupational therapy in the
same area, there shall be a space that can be
separated from the rest of the area if ceramics, sculpture, minor woodwork and light
mechanical work are a part of the occupational therapy program. III
(31) Facilities shall provide a maintenance
room or area. II
(32) A facility shall provide an employees’
dressing or locker room with separate
restrooms for each sex. III
(33) Facilities shall provide storage rooms as
listed: general storage—ten (10) square feet
per bed for the first fifty (50) beds, plus eight
(8) square feet per bed for the next twentyfive (25) beds, plus five (5) square feet per
bed for any additional beds over seventy-five
(75). No storage room shall be less than one
hundred (100) square feet of floor space. The
required residents’ clothes storage room and
storage for outdoor equipment may be included in the minimum area required for general
storage. III
(34) A continuous system of unobstructed
corridors, referred to as required corridors,
shall extend through the enclosed portion of
each story of the building. These corridors
will connect all rooms and spaces with each
other and with all entrances, exit ways and
elevators, with the following exceptions:
work suites, such as the administrative suite
and dietary area, occupied primarily by
employed personnel may contain corridors or
aisles as necessary, and will not be subject to
the rules applicable to required corridors.
Areas may be open to this system as permitted by the 1985 edition of the Life Safety
Code, for those facilities with plans approved
on or before December 31, 1998. All facilities with plans submitted for approval on or
after January 1, 1999, shall comply with the
provisions of the 1997 Life Safety Code,
incorporated by reference in this rule. II/III
(35) A facility shall provide a personal care
room with barber and beauty shop facilities.
III
(36) There shall be an oxygen storage room
that is surrounded by one (1)-hour rated construction with a powered or gravity vent to
the outside. II
(37) Facilities shall have one (1) or more
nursing units. A nursing unit shall not exceed
a maximum of sixty (60) resident beds. Each
nursing unit shall be a single floor continuous
area which does not require resident care
traffic to traverse other areas. A facility shall
not locate a resident room door more than
one hundred forty feet (140') from the nurses’ station and the dirty utility room. II
(38) Resident room area shall be a minimum
of eighty (80) square feet per bed in multiple
bed resident rooms, and one hundred (100)
square feet per bed in one (1)-bed resident
rooms. A continuous aisle not less than three
feet (3') wide shall be available around the
foot and along both sides of each bed. Facilities shall locate beds to avoid drafts, excessive heat and other residents discomforts.
Typical minimum clear dimensions for the
bed area in resident rooms shall be as follows:
1-Bed 10' 6" × 9' 3"
2-Bed 10' 6" × 15' 6"
3-Bed 10' 6" × 21' 9"
4-Bed 18' 0" × 15' 6"
Heating units and handwashing sinks may
protrude into this required space. II
(39) To provide for the isolation of a resident(s) with a communicable disease(s), each
unit shall have at least two (2) private resident
rooms provided with a separate room
equipped with a toilet and handwashing sink
to serve the isolation room only. III
(40) Each resident shall have a wardrobe,
locker or closet. A clothes rod and shelf shall
be provided. III
(41) No room shall be occupied by more than
four (4) beds. III
(42) No resident shall be housed in a room in
which the outside grade line is more than
three feet (3') above the floor level on the
window side of the resident room for a distance of at least fifteen feet (15') from the
outside wall of the resident room. The resident rooms shall be outside rooms with minimum window sizes as follows:
1-Bed 10 square feet
2-Bed 16 square feet
3-Bed 24 square feet
4-Bed 32 square feet
These areas are for total window size including frames. III
(43) Each resident, without entering the general corridor area, shall have access to a toilet
room. III
(44) One (1) toilet room shall serve no more
than six (6) beds and no more than two (2)
resident rooms. II/III
(45) The toilet room shall contain a water
closet and a lavatory. II
(46) If each resident room contains a handwashing sink, the may omit the handwashing
sink from a toilet room that serves adjacent
resident rooms. When a handwashing sink is
located within the same room as the toilet,
the minimum area of a room shall be thirty
(30) square feet. If the room contains only a
toilet, the minimum area of the room shall be
eighteen (18) square feet. III
(47) Each nursing unit shall have a centrally
located nurses’ work station with a work
counter and storage space for charts. The
entire counter shall have a four foot (4') distance between the wall located behind the
counter and the edge of the counter nearest
the wall. III
(48) Facilities shall provide a medicine preparation room next to each nurses’ station that
has at least sixty (60) square feet of useable
floor space. Facilities shall provide a special
locked medication cabinet for storage of the
Class II medications inside the locked medication cabinet. If the outer cabinets are not
locked, the facility must provide a closer and
hardware that cannot be left unlocked on the
door to the medicine room. A facility is also
required to have the following in the medicine
room: a work counter, handwashing sink,
under cabinet storage, a medicine refrigerator, adequate lighting and provisions for
proper temperature control. II/III
(49) Each nursing unit shall have a clean utility room accessible directly from the nursing
unit corridor and near enough to the nurses’
station to facilitate control by the nurses. The
floor and walls shall have impervious surfaces. The facility shall provide this room
with adequate lighting and heating, a handwashing sink and at least one (1) locking cabinet. II/III
(50) Each nursing unit shall have a dirty utility room which is accessible directly from
the nursing unit corridor. The floor shall have
an impervious surface and the walls shall
have impervious surfaces to a minimum
height of five feet (5') above the floor. The
room shall be provided with adequate lighting
and heating, a double sink, clinic sink and at
least one (1) locking cabinet. III
(51) Each nursing unit shall contain one (1)
training or handicapped toilet per sex, each
with a floor area of at least five feet by six
feet (5' × 6'). This toilet may be located in
the central bath. III
(52) Each nursing unit shall have a separate
bathroom for each sex. II
(53) Tubs shall be institutional-type, free
standing with a minimum of three feet (3')
clearance from the wall on each side and four
feet (4') at the end. The shower shall be a
minimum of four feet (4') wide and of ample
length for a wheelchair resident. Thirty-inch
by sixty-inch (30" × 60") Americans with
Disability Act (ADA)-approved showers will
be accepted. The facility may replace
required
institutional-type
tub(s)
with
whirlpool tubs or other types of bathing fixtures. III
(54) The aggregate number of tubs or showers or both shall not be less than one for each
fifteen (1:15) beds on each floor. II/III
(55) The facility shall provide a locked cabinet in or near each bathroom for the storage
of cleaning supplies. III
(56) Centralized bathing facilities shall have
fixed partitions or fire-resistant curtains to
provide a private compartment for each water
closet, bathtub and shower. Curtains or doors
shall be installed on access openings. III
(57) Clean linen storage with adequate shelving is required in each nursing unit. III
(58) Each nursing unit must have a stretcher
and wheelchair parking area. III
(59) Equipment and supply storage is
required in each nursing unit. III
(60) Required corridors shall be at least eight
feet (8') wide and shall be wider at elevators
and other points of traffic concentration. No
part of the area of any required corridor or
aisle shall be counted as part of the required
area of any space adjacent to the corridor or
aisle. II/III
(61) The width of stairways shall not be less
than three feet eight inches (3' 8"). The width
shall be measured between handrails where
handrails project more than three and onehalf inches (3 1/2"). II/III
(62) Doors from sleeping and treatment areas
through which residents will pass shall be at
least forty-four inches (44") wide. Doors to
centralized toilets, bathrooms, hair care
salons and small day rooms shall be at least
thirty-six inches (36") wide. Doors to individual toilets adjacent to resident rooms shall
be at least thirty-two inches (32") wide. II
(63) Exit doors shall swing outward. Doors to
rooms shall swing into the rooms they serve.
Doors to small toilet rooms may swing outward into the next room and, if they swing
inward, they shall be equipped for emergency
access. No doors shall swing into required
corridors or aisles except doors to janitors’
closets, linen closets or doors to similar small
spaces that are open only temporarily. II
(64) Ceilings shall be at least eight feet (8').
Ceilings in corridors, storage rooms, toilet
rooms and other minor rooms shall not be
less than seven feet six inches (7' 6"). Suspended tracks, rails and pipes located in the
normal traffic path shall be at least six feet
eight inches (6' 8") above the floor. III
(65) Drinking fountains shall be located in or
near the lobby and recreation area and in each
nursing unit. The fountain shall be accessible
to residents in wheelchairs. III
(66) Facilities with plans approved on or
before December 31, 1998, shall comply
with the American National Standards Institute (ANSI) publication A117.1, 1971, Making Buildings and Facilities Accessible to, and
Useable by, the Physically Handicapped. All
new facilities whose plans were submitted to
the division on or after January 1, 1999, shall
comply with ANSI A117.1, 1992, Making
Buildings and Facilities Accessible to, and
Useable by, the Physically Handicapped,
incorporated by reference in this rule. III
(67) Handrails shall be provided on both
sides of all corridors and aisles used by residents. Corridor handrails shall have ends
return to the wall. III
(68) All stairways shall have handrails on
both sides. II
(69) Facilities shall provide grab bars or
handrails, secured in proper positions to
facilitate the bodily movements of residents,
next to all bathtubs, within all showers and on
at least one (1) side of all toilets. II
(70) Lavatories shall be positioned to be
accessible to wheelchair residents and shall
not have cabinets underneath or any other
unnecessary obstruction to the maneuverability of wheelchairs. III
(71) The facility shall provide mirrors in each
resident’s room or adjoining toilet room.
Mirrors shall be at least three feet (3') high
with the bottom edge located no more than
three feet four inches (3' 4") above the floor
or the facility may use framed tilting
mirror(s). III
(72) Facilities shall provide fire-resistant
divider curtains attached to the ceiling or
walls in all resident rooms other than private
or single bedrooms. A facility shall place
these divider curtains to provide complete
privacy for each bed. III
(73) All new facilities and additions to all
areas of existing facilities which undergo
major remodeling, shall be of sufficient
strength in all their parts to resist all stresses
imposed by dead loads, live loads and lateral
or uplift forces such as wind, without exceeding, in any of the structural materials, the
allowable working stresses established for
these materials by generally accepted good
engineering practice. II
(74) The following unit live loads shall be the
minimum distributed live loads acceptable for
the occupancies listed:
(A) Facility bedrooms and all adjoining
service rooms which compose a typical nursing unit (except solariums and corridors)—
forty pounds per square foot (40 psf); II
(B) Solariums, corridors in nursing units
and all corridors above the first floor, examination and treatment rooms, laboratories, toilet rooms and locker rooms—sixty (60) psf;
II
(C) Offices, conference room, library,
kitchen, corridors and other public areas on
first the floor—eighty (80) psf; II
(D) Stairways, laundry, large rooms used
for dining, recreation or assembly areas and
workshops—one hundred (100) psf; II
(E) Records file room, storage and supply—one hundred twenty-five (125) psf; II
(F) Mechanical equipment room—one
hundred fifty (150) psf; II
(G) Roofs (except use increased value
where snow and ice may occur)—twenty (20)
psf; and II
(H) Wind—as required by local conditions
but not less than fifteen (15) psf. II
(75) For live loads of one hundred (100)
pounds or less per square foot, the design live
load on any member supporting one hundred
fifty (150) square feet or more may be
reduced at the rate of eight hundredths of a
percent (0.08%) per square foot of area supported by the member, except that no reductions shall be made for roof live loads or for
live loads of areas to be occupied as places of
public assembly. The reduction shall exceed
neither “R”, as determined by the following
formula nor sixty percent (60%): II
D + L
R = 100 × _______________
4.33 L
where
R = reduction in percent;
D = dead load per square foot of area supported by the member; and
L = design live load per square foot of area
supported by the member.
(76) For live loads exceeding one hundred
(100) psf, no reduction shall be made, except
that the design live loads on columns may be
reduced twenty percent (20%). II
(77) Floor areas where partition positions are
subject to change shall be designed to support
a uniformly distributed load of twenty-five
(25) psf in addition to all other loads. II
(78) Foundations shall rest on natural solid
ground or properly compacted fill and shall
be carried to a depth of not less than one foot
(1') below the estimated frost line or shall
rest on leveled rock or load-bearing piles
when solid ground is not encountered. Footings, piers and foundation walls shall be adequately protected against deterioration from
the action of groundwater. A facility shall
take reasonable care to establish proper soil
bearing values for the building site soil. If the
bearing capacity of a soil is in question, a
recognized load test may be used to determine the safe bearing value. II
(79) All facilities with plans approved
between June 10, 1981 and December 31,
1998, shall comply with the 1985 edition of
the Life Safety Code, and all new facilities
with plans approved on or after January 1,
1999, shall comply with the 1997 edition of
the Life Safety Code (National Fire Protection
Association NFPA 101), which are incorporated by reference in this rule. No provision
of the 1997 code will be enforced if it is more
restrictive than the code of original plan
approval. Facilities may only use the fire
safety evaluation system found in the 1995
NFPA 101A, incorporated by reference in
this rule, if necessary to justify variance from
the text of the Life Safety Code and not as a
guide for the total design of a new facility. II
(80) Facilities with plans approved on or
before December 31, 1998, shall comply
with the fire-resistant rating of structural elements equal to those required by the 1985
Life Safety Code (NFPA 101). Facilities with
plans approved on or after January 1, 1999,
shall comply with the fire-resistant rating of
structural elements equal to those required by
the 1997 Life Safety Code (NFPA 101),
incorporated by reference in this rule. All
facilities shall meet the following additional
requirement: exterior walls less than thirty
feet (30') from an adjacent building, property
line or parallel wing shall have a two (2)-hour
fire-resistant rating. This distance may be
reduced to fifteen feet (15') if a one (1)-hour
rated wall is provided with sprinkler protection for each window. II
(81) Doors between rooms and the required
corridors shall not have louvres or transoms.
They shall be one and three-fourths inches
(1 3/4") solid-core wood doors or metal
doors with equivalent or greater fire-resistance. II
(82) Laundry and trash chutes, where used,
shall be of fire-resistant material and installed
with a flushing ring, vent to atmosphere and
floor drain in the basement. Facilities shall
provide an automatic sprinkler at the top of
each laundry and trash chute. Each floor shall
have a self-closing one and one-half (1 1/2)-
hour B-label fire door that shall not open to a
corridor. II
(83) Hardware on toilet room doors shall be
operable from both the inside and the outside.
II
(84) The floors of toilets, baths, bedpan
rooms, pantries, utility rooms and janitors’
closets shall have smooth, waterproof surfaces which are wear-resistant. The floors of
residents’ rooms shall be smooth and easily
cleaned. The floors of kitchens and food
preparation areas shall be waterproof, greaseproof, smooth and resistant to heavy wear.
II/III
(85) The walls of all rooms where food and
drink are prepared, served or stored shall
have a smooth surface with painted or equally
washable finish. At the base, they shall be
waterproof and free from spaces which may
harbor ants and roaches. The walls of
kitchens, sculleries, utility rooms, baths,
showers, dishwashing rooms, janitors’ closets
and spaces with sinks shall have waterproof
painted, glazed or similar finishes to a point
above the splash and spray line. III
(86) The ceilings of all sculleries, kitchens
and other rooms where food and drink are
prepared shall be painted with washable
paint. III
(87) All floor construction shall be completely of noncombustible material regardless of
the construction type of the building. II
(88) All new floor covering installed and used
in new and existing licensed facilities on or
after January 1, 1999, shall be Class I in nonsprinklered buildings and Class II in sprinklered buildings. Class I has a critical radiant
flux of zero point forty-five (0.45) or more
watts per square centimeter when tested
according to the 1995 NFPA 253, incorporated by reference in this rule. Class II has a
critical radiant flux of zero point twenty-two
(0.22) or more watts per square centimeter
when tested according to the 1995 NFPA
253. Those facilities who installed new floor
covering on or before December 31, 1998,
shall comply with the requirements of the
1978 edition of the NFPA 253. III
(89) A facility shall furnish and install the
heating system, steam system, boilers and
ventilation to meet all requirements of local
and state codes and NFPA regulations. II/III
(90) The building shall be heated by a two
(2)-pipe steam system, a forced hot water system, a forced hot air system, a system of electrical heating elements or a combination of
two (2) or more of these systems. No open
flame space heaters or space heaters receiving combustion air from the heated space
shall be used. Facilities shall not depend
upon fireplaces for required heating. III
(91) The heating system shall be capable of
heating resident-occupied areas to a temperature of eighty degrees Fahrenheit (80°F)
(27°C) at the winter design temperature. In
spaces where radiant panel heating is used,
facilities may reduce the temperature as
required to maintain an equivalent comfort
level. III
(92) The heating system shall have automatic
controls adequate to provide comfortable
conditions in all portions of the building at all
times. III
(93) Neither the heating nor the ventilating
system shall require the circulation of air
through openings in the required corridor
partitions except for the delivery of ventilating air from corridors through each room
door at a velocity of not more than two hundred fifty feet (250') per minute when the
door is closed and the space under it is not
over one inch (1") in height. No louvres shall
be installed in doors in required corridor partitions. II/III
(94) A facility with plans approved on or
after January 1, 1999, shall install an air-conditioning system, or individual room air-conditioning units, that meet all the 1996 NFPA
90A requirements, incorporated by reference
in this rule. The systems or units must be
capable of maintaining resident-use areas at
eighty-five
degrees
Fahrenheit
(85°F)
(29.4°C) at the summer design temperature.
Those facilities with plans approved on or
before December 31, 1998, shall comply
with the NFPA 90A requirements as referenced in the 1985 Life Safety Code. II/III
(95) Ventilation requirements given in Table
I—Ventilation Requirements shall be met.
II/III
TABLE I VENTILATION REQUIREMENTS
Minimum Air
Pressure Changes of Outdoor Minimum Total Air All Air Exhausted
Relationship to Air Per Hour Changes Per Hour Directly to Air Returned From
Area Designation Adjacent Areas Supplied to Room Supplied to Room Outdoors This Room
Patient Area Corridor P Optional 2 Optional Optional
Physical Therapy N 2 4 Optional Optional
Occupational Therapy N 2 4 Optional Optional
Soiled Work Room
or Soiled Holding N 2 10 Yes No
*Toilet Room N Optional 6 Yes No
Bathroom N Optional 6 Yes No
Janitors’ Closet(s) N Optional 6 Yes No
Linen and Trash
Chute Room N Optional 6 Yes No
Food Preparation
Center E 2 6 Yes Optional
Warewashing Room N Optional 6 Yes No
Dietary Day Storage V Optional 2 Yes No
Laundry, General V 2 6 Yes No
Soiled Linen Sorting
and Storage N Optional 10 Yes No
P = Positive
N = Negative
E = Equal
V = Variable
*Up to 75 cubic feet per minute (cfm) of make-up air for each patient room toilet may be supplied to the corridor and need not be supplied
directly to the room.
NOTE: In the interest of energy conservation, energy saving design innovations that are not in strict conformance with these requirements,
which do not adversely affect direct patient care, will be acceptable if approved in writing by the Division of Aging.
(96) The entire plumbing system and its
maintenance and operation shall comply with
the requirements of all applicable local and
state codes including the requirements set
forth in this rule and with the requirements of
the 1987 National Plumbing Code, which is
incorporated by reference in this rule. II/III
(97) Plumbing fixtures that require hot water
and are resident-accessible shall be supplied
with water thermostatically controlled to provide a water temperature of between one hundred twenty degrees Fahrenheit (120°F)
(49°C) and one hundred five degrees Fahrenheit (105°F) (41°C) at the fixture or faucet.
I/II
(98) The hot water heating equipment shall
have sufficient capacity to supply five (5) gallons (19 l) of water at one hundred twenty
degrees Fahrenheit (120°F) (49°C) per hour
per bed for nursing home fixtures or faucets,
and eight (8) gallons (30 l) of water at one
hundred sixty degrees Fahrenheit (160°F)
(71.1°C) per hour per bed for kitchen and
laundry. The division may accept lesser
capacities following submission of the calculation for the anticipated demand of all fixtures and equipment in the building. II
(99) Pipes shall be sized to supply water to all
fixtures with a minimum pressure of fifteen
pounds per square inch (15 psi) (1.02 atmospheres) at the top floor fixture during maximum demand periods. All plumbing fixtures
except water closets, urinals and drinking
fountains shall have both hot and cold water
supplies. III
(100) Facilities shall protect every supply
outlet or connection to a fixture or appliance
against back flow as provided by the 1987
National Plumbing Code, incorporated by
reference in this rule. All faucets to which
hoses can be attached, all spray fittings and
all other fittings that could deliver water to
points below overflow lines, shall be
equipped with vacuum breakers. II/III
(101) Wherever the usage of fixtures or appliances will permit, water supplied to all fixtures, open tanks and equipment shall be
introduced through a suitable air gap between
the water supply and the flood level of the
fixture. II
(102) Hot water circulating mains and risers
shall be run from the hot storage tank to a
point directly below the highest fixture at the
end of each branch main. III
(103) Where the building is higher than three
(3) stories, each riser shall be circulated. III
(104) Water pipe sizes shall be equal to or
greater than those prescribed by the 1987
National Plumbing Code, incorporated by
reference in this rule. III
(105) All fixtures and equipment shall be
connected through traps to soil and waste piping and to the sewer and they shall all be
properly trapped and vented to the outside. II
(106) Courts, yards and drives which do not
have natural drainage from the building shall
have catch basins and drains to low ground,
storm-water system or dry wells. III
(107) Facilities where gas-fired equipment is
to be installed for use on or after January 1,
1999, shall provide and install all gas piping,
fittings, tanks and specialties in compliance
with the 1996 NFPA 54, Installation of Gas
Appliances and Gas Piping, the 1995 NFPA
58, Storage and Handling of Liquefied
Petroleum Gases, incorporated by reference
in this rule, and the instructions of the gas
supplier, except where more strict requirements are stated. Facilities which installed
gas-fired equipment on or before December
31, 1998, shall ensure that the installation
was in compliance with the instructions and
requirements outlined in the NFPA 54 and
NFPA 58 as referenced in the 1985 Life Safety Code. Where liquefied petroleum gas
(LPG) is used, the Missouri Department of
Agriculture also requires compliance with its
rules. II
(108) Where gas piping enters the building
below grade, it shall have an outside vent as
follows: A concrete box, eighteen inches by
eighteen inches (18" × 18") with three-inch
(3") thick walls, of a height to rest on top of
the entering gas pipe, and top of the box to
come within six inches (6") of top grade. The
box shall be filled with coarse gravel. A oneinch (1") upright vent line shall be to one-half
(1/2) the depth of the box and extend twelve
inches (12") above top grade with a screened
U-vent looking down. The vent line is to be
anchored securely to the building wall. II
(109) Facilities shall not install gas-fired
equipment in any resident bedroom except
that through-wall gas heating units may be
used if vented directly to the outside, take
combustion air directly from the outside and
provide a complete separation of the combustion system from the atmosphere of the occupied area. II
(110) In facilities where oxygen systems are
installed on or after January 1, 1999, the
facilities shall install the oxygen piping, outlets, manifolds, manifold rooms and storage
rooms in accordance with the requirements of
the 1993 NFPA 99, incorporated by reference
in this rule. In facilities where oxygen systems were installed on or before December
31, 1998, facilities shall ensure that the
installation was in compliance with NFPA 99
as required and referenced in the 1985 Life
Safety Code. I/II
(111) The building sanitary drain system may
be cast iron, steel, copper or plastic if
installed in compliance with the National
Plumbing Code, current edition. III
(112) Each main, branch main, riser and
branch to a group of fixtures of the water system shall be valved. III
(113) To prevent condensation, facilities shall
cover cold water mains in occupied spaces
with approved vapor-proof insulation. III
(114) To prevent freezing, facilities shall
insulate all pipes in outside walls. III
(115) Facilities shall test soil, waste, vent and
drain lines according to the requirements of
the 1987 National Plumbing Code, incorporated by reference in this rule. The facility
shall make certification of these tests available to the division. III
(116) After installation and before the nursing home is operating, the facility shall disinfect the entire water distribution system, both
hot and cold, and all connecting equipment
by one (1) of the methods described in the
1987 National Plumbing Code, incorporated
by reference in this rule. III
(117) Water softeners, if used, shall be connected to the hot water supply only or connected so that water used for cooking and
drinking is not softened. III
(118) Facilities with plans approved on or
after January 1, 1999, shall ensure that the
entire electrical system and its maintenance
and operation comply with the 1996 National
Electrical Code, which is incorporated by
reference in this rule. Facilities whose plans
were approved on or before December 31,
1998, shall comply with the National Electrical Code as referenced in the 1985 Life Safety
Code. II/III
(119) Facilities shall adequately light all
occupied areas as required by the duties performed in that space. II/III
(120) Residents’ bedrooms shall have a minimum general illumination of ten (10) footcandles, a night-light and a resident’s reading
light. The outlets for general illumination and
night-lights shall be switched at the door. III
(121) Each single-bed resident room shall
have at least two (2) duplex receptacles. All
multi-bed resident rooms shall have at least
one (1) duplex receptacle at the head of each
bed plus one (1) additional duplex receptacle.
Facilities shall not place duplex receptacles in
a manner to cause an electrical shock hazard.
III
(122) Facilities shall furnish lighting fixtures
of a type suitable for the space for all lighting
outlets. III
(123) If ceiling lights are used in residents’
rooms, they shall be of a type which are shaded or globed to minimize glare. III
(124) Facilities shall provide an electricallypowered nurses’ call system with indicator
lights at the corridor entrance of each bedroom. Audible signals and indicating panels
shall be located in each nurses’ station and
utility room. Facilities shall provide signal
buttons at the head of each resident bed, in
each toilet room and in each bathroom. III
(125) Facilities shall provide night-lights in
hallways, individual toilet rooms, stairways
and resident rooms or adjacent toilet rooms.
II
(126) A qualified electrician shall test and
certify the entire electrical system as being in
compliance with the 1996 National Electrical
Code, incorporated by reference in this rule.
In facilities whose plans were approved on or
before December 31, 1998, the electrician
shall test the system according to the standards of the National Electrical Code as referenced in the 1985 Life Safety Code. Facilities shall make this test certification available
to the division. III
(127) Facilities shall provide a complete,
electrically-operated door alarm system that
is audible in the nurses’ station for all resident-accessible exterior doors. III
(128) A facility shall have emergency lighting for exits, stairs, corridors and nurses’ stations. Facilities may provide this emergency
lighting using an emergency generator or battery-operated lights rated at least one and
one-half (1 1/2) hours. In facilities with
plans approved on or after January 1, 1999,
an emergency generator shall supply emergency power to life support systems as
required by the 1993 NFPA 99, Health Care
Facilities, incorporated by reference in this
rule. In facilities where plans were approved
on or before December 31, 1998, the electrical system shall comply to the standards of
the National Electrical Code as referenced in
the 1985 Life Safety Code. III
(129) The elevator installations shall comply
with all local and state codes, American
Standards Association Specification A17.1,
1993 Safety Code for Elevators and Escalators, the 1996 National Electrical Code,
incorporated by reference in this rule, and the
minimum general standards as set forth in
this rule. In facilities whose plans were
approved on or before December 31, 1998,
the elevators shall comply with applicable
local and state codes and the requirements set
forth in the ASAS A17.1, Safety Code for
Elevators and Escalators, and the National
Electrical Code as referenced in the 1985 Life
Safety Code. II
(130) Any facility with residents on one (1)
or more floors above the first floor shall have
at least one (1) hydraulic or electric motor
driven elevator. Facilities with a bed capacity
from sixty-one to two hundred (61–200)
above the first floor shall not have less than
two (2) elevators. II
(131) Facilities with a bed capacity of from
two hundred to three hundred fifty (200—
350) above the first floor shall have not less
than three (3) elevators—two (2) passenger
and one (1) service. II
(132) Inside cab dimensions of elevators shall
be not less than five feet four inches by eight
feet (5' 4" × 8') with a capacity of three
thousand five hundred pounds (3,500 lbs.).
Cab and shaft doors shall have no less than
three feet ten inches (3' 10") clear opening.
Elevators for which operators will not be
employed shall have automatic push-button
controls, signal controls or dual controls for
use with or without the operator. Where two
(2) push-button elevators are located together
and where one (1) elevator serves more than
three (3) floors and basement, they shall have
collective or signal control. III
(133) Facilities with plans approved on or
after January 1, 1999, shall have overspeed
tests conducted on all elevator machines.
Elevators will be tested for speed and load,
with and without loads, in both directions as
covered by the 1993 Safety Code for Elevators and Escalators, incorporated by reference in this rule. Facilities whose plans were
approved on or before December 31, 1998,
shall conduct overspeed tests in accordance
with applicable local and state codes and the
requirements set forth in the ASAS A17.1,
Safety Code for Elevators and Escalators, as
referenced in the 1985 Life Safety Code.
Facilities shall make this test certification
available to the division. III
AUTHORITY: section 198.009, RSMo Supp.
1998.* This rule originally filed as 13 CSR
15-14.012. Original rule filed July 13, 1983,
effective Oct. 13, 1983. Amended: Filed Aug.
1, 1988, effective Nov. 11, 1988. Amended:
Filed May 11, 1998, effective Dec. 30, 1998.
Emergency amendment filed May 12, 1999,
effective May 22, 1999, expired Feb. 24,
2000. Amended: Filed July 13, 1999, effective Jan. 30, 2000. Moved to 19 CSR 3085.012, effective Aug. 28, 2001.
*Original authority: 198.009, RSMo 1979, amended
1993, 1995.