11 CSR 40-2.040
Heating Boiler
PURPOSE: This rule is to address the design, construction, installation, and operation of heating boilers, water heaters, and jacketed
steam kettles.
(1) As used in this rule, the term “these rules” is intended to
mean 11 CSR 40-2.010 through 11 CSR 40-2.065.
(2) Heating Boilers, Water Heaters, Pool Heaters, and Fired
Jacketed Steam Kettles, Installed or Contracted for Prior to
November 12, 1986.
(A) The service life of any boiler, water heater, pool heater,
or fired jacketed steam kettle of standard construction shall be
unlimited, provided:
1. It meets the inspection requirements of 11 CSR 40-2.022;
and
2. All controls and safety devices required by American
Society of Mechanical Engineers (ASME) Section IV Code for
heating boilers and water heaters and ASME Section VIII,
Division 1 Code for fired jacketed steam kettles and these rules
shall be installed and operable.
(B) The service life of any heating boiler, water heater,
pool heater, or fired jacketed steam kettle of nonstandard
construction shall be thirty (30) years. The thirty (30)-year
life may be extended with the chief inspector’s approval and
compliance with the following requirements:
1. The operating pressure cannot exceed the maximum
allowable working pressure (MAWP). The boiler, water heater,
or fired jacketed steam kettle MAWP shall be calculated in
accordance with the ASME Code or the requirements of the
original code of construction. Objects manufactured to a
standard other than the ASME Code shall be evaluated in
accordance with the “state special” requirements in accordance
with 11 CSR 40-2.064. The allowable stress shall be no greater
than eleven thousand pounds per square inch (11,000 psi). The
joint efficiency shall be in accordance with the appropriate
edition and addenda of the ASME Code, most applicable for the
type of construction. The MAWP of any cast iron boiler shall
not be greater than fifteen (15) psi steam or thirty (30) psi water
pressure;
2. A pressure test shall be conducted every four (4) years
at normal operating pressure not to exceed the MAWP of the
object. The test pressure shall be held for at least thirty (30)
minutes without evidence of leakage and documented to the
satisfaction of the inspector. The inspector need not witness the
test. The test may be an operational test. If the object exhibits
any signs of leakage, it shall be repaired prior to restoring the
object to service;
3. All safety devices and controls required by the applicable
ASME Code and these rules shall be installed and operable.
(3) Heating Boilers, Water Heaters, Pool Heaters, and Fired
Jacketed Steam Kettles Contracted after November 12, 1986.
(A) New and second-hand heating boilers, water heaters, and
pool heaters shall be designed, fabricated, and installed to the
requirements of ASME Section IV Code and these rules. New
and second-hand fired jacketed steam kettles shall be designed,
fabricated, and installed to the requirements of ASME Section
VIII, Division 1 Code and these rules.
(B) Reinstalled boilers may be of standard or nonstandard
construction and shall be installed in accordance with the
requirements of the ASME Code and these rules, non-standard
heating boilers cannot be reinstalled in Missouri except when
relocating from one location to another location within
Missouri. Approval of the chief inspector shall be obtained
prior to reinstalling a nonstandard boiler.
(4) General Requirements for Heating Boilers, Water Heaters,
Pool Heaters, and Fired Jacketed Steam Kettles.
(A) Heating boilers, water heaters, pool heaters, and fired
jacketed steam kettles shall not be operated for a purpose not
originally intended by the manufacturer unless approved by
the board (i.e., potable water heaters may not be operated as a
steam or hot water heating boiler).
(B) Heating boilers, water heaters, pool heaters, and fired
jacketed steam kettles must be installed in accordance with the
manufacturer’s instructions and these rules, unless otherwise
approved by the chief inspector.
(C) Heating boilers with heat input less than 12,500,000 British
thermal units per hour (Btu/hr) contracted after January 1, 2004,
shall meet the requirements of ASME CSD-1. Fuel gas piping for
these boilers shall comply with the requirements of National
Fire Protection Association (NFPA) 54. Oil burning equipment
shall comply with the requirements of NFPA 31. Single unit
boilers with heat input greater than or equal to 12,500,000
Btu/hr, boilers with pulverized fuel systems, and waste heat
boilers shall meet the requirements of NFPA 85. All controls
required by NFPA 85 for automatically fired boilers shall be
installed in accordance with the installation requirements of
ASME CSD-1. Existing installations are exempt from these rules
except that any modification or replacements to the controls
after January 1, 2004, shall meet the requirements for new
installations. Boilers installed on or after January 1, 2010, must
be in accordance with the National Board Inspection Code, Part
1, and these rules.
(D) All safety and safety relief valve outlets shall be piped to
a safe discharge. There shall be no valves on the outlet piping
or between the boiler and the safety or safety relief valve inlet.
The end of all discharge piping shall be visible to the operator
when piped into a drain. Drains on safety or safety relief valve
bodies shall remain open at all times. Safety or safety relief valve
inlet and outlets shall not be reduced. Weighted lever safety
valves are prohibited. Safety valves with either the seat or disk
of cast iron are prohibited. The minimum valve capacity shall
be in accordance with ASME Section IV Code for heating boilers
and hot water heaters and Appendix 19 of ASME Section VIII,
Division 1 Code for fired jacketed steam kettles. Alternatively,
the relieving capacity for heating boilers may be determined
based on the burner output rating or by multiplying the
heating surface in square feet by the applicable value in the
following table:
Minimum Pounds of Steam Per Hour Per Square Foot of
Heating Surface
Fire Tube
Water Tube
Boiler
Boiler
Boiler
Hand fired
5
6
Stoker fired
7
9
Oil, gas, pulverized
fuel fired
8
10
Waterwall
Hand fired
8
8
Stoker fired
10
10
Oil, gas, pulverized
fuel fired
14
16
When a boiler is fired only by a gas having a heat value not
in excess of two hundred (200) Btu/cubic feet (cu. ft.), the
minimum safety or safety relief valve capacity may be based on
the value given for hand fired boilers. The minimum safety or
safety relief valve capacity for electric boilers shall be three and
one-half (3.5) pounds per hour per kilowatt input.
(E) Each heating boiler, water heater, and fired jacketed steam
kettle shall be safely supported. There shall be no excessive
vibration in either the object or the connecting piping.
(F) All existing heating boilers, water heaters, pool heaters,
and fired jacketed steam kettles shall have adequate clearance
on all sides and top to facilitate repair, maintenance, and
inspection. Heating boilers, water heaters, pool heaters, and
fired jacketed steam kettles, installed or reinstalled on or after
January 1, 2010, shall meet the following requirements:
1. There shall be at least thirty-six inches (36") of clearance
on each side of the boiler. Boilers in battery shall not be
installed any closer than forty-eight inches (48"). The front and
rear of the boiler shall not be located nearer than thirty-six
inches (36") from any wall or structure;
2. Boilers shall be installed to allow for removal and
installation of tubes;
3. Boilers with top-opening manholes shall have at least
eighty-four inches (84") of unobstructed clearance above the
manhole to the ceiling of the boiler room;
4. Boilers without top-opening manholes shall have at
least thirty-six inches (36") clearance from the top of the boiler;
5. Boilers with bottom openings used for inspection
or maintenance shall have at least twelve inches (12") of
unobstructed clearance; and
6. Modular heating boilers that require individual
units to be set side by side, front to back, or by stacking may
provide clearances in accordance with the manufacturer’s
recommendations with the approval of the chief inspector.
7. Note: Alternatively, clearances in accordance with the
manufacturer’s recommendations are subject to the approval
of the chief inspector.
(G) All rooms containing heating boilers, water heaters, and
fired jacketed steam kettles with a combined capacity over one
(1) million Btu/hr and over five hundred (500) square feet floor
area shall have at least two (2) exits remotely located from each
other.
(H) Ladders and runways shall be provided between or over
the top of boilers installed or reinstalled on or after January
1, 2010, that are more than eight feet (8') above the operating
floor to afford accessibility for normal operation, maintenance,
and inspection. These ladders and runways must be built and
installed in accordance with the National Board Inspection
Code, Part 1.
(I) Combustion air—The boiler room shall have an adequate
air supply to permit clean, safe combustion, minimize soot
formation, and maintain a minimum of nineteen and onehalf percent (19.5%) oxygen in the air of the boiler room.
The combustion and ventilation air shall be supplied by an
unobstructed opening or by power ventilation or fans.
1. Unobstructed air openings shall be sized on the basis of
one (1) sq. in. (6.50 sq. mm) free area per two thousand British
thermal units per hour (2,000 Btu/hr) (five hundred eighty-six
watts per hour (586 W/hr)) maximum fuel input of the combined burners located in the boiler room or as specified in the
National Fire Protection Association (NFPA) standards for oil
and gas burning installations for the particular job conditions.
The boiler room air supply openings shall be kept clear at all
times.
2. Power ventilators or fans shall be sized on the basis of
0.2 cfm (.0057 cubic meters per minute) for each one thousand
British units per hour (1,000 Btu/hr) (two hundred ninety-three
watts per hour (293 W/hr)) of maximum fuel input for the
combination burners of all boilers located in the boiler room.
Additional capacity shall be required for any other fuel burning equipment in the boiler room.
3. When power ventilators or fans are used to supply combustion air, they shall be installed with interlock devices so that
the burners will not operate without an adequate number of
ventilators/fans in operation.
4. When combustion air is supplied to the boiler by an
independent duct, with or without the employment of power
ventilators or fans, the duct shall be sized and installed in accordance with the manufacturer’s recommendations. However,
ventilation of the boiler room must still be considered.
5. Care should be taken to ensure that steam and water
lines are not routed across combustion air openings, where
freezing may occur.
6. Opening boiler room door(s) and/or window(s) is unacceptable for supplying combustion air.
(J) Controls—
1. Oil-fired, gas-fired, and electrically heated heating boilers, water heaters, pool heaters, and fired jacketed steam kettles shall be equipped with suitable primary (flame safeguard)
safety controls, limit switches, and burners or electric elements
that are labeled and listed by a nationally or internationally
recognized standard.
2. All controls and devices shall be installed in accordance
with the manufacturer’s recommendations, and/or industry
standards, as applicable.
3. All automatically fired heating boilers, water heaters,
pool heaters, and fired jacketed steam kettles shall have a disconnecting means capable of being locked in the open position and shall be installed at an accessible location in the same
room as the object. This disconnect means shall disconnect all
sources of potential from the object.
4. A manually operated remote shutdown switch or circuit
breaker shall be located just outside the entrance door of the
room the object is located in and be marked for easy identification. Consideration should be given to the type and location of
the switch to safeguard against tampering. If the entrance door
is on the building exterior, the switch should be located just
inside the door. If there is more than one (1) door to the room,
there should be a switch located at each door. The emergency
switch must be installed in accordance with the manufacturer’s instructions or a nationally recognized standard and must
cause a safety shutdown and lockout.
(K) Each gas-fired water heater contracted after January 1,
2010, must be certified to the American National Standard/CSA
Standard for Gas Water Heaters, Volume III (ANSI Z21.10.3 CSA
4.3) and must bear a label as proof of this certification.
(L) Each gas-fired pool heater contracted after January 1,
2010, must meet one (1) of the following—
1. Be certified to the American National Standard/CSA
Standard For Gas-Fired Pool Heaters, (ANSI Z21.56 CSA 4.7) and
bear the label as proof of this certification; or
2. Commercial pool heaters applications that do not have
one hundred percent (100%) of pool loop water flow circulating
through the pool heater may be certified to the American
National Standard/CSA Standard for Gas Water Heaters, Volume
III (ANSI Z21.10.3 CSA 4.3) and must bear a label as proof of
this certification, provided the unit must bear a label from
the manufacturer as evidence that the water heater has been
approved for commercial pool heating applications when
installed per the manufacturer’s instructions. Additionally,
the manufacturer must provide additional listed temperature
controls that will limit the water temperature delivered to the
pool from exceeding one hundred eight degrees Fahrenheit
(108 °F) with details for the installation of these controls.
(M) The Code nameplates shall remain readily accessible
at all times. Loose or missing nameplates shall be replaced
or reattached as provided for in the National Board Inspection
Code.
(N) Rental heating boilers, water heaters, and fired jacketed
steam kettles, used for temporary service, shall meet all of the
requirements of these rules. The internal inspection, required
by 11 CSR 40-2.022, may be waived by the inspector, based on
documentation that a national board-commissioned inspector
has evaluated the internal surfaces of the object within the
past twelve (12) months and found the object acceptable for
use. An external, in-operation inspection shall be the basis
for the inspection certificate. The inspection certificate shall
expire no later than twenty-four (24) months from the date of
the last internal inspection.
AUTHORITY: section 650.215, RSMo 2000.* Original rule filed May
12, 1986, effective Oct. 27, 1986. Amended: Filed Sept. 27, 1990,
effective Feb. 14, 1991. Amended: Filed Oct. 3, 1995, effective April
30, 1996. Rescinded: Filed March 10, 2003, effective Aug. 30, 2003.
Readopted: Filed Sept. 25, 2002, effective May 30, 2003. Amended:
Filed Jan. 12, 2006, effective June 30, 2006. Amended: Filed June
30, 2009, effective Feb. 28, 2010.
*Original authority: 650.215, RSMo 1984, amended 1990, 1993, 1995.