10 CSR 60-15.080
Monitoring Requirements for Water Quality Parameters
PURPOSE: This rule sets forth the procedures and requirements for monitoring drinking water to determine how corrosive the
water is to the distribution system.
(1) General Requirements. All large (serving
more than fifty thousand (>50,000) persons)
water systems and all small-(serving less than
or equal to three thousand three hundred
(£3,300) persons) and medium-size (serving
three thousand three hundred one to fifty
thousand (3,301–50,000) persons) systems
that exceed the lead or copper action level
shall monitor water quality parameters in
addition to lead and copper in accordance
with this rule. The requirements of this rule
are summarized in the table at the end of this
rule.
(A) Sample Collection Methods.
1. Tap samples shall be representative of
water quality throughout the distribution system taking into account the number of persons served, the different sources of water,
the different treatment methods employed by
the system and seasonal variability. Tap sampling under this rule is not required to be
conducted at taps targeted for lead and copper sampling under 10 CSR 60-15.070(1).
(Note: Systems may find it convenient to conduct tap sampling for water quality parameters at sites used for coliform sampling under
10 CSR 60-4.020(1)(A).)
2. Samples collected at the entry
point(s) to the distribution system shall be
from locations representative of each source
after treatment. If a system draws water from
more than one (1) source and the sources are
combined before distribution, the system
must sample at an entry point to the distribution system during periods of normal operating conditions (that is, when water is representative of all sources being used).
(B) Number of Samples.
1. Systems shall collect two (2) tap samples for applicable water quality parameters
during each monitoring period specified
under sections (2)–(5) of this rule from the
following number of sites:
Sites for Water
System Size
Quality Parameters
(# People Served)
(Number)
>100,000
25
10,001–100,000
10
3,301–10,000
3
501–3,300
2
101–500
1
£100
1
2. Except as provided in subsection
(3)(C) of this rule, systems shall collect two
(2) samples for each applicable water quality
parameter at each entry point to the distribution system during each monitoring period
specified in section (2) of this rule. During
each monitoring period specified in sections
(3)–(5) of this rule, systems shall collect one
(1) sample for each applicable water quality
parameter at each entry point to the distribution system.
(2) Initial Sampling. All large (serving more
than fifty thousand (>50,000) persons) water
systems shall measure the applicable water
quality parameters as specified in this rule at
taps and at each entry point to the distribution
system during each six- (6-) month monitoring period specified in 10 CSR 6015.070(4)(A). All small (serving less than or
equal to three thousand three hundred
(£3,300) persons) and medium-size (serving
three thousand three hundred one to fifty
thousand (3,301–50,000) persons) systems
shall measure the applicable water quality
parameters at the locations specified as follows during each six- (6-) month monitoring
period specified in 10 CSR 60-15.070(4)(A)
during which the system exceeds the lead or
copper action level:
(A) At taps—
1. pH;
2. Alkalinity;
3. Orthophosphate, when an inhibitor
containing a phosphate compound is used;
4. Silica, when an inhibitor containing a
silicate compound is used;
5. Calcium;
6. Conductivity; and
7. Water temperature; and
(B) At each entry point to the distribution
system, all of the applicable parameters listed
in subsection (2)(A) of this rule.
(3)
Monitoring
After
Installation
of
Corrosion Control. Any large system which
installs optimal corrosion control treatment
pursuant to 10 CSR 60-15.020(1)(A)4. shall
measure the water quality parameters at the
locations and frequencies specified in this
section during each six- (6-) month monitoring period specified in 10 CSR 6015.070(4)(B)1. Any small- or medium-size
system which installs optimal corrosion control treatment shall conduct monitoring during each six- (6-) month monitoring period as
specified in 10 CSR 60-15.070(4)(B)2. in
which the system exceeds the lead or copper
action level.
(A) At taps, two (2) samples for—
1. pH;
2. Alkalinity;
3. Orthophosphate, when an inhibitor
containing a phosphate compound is used;
4. Silica, when an inhibitor containing a
silicate compound is used; and
5. Calcium, when calcium carbonate
stabilization is used as part of corrosion control.
(B) Except as provided in subsection
(3)(C) of this rule, at each entry point to the
distribution system, at least one (1) sample
no less frequently than every two (2) weeks
(bi-weekly)—
1. For pH;
2. When alkalinity is adjusted as part of
optimal corrosion control, a reading of the
dosage rate of the chemical used to adjust
alkalinity and the alkalinity concentration;
and
3. When a corrosion inhibitor is used as
part of optimal corrosion control, a reading
of the dosage rate of the inhibitor used and
the concentration of orthophosphate or silica
(whichever is applicable).
(C) Any groundwater system can limit
entry point sampling described in subsection
(3)(B) of this rule to those entry points that
are representative of water quality and treatment conditions throughout the system. If
water from untreated groundwater sources
mixes with water from treated groundwater
sources, the system must monitor for water
quality parameters both at representative
entry points receiving treatment and representative entry points receiving no treatment.
Prior to the start of any monitoring under this
subsection, the system shall provide to the
department written information identifying
the selected entry points and documentation,
including information on seasonal variability,
sufficient to demonstrate that the sites are
representative of water quality and treatment
conditions throughout the system.
(4) Monitoring After Department Specifies
Water Quality Parameter Values for Optimal
Corrosion Control. After the department
specifies the values for applicable water quality control parameters reflecting optimal corrosion control treatment under 10 CSR 6015.030(7), all large (serving more than fifty
thousand (>50,000) persons) systems shall
measure the applicable water quality parameters in accordance with section (3) of this rule
and determine compliance with the requirements of 10 CSR 60-15.030(8) every six (6)
months with the first six- (6-) month period
to begin on either January 1 or July 1,
whichever comes first, after the department
specifies the optimal values under 10 CSR
60-15.030(7). Any small- (serving less than
three thousand three hundred (<3,300) persons) or medium-size (serving three thousand
three hundred one to fifty thousand (3,301–
50,000) persons) system shall conduct such
monitoring during each six- (6-) month period specified in 10 CSR 60-15.070(4)(C) in
which the system exceeds the lead or copper
action level. For any such small- and medium-size system that is subject to a reduced
monitoring frequency pursuant to 10 CSR 6015.070(4)(D) at the time of the action level
exceedance, the start of the applicable six- (6-
) month period under this section shall coincide with the start of the applicable monitoring period under 10 CSR 60-15.070(4)(D).
Compliance with department-designated optimal water quality parameter values shall be
determined as specified under 10 CSR 6015.030(8).
(5) Reduced Monitoring.
(A) Any water system that maintains the
range of values for the water quality parameters reflecting optimal corrosion control treatment during each of two (2) consecutive six-
(6-) month monitoring periods under section
(4) of this rule shall continue monitoring at
the entry point(s) to the distribution system as
specified in subsection (3)(B) of this rule.
That system may collect two (2) tap samples
for applicable water quality parameters from
the following reduced number of sites during
each six- (6-) month monitoring period.
Sites for
System Size
Water Quality Parameters
(# People Served)
(Reduced Number)
>100,000
10
10,001–100,000
7
3,301–10,000
3
501–3,300
2
101–500
1
£100
1
(B) Any water system that maintains the
range of values for the water quality parameters reflecting optimal corrosion control treatment specified by the department under 10
CSR 60-15.030(6) during three (3) consecutive years of annual monitoring under this
subsection may reduce the frequency with
which it collects the number of tap samples
for applicable water quality parameters specified in subsection (5)(A) of this rule from
every six (6) months to annually. This sampling begins during the calendar year immediately following the end of the monitoring
period in which the third consecutive year of
six- (6-) month monitoring occurs. Any water
system that maintains the range of values for
the water quality parameters reflecting optimal corrosion control treatment specified by
the department under 10 CSR 60-15.030(6)
during three (3) consecutive years of annual
monitoring under this rule may reduce the
frequency with which it collects the number
of tap samples for applicable water quality
parameters specified in section (6) of this rule
from annually to every three (3) years. This
sampling begins no later than the third calendar year following the end of the monitoring
period in which the third consecutive year of
monitoring occurs. A water system may
reduce the frequency with which it collects
tap samples for applicable water quality
parameters specified in subsection (5)(A) of
this rule to every three (3) years if it demonstrates during two (2) consecutive monitoring
periods that its tap water lead level at the
ninetieth percentile is less than or equal to the
PQL for lead specified in 10 CSR 605.010(5)(H), that its tap water copper level at
the ninetieth percentile is less than or equal to
0.65 mg/L for copper, and that it also has
maintained the range of values for the water
quality parameters reflecting optimal corrosion control treatment specified by the
department under 10 CSR 60-15.030(7).
Monitoring conducted every three (3) years
shall be done no later than every third calendar year.
(C) A water system that conducts sampling
annually shall collect these samples evenly
throughout the year so as to reflect seasonal
variability.
(D) Any water system subject to the
reduced monitoring frequency that fails to
operate at or above the minimum value or
within the range of values for the water quality parameters specified by the department in
10 CSR 60-15.030(7) for more than nine (9)
days in any six- (6-) month period specified
in 10 CSR 60-15.030(8) shall resume distribution system tap water sampling in accordance with the number and frequency
requirements in section (4) of this rule. Such
a system may resume annual monitoring for
water quality parameters at the tap at the
reduced number of sites specified in subsection (5)(A) of this rule after it has completed
two (2) subsequent consecutive six- (6-)
month rounds of monitoring that meet the criteria of that paragraph and/or may resume triennial monitoring for water quality parameters at the tap at the reduced number of sites
after it demonstrates through subsequent
rounds of monitoring that it meets the criteria
of either paragraph (5)(B)1. or (5)(B)2. of
this rule.
(6) Additional Monitoring by Systems. The
results of any monitoring conducted in addition to the minimum requirements of this rule
shall be considered by the system and the
department in making any determinations
(that is, determining concentrations of water
quality parameters) under this rule or 10 CSR
60-15.030.
Summary of Monitoring Requirements for Water Quality Parameters1
Monitoring Period
Parameters2
Location
Frequency
Initial monitoring
pH, alkalinity,
Taps and at entry
Every six (6) months
orthophosphate
point(s) to the
or silica3,
distribution
calcium, conductivity,
system
temperature
After
pH, alkalinity,
Taps
Every six (6) months
installation
orthophosphate or
of corrosion
silica3, calcium4
control
pH, alkalinity dosage
Entry point(s) to
No less frequently
rate and concentration
distribution system6
than every two (2)
(if alkalinity adjusted
weeks
as part of corrosion
control), inhibitor
dosage rate and
inhibitor residual5
After department
pH, alkalinity,
Taps
Every six (6) months
specifies parameter
orthophosphate or
values for optimal
silica3, calcium4
corrosion control
pH, alkalinity dosage
Entry point(s) to the
No less frequently
rate and concentration
distribution system6
than every two (2)
(if alkalinity adjusted
weeks
as part of corrosion
control), inhibitor
dosage rate and
inhibitor residual5
Reduced Monitoring
pH, alkalinity,
Taps
Every six (6) months,
orthophosphate
annually7 or every three
or silica3, calcium4
(3) years8 at a reduced
number of sites
pH, alkalinity dosage
Entry point(s) to the
No less
rate and concentration
distribution system6
frequently than every
(if alkalinity adjusted
two (2) weeks
as part of corrosion
control), inhibitor
dosage rate and
inhibitor residual5
1Table is for illustrative purposes; consult the text of this rule for precise regulatory requirements.
2Small- and medium-size systems have to monitor for water quality parameters only during monitoring periods in which the system exceeds
the lead or copper action level.
3Orthophosphate must be measured only when an inhibitor containing a phosphate compound is used. Silica must be measured only when an
inhibitor containing silicate compound is used.
4Calcium must be measured only when calcium carbonate stabilization is used as part of corrosion control.
5Inhibitor dosage rates and inhibitor residual concentrations (orthophosphate or silica) must be measured only when an inhibitor is used.
6Groundwater systems may limit monitoring to representative locations throughout the system.
7Water systems may reduce frequency of monitoring for water quality parameters at the tap from every six (6) months to annually if they have
maintained the range of values for water quality parameters reflecting optimal corrosion control during three (3) consecutive years of moni-
toring.
8Water systems may further reduce the frequency of monitoring for water quality parameters at the tap from annually to once every three (3)
years if they have maintained the range of values from water quality parameters reflecting optimal corrosion control during three (3) consec-
utive years of annual monitoring. Water systems may accelerate to triennial monitoring for quality parameters at the tap if they have main-
tained ninetieth percentile lead levels less than or equal to 0.005 mg/L, ninetieth percentile copper levels less than or equal to 0.65 mg/L,
and the range of water quality parameters designated by the department under 10 CSR 60-15.030(7) as representing optimal corrosion con-
trol during two (2) consecutive six- (6-) month monitoring periods.
AUTHORITY: section 640.100, RSMo Supp.
2011.* Original rule filed Aug. 4, 1992, effective May 6, 1993. Amended: Filed Feb. 1,
1996, effective Oct. 30, 1996. Amended:
Filed Aug. 14, 2001, effective April 30, 2002.
Amended: Filed Oct. 17, 2011, effective May
30, 2012.