19 CSR 30-85.022
Fire Safety and Emergency Preparedness Standards for New and Existing Intermediate Care and Skilled Nursing Facilities
PURPOSE: This rule establishes fire-safety
and emergency preparedness requirements for
new and existing intermediate care and
skilled nursing facilities.
PUBLISHER’S NOTE: The secretary of state
has determined that the publication of the
entire text of the material which is incorporated by reference as a portion of this rule
would be unduly cumbersome or expensive.
This material as incorporated by reference in
this rule shall be maintained by the agency at
its headquarters and shall be made available
to the public for inspection and copying at no
more than the actual cost of reproduction.
This note applies only to the reference material. The entire text of the rule is printed
here.
AGENCY NOTE: All rules relating to longterm care facilities licensed by the Department of Health and Senior Services are followed by a Roman Numeral notation which
refers to the class (either class I, II, or III) of
standard as designated in section 198.085,
RSMo 2000.
(1) Definitions. For the purpose of this rule,
the following definitions shall apply:
(A) Accessible spaces—shall include all
rooms, halls, storage areas, basements, attics,
lofts, closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes;
(B) Area of refuge—a space located in or
immediately adjacent to a path of travel leading to an exit that is protected from the
effects of fire, either by means of separation
from other spaces in the same building or its
location, permitting a delay in evacuation. An
area of refuge may be temporarily used as a
staging area that provides some relative safety
to its occupants while potential emergencies
are assessed, decisions are made, and if
applicable, evacuation has begun;
(C) Major renovation—shall include the
following:
1. Addition of any room(s), accessible
by residents, that either exceeds fifty percent
(50%) of the total square footage of the facility or exceeds four thousand five hundred
(4,500) square feet;
2. Repairs, remodeling, or renovations
that involve more than fifty percent (50%) of
the building;
3. Repairs, remodeling, or renovations
that involve more than four thousand five
hundred (4,500) square feet of a smoke section; or
4. If the addition is separated by two-
(2-) hour fire-resistant construction, only the
addition portion shall meet the requirements
for an NFPA 13, 1999 edition, sprinkler system, unless the facility is otherwise required
to meet NFPA 13, 1999 edition; and
(D) Concealed spaces—shall include areas
within the building that cannot be occupied or
used for storage.
(2) General Requirements.
(A) All National Fire Protection Association (NFPA) codes and standards cited in this
rule: NFPA 10, Standard for Portable Fire
Extinguishers, 1998 edition; NFPA 13, Standard for the Installation of Sprinkler Systems,
1999 edition; NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 1998 edition;
NFPA 99, Standard for Health Care Facilities, 1999 edition; NFPA 101, The Life Safety
Code, 2000 edition; NFPA 72, National Fire
Alarm Code, 1999 edition; NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 1998 edition; NFPA 253, Standard
Method of Test of Surface Burning Characteristics of Building Materials, 2000 edition;
NFPA 701, Standard Methods of Fire Tests
for Flame Propagation of Textiles and Films,
1999 edition; NFPA 211, Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances, 2000 edition; and NFPA 101A, Guide
to Alternative Approaches to Life Safety,
2001 edition, are incorporated by reference in
this rule and available for purchase from the
National Fire Protection Agency, 1 Batterymarch Park, Quincy, MA 02269-9101;
www.nfpa.org; by telephone at (617) 7703000 or 1-800-344-3555. This rule does not
incorporate any subsequent amendments or
additions to the materials listed above.
(B) This rule does not prohibit facilities
from complying with standards set forth in
newer editions of the incorporated by reference material listed in subsection (2)(A) of
this rule if approved by the department.
(C) The department shall have the right of
inspection of any portion of a building in
which a licensed facility is located unless the
unlicensed portion is separated by two- (2-)
hour fire-resistant construction. I/II
(D) Facilities shall not use space under
stairways to store combustible materials. I/II
(E) No section of the building shall present
a fire hazard. I/II
(F) All facilities shall notify the department immediately after the emergency is
addressed if there is a fire in the facility or
premises and shall submit a complete written
fire report to the department within seven (7)
days of the fire, regardless of the size of the
fire or the loss involved. II/III
(G) Following the discovery of any fire, the
facility shall monitor the area and/or the
source of the fire for a twenty-four- (24-)
hour period. This monitoring shall include, at
a minimum, hourly visual checks of the area.
These hourly visual checks shall be documented. I/II
(H) All electrical appliances shall be
Underwriters’ Laboratories (UL) or Factory
Mutual (FM)-approved, shall be maintained
in good repair, and no appliances or electrical
equipment shall be used which emit fumes or
which could in any other way present a hazard to the residents. I/II
(3) All openings that could permit the passage
of fire, smoke, or both, between floors shall
be fire-stopped with a suitable noncombustible material. II/III
(4) Hazardous areas shall be separated by
construction of at least one- (1-) hour fireresistant construction. Hazardous areas may
be protected by an automatic sprinkler system
in lieu of a one- (1-) hour rated fire-resistant
construction. When the sprinkler option is
chosen, the areas shall be separated from
other spaces by smoke-resistant partitions and
doors. The doors shall be self-closing or
automatic closing. II
(5) The storage of any unnecessary combustible materials in any part of a building in
which a licensed facility is located is prohibited. No section of the building shall present
a fire hazard. I/II
(6) Oxygen storage shall be in accordance
with NFPA 99, 1999 edition. Facilities shall
use permanent racks or fasteners to prevent
accidental damage or dislocation of oxygen
cylinders. Safety caps shall remain intact
except where a cylinder is in actual use or
where the regulator has been attached and the
cylinder is ready for use. Individual oxygen
cylinders in use or with an attached regulator
shall be supported by cylinder collars or by
stable cylinder carts. II/III
(7) Each nursing unit may maintain only one
(1) emergency-use oxygen tank in a readily
accessible unit area. II
(8) Fire Extinguishers.
(A) Fire extinguishers shall be provided at
a minimum of one (1) per floor, so that there
is no more than seventy-five feet (75') travel
distance from any point on that floor to an
extinguisher. I/II
(B) All new or replacement portable fire
extinguishers shall be ABC-rated extinguishers, in accordance with the provisions of
NFPA 10, 1998 edition. A K-rated extinguisher or its equivalent shall be used in lieu
of an ABC-rated extinguisher in the kitchen
cooking areas. II
(C) Fire extinguishers shall have a rating of
at least—
1. Ten pounds (10 lbs.), ABC-rated or
the equivalent, in or within fifteen feet (15')
of hazardous areas as defined in 19 CSR 3083.010; II and
2. Five pounds (5 lbs.), ABC-rated or
the equivalent, in other areas. II
(D) All fire extinguishers shall bear the
label of the UL or the FM Laboratories and
shall be installed and maintained in accordance with NFPA 10, 1998 edition. This
includes the documentation and dating of a
monthly pressure check. II/III
(9) Facilities shall provide every cooking
range with a range hood and approved range
hood extinguishing system installed, tested,
and maintained in accordance with NFPA 96,
1998 edition. The range hood and its extinguishing system shall be certified at least
twice annually in accordance with NFPA 96,
1998 edition. II/III
(10) Complete Fire Alarm Systems.
(A) Facilities shall have a complete fire
alarm system installed in accordance with
NFPA 101, Section 18.3.4, 2000 edition.
The complete fire alarm system shall automatically transmit to the fire department, dispatching agency, or central monitoring company. The complete fire alarm system shall
include visual signals and audible alarms that
can be heard throughout the building and a
main panel that interconnects all alarm-activating devices and audible signals in accordance with NFPA 72, 1999 edition. Manual
pull stations shall be installed at or near each
required nurse/attendant’s station and each
required exit. Smoke detectors shall be interconnected to the complete fire alarm system.
Specific minimum requirements relating to
the interconnected smoke detectors are found
in subsections (10)(I) and (10)(J) of this rule.
I/II
(B) All facilities shall test and maintain the
complete fire alarm system in accordance
with NFPA 72, 1999 edition. I/II
(C) All facilities shall have inspections and
written certifications of the complete fire
alarm system completed by an approved qualified service representative in accordance
with NFPA 72, 1999 edition, at least annually. I/II
(D) The complete fire alarm system shall
be activated by all of the following: sprinkler
system flow alarm, smoke detectors, heat
detectors, manual pull stations, and activation
of the range hood extinguishment system.
II/III
(E) Facilities shall test by activating the
complete fire alarm system at least once a
month. II/III
(F) Facilities shall maintain a record of the
complete fire alarm system tests, inspections
and certifications required by subsections
(10)(B), (10)(C), and (10)(E) of this rule. III
(G) Upon discovery of a fault with the
complete fire alarm system, the facility shall
correct the fault. I/II
(H) When a complete fire alarm system is
to be out-of-service for more than four (4)
hours in a twenty-four- (24-) hour period, the
facility shall immediately notify the department and the local fire authority and implement an approved fire watch in accordance
with NFPA 101, 2000 edition, until the fire
alarm system has returned to full service. I/II
(I) All facilities shall have smoke detectors
interconnected to the complete fire alarm system in all corridors and spaces open to corridors. Smoke detectors shall be no more than
thirty feet (30') apart with no point on the
ceiling more than twenty-one feet (21') from
a smoke detector. I/II
(J) Facilities that have a sprinkler system
exemption shall have smoke detectors interconnected to the complete fire alarm system
in all accessible spaces within the facility as
required by NFPA 72, 1999 edition. Smoke
detectors shall be no more than thirty feet
(30') apart with no point on the ceiling more
than twenty-one feet (21') from a smoke
detector. Smoke detectors shall not be
installed in areas where environmental influences may cause nuisance alarms. Such areas
include, but are not limited to, kitchens, laundries, bathrooms, mechanical air handling
rooms, and attic spaces. In these areas, heat
detectors interconnected to the complete fire
alarm system shall be installed. Bathrooms
not exceeding fifty-five (55) square feet and
clothes closets, linen closets, and pantries not
exceeding twenty-four (24) square feet are
exempt from having any detection device if
the walls and ceilings are surfaced with limited-combustible or noncombustible material
as defined in NFPA 101, 2000 edition. Concealed spaces of noncombustible or limitedcombustible construction are not required to
have detection devices. These spaces may
have limited access but cannot be occupied or
used for storage. I/II
(K) For each facility not having a sprinkler
system exemption, each resident room or any
room designated for sleeping shall be
equipped with at least one (1) battery-powered
smoke alarm installed, tested, and maintained
in accordance with manufacturer’s specifications. In addition, the facility shall be
equipped with interconnected heat detectors
installed, tested, and maintained in accordance with NFPA 72, 1999 edition, with
detectors in all areas subject to nuisance
alarms, including, but not limited to, kitchens,
laundries, bathrooms, mechanical air handling
rooms, and attic spaces. I/II
1. The facility shall maintain a written
record of the monthly testing and battery
changes. The written records shall be
retained for one (1) year. I/II
2. Upon discovery of a fault with any
detector or alarm, the facility shall correct
the fault. I/II
(11) Sprinkler System.
(A) All facilities shall have inspections and
written certifications of the sprinkler system
completed by an approved qualified service
representative in accordance with NFPA 25,
1998 edition. The inspections shall be in
accordance with the provisions of NFPA 25,
1998 edition, with certification at least annually by a qualified service representative. I/II
(B) All facilities licensed prior to August
28, 2007, that were not required to have a
complete sprinkler system in accordance with
NFPA 13 shall have until December 31,
2012, to comply with NFPA 13, 1999 edition. I/II
1. Exemptions shall be granted if the
facility presents evidence in writing from a
certified sprinkler system representative or
licensed engineer that the facility is unable to
install an approved NFPA 13, 1999 edition,
system due to the unavailability of the water
supply. I/II
(C) Facilities that have a sprinkler system
installed prior to August 28, 2007, shall
inspect, maintain, and test these systems in
accordance with the requirements in effect
for such facilities on August 27, 2007. I/II
(D) Facilities licensed on or after August
28, 2007, or any section of a facility in which
a major renovation has been completed on or
after August 28, 2007, shall install and maintain a complete sprinkler system in accordance with NFPA 13, 1999 edition. I/II
(E) When a sprinkler system is to be outof-service for more than four (4) hours in a
twenty-four- (24-) hour period, the facility
shall immediately notify the department and
the local fire authority and implement an
approved fire watch in accordance with
NFPA 101, 2000 edition, until the sprinkler
system has returned to full service. I/II
(12) Each floor of an existing licensed facility
shall have at least two (2) unobstructed exits
remote from each other. One (1) of the
required exits in an existing multi-story facility must be an outside stairway or an enclosed
stair that is separated by one- (1-) hour construction from each floor and has an exit
leading directly outside at grade level. One
(1) exit may lead to a lobby with exit facilities
to the ground level outside instead of leading
directly to the outside. The lobby shall have
at least a one- (1-) hour fire-rated separation
from the remainder of the exiting floor. I/II
(13) If facilities have outside stairways, they
shall be substantially constructed to support
residents during evacuation. These stairways
shall be protected or cleared of ice and snow.
Stairways shall be of sturdy construction
using at least two-inch (2") lumber and shall
be continuous to ground level. All treads and
risers shall be of the same height and width
throughout the entire stairway, not including
landings. II/III
(14) Fire escapes added to existing buildings,
whether interior or exterior, shall have at
least a minimum thirty-six-inch (36") width,
eight-inch (8") maximum risers, a nine-inch
(9") minimum tread, no winders, a maximum
height between landings of twelve feet (12'),
minimum landing dimensions of forty-four
inches (44"), landings at each exit door, and
handrails on both sides. Exit(s) to fire
escapes shall be at least thirty-six inches
(36") wide, and the fire-escape door shall
swing outward. All treads and risers shall be
of the same height and width throughout the
entire stairway, not including landings. II/III
(15) Facilities with three (3) or more floors
shall comply with the provisions of Chapter
320, RSMo, which requires that outside
stairways be constructed of iron or steel. II
(16) Door locks shall be of a type that can be
opened from the inside by turning the knob or
operating a simple device that will release the
lock, or shall meet the requirements of Section 19.2 of NFPA 101, 2000 edition. Only
one (1) lock will be permitted on any one (1)
door. I/II
(17) All exit doors in existing licensed facilities shall be at least thirty inches (30") wide.
II
(18) All exit doors in new facilities shall be at
least forty-four inches (44") wide. II
(19) In all facilities, all exit doors and
vestibule doors shall swing outward in the
direction of exit travel. II
(20) In all existing licensed facilities, all horizontal exit doors in fire walls and all doors
in smoke barrier partitions may swing in
either direction. These doors normally may
be open, but shall be automatically self-closing upon activation of the fire alarm system.
They shall be capable of being manually
released to self-closing action. II/III
(21) Facilities shall maintain corridors to be
free of obstruction, equipment, or supplies
not in use. Doors to resident rooms shall not
swing into the corridor. II/III
(22) Facilities shall place signs bearing the
word EXIT in plain, legible block letters at
each required exit, except at doors directly
from rooms to exit corridors or passageways.
II
(23) Wherever necessary, the facility shall
place additional signs in corridors and passageways to indicate the exit’s direction. Letters on these signs shall be at least six inches
(6") high and principle strokes three-fourths
inch (3/4") wide, except that the letters of
internally illuminated exit signs may be not
less than four inches (4") high. III
(24) Facilities shall maintain all exit and
directional signs to be clearly legible and
electrically illuminated at all times by acceptable means such as emergency lighting when
lighting fails. II
(25) Facilities shall have emergency lighting
of sufficient intensity to provide for the safety
of residents and other people using any exit,
stairway, and corridor. The lighting shall be
supplied by an emergency service, an automatic emergency generator or battery lighting
system. This emergency lighting system shall
be equipped with an automatic transfer
switch. In an existing licensed facility, battery
lights, if used, shall be wet cell units or other
rechargeable-type batteries that shall be ULapproved and capable of operating the light
for at least one and one-half (1 1⁄2) hours.
Battery-operated emergency lighting shall be
tested for at least thirty (30) seconds every
thirty (30) days, and an annual function test
shall be conducted for the full operational
duration of one and one-half (1 1⁄2) hours.
Records of these tests shall be documented
and maintained for review. II
(26) If existing licensed facilities have laundry chutes, dumbwaiter shafts, or other similar vertical shafts, they shall have a fire resistance rating of at least one (1) hour if serving
three (3) or fewer stories. Enclosures serving
four (4) or more stories shall have at least a
two- (2-) hour fire-rated enclosure. These
chute or shaft doors shall be self-closing or
shall have any other approved device that will
guarantee separation between floors. II
(27) Existing licensed multistoried facilities
shall provide a smoke separation barrier
between the basement and the first floor and
the floors of resident-use areas. At a minimum, this barrier shall consist of one-half
inch (1/2") gypsum board, plaster, or equivalent. There shall be a one and three-fourths
inch (1 3/4") thick solid-core wood door, or
equivalent, at the top or bottom of the stairs.
If the door is glazed, it shall be glazed with
wired glass. II
(28) Each floor accessed by residents shall be
divided into at least two (2) smoke sections
with each section not exceeding one hundred
fifty feet (150') in length or width. If the
floor’s dimensions do not exceed seventy-five
feet (75') in length or width, a division of the
the floor into two (2) smoke sections will not
be required. II
(29) Each smoke section shall be separated by
one- (1-) hour fire-rated walls that are continuous from outside wall-to-outside wall and
from floor-to-floor or floor-to-roof deck. All
doors in this wall shall be at least twenty-
(20-) minute fire rated or its equivalent, selfclosing, and may be held open only if the
door closes automatically upon activation of
the fire alarm system. II
(30) Existing licensed facilities shall have
attached self-closing devices on all doors providing separation between floors. If the doors
are to be held open, they shall have electromagnetic hold-open devices that are interconnected with either a smoke alarm or with
other smoke-sensitive fire extinguishment or
alarm systems in the building. II/III
(31) Smoking shall be permitted only in designated areas. Areas where smoking is permitted shall be directly supervised unless the
resident has been assessed by the facility and
determined capable of smoking unassisted.
At least annually, the facility shall reassess
those residents the facility has determined to
be capable of smoking unsupervised and shall
also reassess such resident when changes in
his or her condition indicate the resident may
no longer be capable of smoking without
supervision. The facility shall document this
assessment in the resident’s medical record.
II
(32) Designated smoking areas shall have
ashtrays of noncombustible material and of
safe design. The contents of ashtrays shall be
disposed of properly in receptacles made of
noncombustible material. II/III
(33) Fire Drills and Emergency Preparedness.
(A) All facilities shall have a written plan
to meet potential emergencies or disasters
and shall request consultation and assistance
annually from a local fire unit for review of
fire and evacuation plans. If the consultation
cannot be obtained, the facility shall inform
the state fire marshal in writing and request
assistance in review of the plan. An up-todate copy of the facility’s entire plan shall be
provided to the local jurisdiction’s emergency
management director. II/III
(B) The plan shall include, but is not limited to—
1. A phased response ranging from relocation of residents to an immediate area within the facility; relocation to an area of refuge,
if applicable; or to total building evacuation.
This phased response part of the plan shall be
consistent with the direction of the local fire
unit or state fire marshal and shall be appropriate for the fire or emergency;
2. Written instructions for evacuation of
each floor including evacuation to areas of
refuge, if applicable, and floor plan showing
the location of exits, fire alarm pull stations,
fire extinguishers, and any areas of refuge;
3. Evacuating residents, if necessary,
from an area of refuge to a point of safety
outside the building;
4. The location of any additional water
sources on the property such as cisterns,
wells, lagoons, ponds, or creeks;
5. Procedures for the safety and comfort
of residents evacuated;
6. Staffing assignments;
7. Instructions for staff to call the fire
department or other outside emergency services;
8. Instructions for staff to call alternative resource(s) for housing residents, if necessary;
9. Administrative staff responsibilities;
and
10. Designation of a staff member to be
responsible for accounting for all residents’
whereabouts. II/III
(C) The written plan shall be accessible at
all times and an evacuation diagram shall be
posted on each floor in a conspicuous place
so that employees and residents can become
familiar with the plan and routes to safety.
II/III
(D) A minimum of twelve (12) fire drills
shall be conducted annually with at least one
(1) every three (3) months on each shift. At
least four (4) of the required fire drills must
be unannounced to residents and staff,
excluding staff who are assigned to evaluate
staff and resident response to the fire drill.
The fire drills shall include a simulated resident evacuation that involves the local fire
department or emergency service at least
once a year. II/III
(E) The fire alarm shall be activated during
all fire drills unless the drill is conducted
between 9 p.m. and 6 a.m., when a facilitygenerated predetermined message is acceptable in lieu of the audible and visual components of the fire alarm. II/III
(F) The facility shall keep a record of all
fire drills including the simulated resident
evacuation. The record shall include the time,
date, personnel participating, length of time
to complete the fire drill, and a narrative
notation of any special problems. III
(34) Fire Safety Training Requirements.
(A) The facility shall ensure that fire safety
training is provided to all employees:
1. During employee orientation;
2. At least every six (6) months; and
3. When training needs are identified as
a result of fire drill evaluations. II/III
(B) The training shall include, but is not
limited to, the following:
1. Prevention of fire ignition, detection
of fire, and control of fire development;
2. Confinement of the effects of fire;
3. Procedures for moving residents to an
area of refuge, if applicable;
4. Use of alarms;
5. Transmission of alarms to the fire
department;
6. Response to alarms;
7. Isolation of fire;
8. Evacuation of the immediate area and
building;
9. Preparation of floors and facility for
evacuation; and
10. Use of the evacuation plan required
by section (33) of this rule. II/III
(35) The use of wood- or gas-burning fireplaces will be permitted only if the fireplaces
are built of firebrick or metal, enclosed by
masonry, and have metal or tempered glass
screens. The chimneys shall be of masonry
construction with flue linings that have at
least eight inches (8") of masonry separating
the flue lining and the fireplace from any
combustible material. All fireplaces shall be
installed, operated, and maintained in a safe
manner. Fireplaces not in compliance with
these requirements may be provided if they
are for decorative purposes only or if they are
equipped with decorative-type electric logs or
other electric heaters which bear the UL label
and are constructed of electrical components
complying with and installed in compliance
with the National Electrical Code, incorporated by reference in this rule. Fireplaces
meeting standards set forth in NFPA 211,
2000 edition, are considered in compliance
with this rule. II/III
(36) All electric or gas clothes dryers shall be
vented to the outside and the lint trap cleaned
regularly. II/III
(37) In existing licensed facilities, all wall
and ceiling surfaces shall be smooth and free
of highly-combustible materials. II/III
(38) All curtains in resident-use areas shall be
rendered and maintained flame-resistant in
accordance with NFPA 701, 1999 edition.
II/III
(39) All new floor covering installed in buildings that do not have a sprinkler system shall
be Class I in accordance with NFPA 253,
2000 edition. II/III
(40) Trash and Rubbish Disposal Requirements.
(A) Only metal or UL- or FM-approved
wastebaskets shall be used for the collection
of trash. II
(B) The facility shall maintain the exterior
premises in a manner as to provide for fire
safety. II
(C) Trash shall be removed from the
premises as often as necessary to prevent fire
hazards and public health nuisance. II
(D) No trash shall be burned within fifty
feet (50') of any facility except in an approved
incinerator. I/II
(E) Trash may be burned only in a masonry or metal container. The container shall be
equipped with a metal cover with openings no
larger than one-half inch (1/2") in size. II/III
(41) Minimum Staffing for Safety and Protective Oversight to Residents.
(A) In a building that is of fire-resistant
construction or a building with a sprinkler
system, minimum staffing shall be the following:
Time Personnel Residents
7 a.m. to 3 p.m. 1 3–10*
(Day)
3 p.m. to 11 p.m. 1 3–15*
(Evening)
11 p.m. to 7 a.m. 1 3–20*
(Night)
*One (1) additional staff person for every
fraction after that. I/II
(B) In a building that is of nonfire-resistant
construction or a building that has a sprinkler
system exemption, minimum staffing shall be
the following:
Time Personnel Residents
7 a.m. to 3 p.m. 1 3–10*
(Day)
3 p.m. to 11 p.m. 1 3–15*
(Evening)
11 p.m. to 7 a.m. 1 3–15*
(Night)
*One (1) additional staff person for every
fraction after that. I/II
AUTHORITY: sections 198.074 and 198.079,
RSMo Supp. 2011.* This rule originally filed
as 13 CSR 15-14.022. Original rule filed July
13, 1983, effective Oct. 13, 1983. Amended:
Filed Sept. 12, 1984, effective Dec. 13, 1984.
Amended: Filed Aug. 1, 1988, effective Nov.
11, 1988. Amended: Filed May 11, 1998,
effective Dec. 30, 1998. Emergency amendment filed May 12, 1999, effective May 22,
1999, expired Feb. 24, 2000. Amended: Filed
July 13, 1999, effective Jan. 30, 2000. Moved
to 19 CSR 30-85.022, effective Aug. 28, 2001.
Emergency amendment filed Nov. 24, 2008,
effective Dec. 4, 2008, expired June 1, 2009.
Amended: Filed Nov. 24, 2008, effective May
30, 2009. Amended: Filed March 15, 2012,
effective Oct. 30, 2012. **
*Original authority: 198.074, RSMo 2007 and 198.079,
RSMo 1979, amended 2007.
**Pursuant to Executive Order 21-07, 19 CSR 30-85.022, sections
(8) and (9) and subsections (10)(C) and (11)(A) was suspended from
April 15, 2020 through May 1, 2021. Pursuant to Executive Order
21-09, 19 CSR 30-85.022, subsection (33)(D) was suspended from
April 15, 2020 through December 31, 2021.