20 CSR 4240-10.030
Standards of Quality
PURPOSE: This rule prescribes standards of quality for electric, gas
and water utilities operating under the jurisdiction of the Public
Service Commission.
(1) This rule applies to all gas, electric, and water corporations,
as these terms are defined in section 386.020, RSMo, engaged
in the business of furnishing gas or electricity for light, heat,
or power, or supplying water for domestic or commercial uses
within Missouri. The word utility, when used in these rules,
shall be construed to mean any gas corporation, electric corpo
ration, or water corporation engaged in the designated busi
ness. Sections (10), (11), and (12) of this rule additionally apply
to all persons, municipalities, or corporations owning, leasing,
operating, or controlling facilities used in the transportation
by pipeline and distribution to customers within Missouri of
manufactured gas and renewable natural gas (RNG) as defined
in 20 CSR 4240-40.100.
(2) A record shall be kept, systematically arranged, of the
names and addresses of all consumers furnished with metered
service, with the identification number of meter or meters in
use for each consumer. Records shall be kept showing the fol
lowing information for each meter: date of purchase; compa
ny’s number, if any; name plate data; place of last installation;
and date of last test.
(3) Each utility shall keep records of tests of the accuracy of
each of its meters, until superseded by a later test but not less
than two (2) years. These records shall give sufficient infor
mation to identify the meter; the reason for the test; the date
of the test and reading of the meter; the name of the person
making the test; the accuracy as found and as left, together
with enough of the data taken at the time of the test to permit
the convenient checking of the methods employed; and the
calculations. Systems of meter and test records already in use
will meet with the approval of the commission, provided they
conform substantially with the rule. Application shall be made
to the commission for this approval.
(4) The allowance of certain variations from correctness on
meters as specified in this rule does not mean that meters may
deliberately be set in error by the amount of the tolerance. This
tolerance is specified to allow for the necessary irregularities
in meter tests and maintenance conducted on a commercial
scale.
(5) Each service meter shall be suited to the particular installa
tion to which it is assigned and chosen with a view of obtain
ing the best adaption to local conditions and to the load.
(6) It is suggested that those utilities not required to maintain
certain testing equipment specified in the rule arrange to per
form the tests by making use of the testing equipment of some
nearby utility required to maintain the testing equipment.
(7) Reasonable efforts shall be made to eliminate interruptions
of service, and when these interruptions occur, service should
be re-established with the shortest possible delay. When ser
vice is interrupted for the purpose of working on any portion
of the system, the interruption should occur at a time which
will cause the least inconvenience to the consumer, and those
seriously affected by the interruptions, if possible, should be
notified in advance. A record shall be kept of all interruptions
of service on the entire system or major divisions, including the
times, duration and cause of each interruption. These records
shall be filed, made available for inspection by the commission,
and preserved for a period of at least one (1) year.
(8) Each utility shall keep a record of the time of starting up
and shutting down all important items of equipment. A record
shall be kept of the indications of the principal switchboard in
struments, station meters, gauges, and the like, readings being
taken at sufficiently frequent intervals to show the characteris
tics of the load. When feasible, graphic recording instruments
should be used for this purpose in accordance with the best
modern practice. These records or charts, suitably identified
and dated, shall be filed available for inspection by the com
mission and preserved for a period of at least two (2) years.
(9) When gas is to be tested under this rule, a cubic foot of gas
shall be taken to be that amount of gas which occupies the vol
ume of one (1) cubic foot when saturated with water vapor and
at a temperature of sixty degrees Fahrenheit (60°F) and under
a pressure above zero (0) of thirty inches (30") of mercury. For
the purpose of measurement of gas to a consumer at the stated
delivery pressure, a cubic foot of gas shall be taken to be the
amount of gas which occupies a volume of one (1) cubic foot
under the conditions existing in the consumer’s meter as and
where installed, provided the meter is not subject to abnor
mal temperature conditions. In cases where gas is supplied to
customers through orifice or positive displacement meters at
other than stated delivery pressure, a cubic foot of gas shall
be defined to be that volume of gas which, at sixty degrees
Fahrenheit (60°F) and at absolute pressure of 14.73 pounds per
square inch (psi) (thirty inches (30") of mercury), occupies one
(1) cubic foot, except that in cases where different bases that
are considered by the commission to be fair and reasonable are
provided for in gas sales contracts or in rules or practices of a
utility, these different bases shall be effective.
(10) Unless otherwise ordered by the commission, all gas, in
cluding manufactured gas and RNG delivered to customers
in the state other than gas that is delivered on an interstate
natural gas pipeline subject to the jurisdiction of the Federal
Energy Regulatory Commission (FERC), shall conform to the
following specifications:
(A) The gas shall have a gross heating value between nine
hundred fifty (950) and one thousand two hundred (1,200)
British thermal units (Btu) per dry standard cubic foot. For
purposes of this rule, the term “gross heating value” when
applied to a cubic foot of gas shall mean the number of Btus
produced by the complete combustion of the amount of gas
that would occupy a volume of one (1) cubic foot at fourteen
and seventy-three hundredths (14.73) pounds per square inch
absolute (psia) at a temperature of sixty degrees Fahrenheit
(60oF);
(B) The gas shall not contain more than seven (7) pounds of
water in vapor phase per million cubic feet;
(C) The gas shall be free from hydrocarbons and water (H2O)
in liquid state at the temperatures and pressures delivered,
and shall not have a hydrocarbon dew point in excess of the
lower of forty degrees Fahrenheit (40oF) or the gas delivery
temperature;
(D) The gas shall not contain in excess of one percent (1%)
by volume of oxygen (O2), and every reasonable effort shall be
made to keep the gas completely free of oxygen;
(E) The gas shall not contain more than four hundred (400)
parts per million (ppm) of hydrogen (H2);
(F) The gas shall not contain more than one-half (0.5) grain of
hydrogen sulfide (H2S) per one hundred (100) cubic feet;
(G) The gas shall not contain more than twenty (20) grains of
total sulfur per one hundred (100) cubic feet;
(H) The gas shall not contain more than two percent (2%) by
volume of carbon dioxide (CO2);
(I) The gas shall not contain more than three percent (3%) by
volume of nitrogen (N2);
(J) The gas shall be at a temperature between forty degrees
Fahrenheit (40oF) and one hundred degrees Fahrenheit (100oF);
(K) The gas shall be substantially free from impurities that
may cause excessive fumes when combusted in a properly
designed and adjusted burner;
(L) The gas shall not contain, either in the gas or in any liquid
within the gas, any microbial organism, active bacteria, or
bacterial agent capable of contributing to or causing corrosion
or other operational problems. For purposes of this rule,
microbial organisms, bacteria, and bacterial agents include
sulfate reducing bacteria (SRB) and acid producing bacteria
(APB); and
(M) Each gas utility, including municipal systems, receiving or
transporting manufactured gas or RNG on its gas transmission
and distribution systems shall further limit the quantity
of impurities and physical and chemical properties in the
manufactured gas and RNG as necessary so that the gas is
delivered within the limits of its system.
(11) Each gas utility, including municipal systems, receiving
or transporting manufactured gas and RNG on its gas
transmission and distribution systems shall provide, install,
operate, maintain, and continuously monitor sensors and
testing equipment to determine if the quality of manufactured
gas and RNG meets the requirements of section (10) of this rule.
(12) Each gas utility, including municipal systems, receiving or
transporting manufactured gas or RNG on its gas transmission
and distribution systems shall install an isolation device at
each location where manufactured gas or RNG is delivered
to its natural gas pipeline systems. Each isolation device shall
be designed and operated to completely isolate the source
of manufactured gas or RNG from the downstream pipeline
when the gas does not meet the quality standards in section
(10) of this rule, as determined by the monitoring and testing
performed in section (11) of this rule.
(13) Reserved.
(14) Reserved.
(15) Reserved.
(16) Except by special authority from the commission for the
delivery of a higher service pressure, gas shall be furnished at
not less than equivalent to four inches (4") water column nor
more than two (2) pounds per square inch gauge (psig) pressure
measured at the inlet of the consumer’s piping downstream
from the meter, provided that with respect to any consumer
whose rate of consumption, based upon designed capacity
of installed equipment, reaches or exceeds four hundred fifty
(450) cubic feet per hour, a utility, without obtaining special
permission, may furnish gas to the consumer at a maximum
pressure greater than two (2) psig if the utility shall determine
that a greater pressure is available and is desirable to effect
economy in delivery or efficiency in utilization of gas by the
consumer. In those instances where the delivery pressure to
the consumer is greater than an equivalent to fourteen inches
(14") of water column, a regulator shall be required ahead of all
gas consuming equipment. The maximum pressure on any one
(1) day at the inlet of the consumer’s piping downstream from
the meter shall never exceed twice the minimum pressure
at that point on that day. At the time a utility establishes gas
service to any applicant, a leakage test shall be made at the
intended delivery pressure to the consumer to insure that the
applicant’s fuel line is in a safe condition, provided, however, if
the maximum delivery pressure exceeds two (2) psig then the
customer’s piping system shall be tested at one and one-half (1
1/2) times the maximum delivery pressure. Service shall not be
established until the utility determines that this test has been
properly made.
(17) Each utility furnishing gas service in cities of two thou
sand five hundred (2,500) inhabitants or over shall maintain
a graphic recording pressure gauge at its plant, downtown of
fice, or at some central point in the distributing system or each
subdivision of the system where continuous records shall be
made of the service pressure at that point. Utilities operating in
AND INSURANCE
cities of five thousand (5,000) or more inhabitants shall equip
themselves with one (1) or more graphic recording pressure
gauges in addition to the foregoing and shall make frequent
records, each covering intervals of at least twenty-four (24)
hours duration of the gas service pressure at various points on
the system. All records or charts made by these meters shall be
identified, dated, and kept on file available for inspection for a
period of at least two (2) years.
(18) No gas service meter shall be allowed in service which has
incorrect gear ratio or dial train or is in any way mechanically
defective or shows an error in measurement in excess of two
percent (2%) when passing gas at the rate of six (6) cubic feet
per hour per rated light capacity. When adjustment is neces
sary, the adjustment should be made to within at least one
percent (1%) of correct registration. Tests for accuracy shall be
made with a suitable meter prover, at least two (2) consecutive
test runs being made which agree within one-half (1/2) of one
percent (1%).
(19) Unless otherwise ordered by the commission, each gas ser
vice meter installed shall be periodically removed, inspected
and tested at least once every one hundred twenty (120)
months, or as often as the results obtained may warrant to in
sure compliance with the provisions of section (18) of this rule.
(20) Each utility furnishing metered gas service shall make a
test of the accuracy of any gas service meter free of charge
upon request of a consumer, provided that the meter has not
been tested within twelve (12) months previous to the request.
The consumer shall be notified of the time and place of the test
so that s/he may be present to witness the test should s/he so
desire. A written report giving the results of the requested test
shall be made to the consumer requesting the results, the orig
inal record being kept on file at the office of the utility under
the provisions of section (2) of this rule.
(21) Any gas service meter will be tested by the commission
upon written application of the consumer or utility as follows:
(A) The utility involved either shall remove the meter or give
its consent to the removal of the meter but the consumer shall
be given an opportunity to witness the disconnection, packing
and shipment of the meter should s/he so desire;
(B) The meter will be returned with a special seal which, if
the meter is to be reinstalled on this consumer’s premises, shall
not be disturbed until after the consumer has been given an
opportunity to inspect the meter;
(C) A fee of two dollars ($2) will be charged by this commis
sion and paid to the Division of Collections of the Department
of Revenue of Missouri for each gas service meter tested having
a capacity of not exceeding ten (10) lights. For larger meters a
proportionally larger fee will be charged, depending upon the
size of the meter; and
(D) If the meter is fast beyond the prescribed limit in section
(18) of this rule, the utility will be required to pay the test fee
and cost of shipping meter; otherwise these expenses shall be
borne by the consumer requesting the test.
(22) Each utility having more than one hundred (100) gas
meters in service shall maintain one (1) or more suitable gas
meter provers of standard design and keep in proper adjust
ment so as to register the condition of meters tested within
one-half (1/2) of one percent (1%). Each meter prover must be
accompanied by a certificate of calibration indicating that it
has been tested with a standard which has been certified by
the National Bureau of Standards or some testing laboratory of
recognized standing. Meter provers must be located in a large,
comfortable working space, free from excessive temperature
variations, easily accessible and equipped with all necessary
facilities and accessories. Meter testing equipment shall at all
reasonable hours be accessible for inspection and use by any
authorized representative of this commission.
(23) Each electric utility supplying energy from a constant
potential system shall adopt standard service voltages for the
entire system and each subdivision. Every reasonable effort
shall be made by the use of proper equipment and operation
to maintain those voltages within a practicable tolerance. The
suitability and adequacy of these service voltages may be de
termined at any time by the commission. For lighting service,
the variation in voltage for periods longer than one (1) minute,
as measured at the consumer’s cut-out, shall not exceed or fall
below these units—
(A) For general all-purpose supply where nominal voltage
is one hundred twenty (120) volts, one hundred twenty-seven
(127) volts maximum and one hundred ten (110) volts minimum;
(B) For general all purpose supply where nominal voltage is
one hundred fifteen (115) volts, one hundred twenty-five (125)
volts maximum and one hundred eight (108) volts minimum;
(C) For rural service, one hundred twenty-seven (127) volts
maximum and one hundred ten (110) volts minimum; and
(D) For power service, the voltage, at any time, shall not be
greater than ten percent (10%) above or below standard service
voltage. The ranges of voltages indicated in this subsection
shall be considered as being made up of three (3) voltage
zones—namely, the favorable zone, tolerable zone and the ex
treme zone. The favorable zone shall be that range of voltage
variation with four percent (4%) above and five percent (5%)
below nominal. The tolerable zone shall be that zone between
six percent (6%) above and eight percent (8%) below nominal
voltage, and the extreme zone shall not exceed the maximum
and minimum range of the tolerable zone more than an addi
tional three percent (3%). When the system voltage variations
extend to within the extreme zone, the utility shall take those
steps as may be required to improve the system voltages, or the
subdivisions of, the utility, as the case may be, to within either
the favorable or the tolerable zone. The utilities will not be held
responsible for variations in service voltage at a customer’s
premises caused by the operation of that customer’s apparatus
in violation of the utility’s rules or by the action of the elements
or causes beyond the utility’s control. The requirements listed
in this paragraph may be waived for any particular consumer
by special written agreement other than the regular service
contract or application, provided that the arrangement does
not affect the quality or service to other consumers.
(24) To ensure compliance with the requirements specified in
section (23) of this rule, each utility furnishing electric service
shall supply itself with one (1) or more portable indicating volt
meters, suitable of the service voltages condition. Where two
hundred fifty (250) or more consumers are served by any utility,
it must provide itself with one (1) or more portable graphic re
cording voltmeters suitable for the service voltages furnished.
A sufficient number of voltage surveys must be made by each
utility to indicate that service furnished from various trans
formers and service mains is at all times in compliance with
the previously mentioned requirements. When graphic re
cording voltmeters are used, each chart or record should cover
an interval of at least twenty-four (24) hours duration. These
records or charts suitably identified and dated shall be kept on
file available for inspection for a period of at least two (2) years.
(25) Except as provided in this rule, each electric service watthour meter placed in service shall be tested and adjusted for
accuracy before installation or within thirty (30) days after
that. New meters manufactured during and since 1937 may be
placed in service without testing if the meters are not opened
and if the manufacturer’s seal is not broken. Whenever a watthour meter manufactured during or since 1937 is required to
be tested for reasons other than physical or electrical damage,
it should not be opened unless faulty registration (as defined
in this rule) is indicated. Each watt-hour meter which appears
to be in good condition may be tested by loading the meter
sufficiently to cause it to register not less than one hundred
(100) kilowatt hours (kWh) at varying rates of current flow for
a specified period of time. If this procedure is used, the meter
must be checked with a standard meter, previously determined
to be accurate, by reading and comparing the dial registers of
the meter being tested with the standard meter. If the dial reg
ister of the meter being tested shows less than ninety-nine (99)
kWh or more than one hundred one (101) kWh (for each one
hundred (100) kWh of registration at varying rates of current
flow), the meter will be considered as one with faulty regis
tration and will be opened, retested and adjusted. Otherwise,
it will be available to be placed in service. With respect to
the testing of all meters manufactured prior to 1937 and with
respect to those meters manufactured during and since 1937
which are required, under this rule, to be opened, retested
and adjusted, the following procedure shall be followed (This
procedure may be followed in all cases, at the option of the
electric corporation.):
(A) Tests and adjustments for accuracy shall be made at from
five percent to ten percent (5%–10%) and at from seventy-five
percent to one hundred percent (75%–100%) of rated capacity
of meter;
(B) Tests for accuracy at each load shall be made with suit
able working standards by taking the average of at least two (2)
test runs of at least thirty (30) seconds each which agree within
one percent (1%), except that where stroboscopic or similarly
precise methods of testing are used, only one (1) test run need
be made;
(C) Any meter operating on inductive load should be tested
under inductive load and should be adjusted to register accu
rately at the approximate power factor conditions at which the
meter will normally be required to operate, or at fifty percent
(50%) and one hundred percent (100%) power factors;
(D) When testing, each meter shall be adjusted as accurately
as practical for correct registration at the test load specified.
Where necessary to adjust the meter fast at light or heavy load,
for correct registration at normal load or to correct for induc
tive load, the fast adjustment should not exceed two percent
(2%) above correct registration; and
(E) Commutator-type meters, when feasible, should be al
lowed to remain in actual service at least five (5) days before
being tested.
(26) No electric service watt-hour meter shall be allowed in
service which has incorrect constants or dial train, or which
creeps at no load at the rate of more than one (1) disk revolu
tion in five (5) minutes or less when maximum service voltage
under which meter operates is applied or which is in any way
mechanically defective. Nothing contained in this section shall
require any electric corporation to open any new meter manu
factured during and since 1937.
(27) Any electric service meter tested on complaint or for any
other reason after having been in service may be considered
as having been recording within allowable limits of accuracy
at any possible load if it is found to register within three per
cent (3%) of correct registration when tested in accordance
with the provisions of section (25). After the test, however, the
meter shall be adjusted for accuracy in accordance with the
provisions of section (25) before being again placed in service.
It is suggested that the average accuracy of a meter in service
be defined as follows and that the condition of the meter, as
thus determined, be used as a basis for adjusting consumer’s
bills for incorrect registration beyond certain limits where any
utility makes the adjustment a part of its commercial practice:
(A) Test an induction meter or a commutator meter at ap
proximately five percent to ten percent (5%–10%) of rated capac
ity of meter and at seventy-five percent to one hundred percent
(75%–100%) rated capacity of meter; and
(B) The average of the tests at light and heavy load, defined
as the average accuracy or condition of meter, shall be ob
tained by multiplying the result of the test at heavy load by
four (4) and adding the result of the test at light load and divid
ing the total by five (5).
(28) Unless otherwise ordered by the commission, each electric
service watt-hour meter shall be periodically tested in accor
dance with the following schedule or as often as the results
obtained may warrant, and adjusted in accordance with sec
tion (25):
(A) Induction-type meters manufactured prior to 1927—
1. Induction-type meters having rated current capacity
not exceeding fifty (50) amperes, at least once every sixty (60)
months; and
2. Induction-type meters having rated current capacity
exceeding fifty (50) amperes, at least once every twenty-four
(24) months;
(B) Induction-type meters manufactured during the period
1927–1936—
1. Induction-type meters having rated current capacity not
exceeding fifty (50) amperes, at least once every ninety-six (96)
months;
2. Induction-type meters having rated current capacity
exceeding fifty (50) amperes, at least once every thirty (30)
months;
3. Commutator-type meters with rated current capacities
not exceeding fifty (50) amperes and voltage ratings not ex
ceeding two hundred fifty (250) volts, at least once every twen
ty-four (24) months; and
4. All other meters at least once every twelve (12) months;
(C) Induction-type meters manufactured during and since
1937, at least once every two hundred forty (240) months; and
(D) In commutator meters having heavy moving elements
and sapphire jewels, the number of revolutions of the moving
element between tests should not ordinarily exceed one (1)
million.
(29) Each utility furnishing metered electric service shall make
a test of the accuracy of any electric service meter free of
charge upon request of a consumer, provided that the meter
has not been tested within twelve (12) months previous to the
request. The consumer shall be notified of the time and place
of the test so that s/he may be present to witness the test should
s/he so desire. A written report giving the result of the test
shall be made to the consumer requesting the test, the original
record being kept on file at the office of the utility under the
provisions of section (2) of this rule.
AND INSURANCE
(30) Any electric service meter will be tested by the commis
sion upon written application of the consumer or utility. The
utility involved shall either remove the meter or give its con
sent to the removal of the meter, but the consumer shall be
given an opportunity to witness the disconnection, packing
and shipment of the meter should s/he so desire. The meter
will be removed with a special seal which, if the meter is to be
reinstalled on this consumer’s premises, shall not be disturbed
until after the consumer has been given an opportunity to
inspect the meter. A fee of two dollars ($2) will be charged
by this commission and paid to the Division of Collections of
the Missouri Department of Revenue for each single-phase or
direct-current watt-hour meter having a current capacity not
exceeding twenty-five (25) amperes and without instrument
transformers. For other meters a proportionally larger fee will
be charged, depending upon the type and size of the meter. If
the meter is fast beyond the prescribed limit in section (27) of
this rule, the utility will be required to pay the test fee and cost
of shipping the meter; otherwise these expenses shall be borne
by the consumer requesting the test.
(31) Each utility furnishing metered electric service shall main
tain suitable working standards of a rugged type for the test
ing of electric service meters. These working standards must
be calibrated frequently to ensure their accuracy. Approved
secondary standards shall be owned and maintained by each
utility having more than two hundred fifty (250) meters in ser
vice for the calibration of the working standards. All secondary
standards and the working standards of those utilities not
required to maintain secondary standards must be submitted
at sufficiently frequent intervals to ensure unquestionable
accuracy to the Bureau of Standards at Washington, D.C. or to
some testing laboratory of recognized standing for calibration
where the utility does not maintain a testing laboratory hav
ing primary standards. Each standard shall be accompanied
by its certificate of calibration dated and signed by the proper
authority. These certificates when superseded shall be kept on
file at the office of the utility, available for inspection. Meter
testing equipment shall at all reasonable hours be accessible
for inspection and use by any authorized representative of the
commission.
(32) All water furnished by utilities for human consumption
and general household purposes shall conform to standards
adopted by the Missouri Department of Health. The source of
supply shall be of adequate quantity to ensure a supply with
out interruption at all times. Treatment and filtration by ap
proved methods is strongly recommended where doubt exists
as to the quality of the water furnished at any time. Satisfactory
treatment and filtration of water drawn from surface supplies
is required. Disinfection treatment by hypoclorites of lime,
chlorine gas or other approved disinfecting agents, is generally
necessary for all public water supplies. Storage reservoirs for
finished water, where possible, shall be covered to protect the
supply from sunlight and contamination. Where covered reser
voirs are not provided due to local circumstances, chlorination
facilities shall be provided at the reservoir in addition to the
facilities provided at the plant.
(33) Bacteriological analyses shall be periodically made of
water furnished for public uses as prescribed by the Missouri
Department of Health. The commission reserves the right to
require under its supervision an extended bacteriological as
well as physical and chemical examination when deemed
advisable for any particular water furnished. The results of
all tests made must be recorded and kept on file available for
public inspection for a period of at least two (2) years. These re
cords must indicate when, where, and by whom each test was
made. Methods of water analysis prescribed by the Missouri
Department of Health shall be followed as regards chemical,
physical and bacteriological examination and collection of
samples and any departure from these methods must be spe
cifically stated.
(34) Dead ends in the distributing mains should be avoided
as far as possible. Where the dead ends exist, they should be
flushed when necessary to ensure satisfactory quality of water
to consumers. To allow flushing, dead ends should be equipped
with hydrants, flush valves, or other means of allowing water
to be removed from these dead ends.
(35) Every effort must be made to maintain water pressure
which will at no time fall below an adequate minimum pres
sure suitable for domestic service. In addition to furnishing
domestic and commercial service, each utility furnishing
fire-hydrant service must be able, within a reasonable period
of time after notice, to supply fire-hydrant service to local fire
fighting equipment and facilities. No utility, however, shall be
required to install larger mains or fire-hydrants or otherwise
supply fire service, unless proper contractual arrangements
shall have been made with the utility by the municipality,
agency, or individual desiring the service.
(36) Each utility furnishing water service in cities of two thou
sand five hundred (2,500) or five thousand (5,000) inhabitants
shall maintain graphic recording pressure gauges at its plant
and at its downtown office or at some central point in the dis
tributing system, where continuous records shall be made of
the pressure in the mains at these points. Utilities operating in
cities of five thousand (5,000) or more inhabitants shall equip
themselves with one (1) or more graphic recording pressure
gauges in addition to the previously mentioned and shall make
frequent records, each covering intervals of at least twenty-four
(24) hours duration, of the water pressure at various points on
the system. All records or charts made by these meters shall be
identified, dated, and kept on file available for inspection for a
period of at least two (2) years.
(37) No water service meter shall be allowed in service which
has an incorrect gear ratio or dial train or is mechanically
defective or shows an error in measurement in excess of five
percent (5%) when registering water at stream flow equivalent
to approximately one-tenth (1/10) and full normal rating under
the average service pressure. When adjustment is necessary,
the adjustment shall be made as accurately as practical for av
erage rate of flow under actual conditions of installation. Tests
for accuracy shall be made with a suitable testing device in
accordance with the best modern water meter practice and at
rates of flow which will properly reflect the accuracy of meters
over each meter’s range of minimum to maximum flow.
(38) Unless otherwise ordered by the commission, each water
service meter installed shall be periodically removed, in
spected and tested in accordance with the following schedule,
or as often as the results obtained may warrant to insure com
pliance with the provisions of section (37) of this rule:
(A) Five-eighths inch (5/8") meter—ten (10) years or two
hundred thousand (200,000) cubic feet, whichever occurs first;
(B) Three-fourths inch (3/4") meter—eight (8) years or three
hundred thousand (300,000) cubic feet, whichever occurs first;
(C) One inch (1") meter—six (6) years or four hundred thou
sand (400,000) cubic feet, whichever occurs first; and
(D) All meters above one inch (1")—every four (4) years.
(39) Each utility furnishing metered water service shall make a
test of the accuracy of any water service meter free of charge
upon request of a consumer, provided that the meter has not
been tested within twelve (12) months previous to the request.
The consumer shall be notified of the time and place of the test
so that s/he may be present to witness the test should s/he so
desire. A written report giving the result of the requested test
shall be made to the consumer requesting the test, the original
record being kept on file at the office of the utility under the
provisions of section (2) of this rule.
(40) Any water service meter will be tested by the commission
upon written application of the consumer or utility. The utility
involved shall either remove the meter or give its consent to
the removal of the meter, but the consumer shall be given
an opportunity to witness the disconnection, packing and
shipment of the meter should s/he so desire. The meter will
be returned with a special seal which, if the meter is to be
reinstalled on this consumer’s premises, shall not be disturbed
until after the consumer has been given an opportunity to
inspect the meter. A fee of two dollars ($2) will be charged by
this commission and paid to the Division of Collections of the
Missouri Department of Revenue for each water service meter
tested ranging in size up to one inch (1"). For larger meters a
proportionally larger fee will be charged, depending upon the
size of the meter. If the meter is fast beyond the prescribed limit
in section (37) of this rule, the utility will be required to pay the
test fee and cost of shipping meter; otherwise these expenses
shall be borne by the consumer requesting the test.
(41) Each utility furnishing metered water service in cities of
three thousand (3,000) or more inhabitants shall maintain one
(1) or more suitable water meter testers and keep the water
meter tester in proper adjustment so as to register accurately
the condition of the meters tested at all times. Meter testers
must be located in a suitable working space, easily accessible
and equipped with all necessary facilities and accessories.
Meter testing equipment shall at all reasonable hours be ac
cessible for inspection by any authorized representative of the
commission or by any authorized representative of any de
partment of weights and measures of Missouri or any political
subdivision in which the utility operates.
(42) Preliminary engineering reports followed by detailed
plans and specifications for new constructions, additions to or
changes or alterations to any existing public water supply or
water purification plant shall be submitted to the Department
of Health for examination and written approval secured from
the Department of Health before contracts are let or construc
tion begun. Water utilities must comply with all regulations of
the Department of Health or other regulatory bodies having ju
risdiction pertaining to installation, extension, and operation
of public water supplies.
(43) Utilities shall determine the characteristics of service to be
made available to each consumer, based upon the location of
the premises, size and operating characteristics of the consum
er’s equipment and shall furnish information, upon request, as
to the standard class of service to be furnished which, in the
case of either new or enlarged electric connections, shall spec
ify the nominal voltage and number of phases and the number
of wires over which service will be delivered. Utilities, when
requested, shall provide reasonable assistance to consumers in
the selection of equipment best adapted to the service to be
furnished and inform consumers as to conditions under which
efficient use of service may be realized.
AUTHORITY: sections 386.310 and 393.140, RSMo 2016, and sec
tion 386.895, RSMo Supp. 2024.* This rule originally filed as 4
CSR 240-10.030. Original rule filed March 5, 1953, effective March
15, 1953. Amended: Filed Sept. 22, 1959, effective Oct. 1, 1959.
Amended: Filed May 2, 1968, effective May 16, 1968. Moved to 20
CSR 4240-10.030, effective Aug. 28, 2019. Amended: Filed May 15,
2024, effective Dec. 30, 2024.
*Original authority: 386.310 RSMo 1939, amended 1979, 1989, 1996; 386.895, RSMo
2021; and 393.140, RSMo 1939, amended 1949, 1967.