19 MAC Pt. 7, R. 5.06.2
Fire Separation
Cite as 19 Miss. Admin. Code Pt. 7, R. 5.06.2
Fire Separation
Separation from adjacent structures and lot lines is based on the fire resistance rating of the
home pursuant to NFPA 501A Standard for Fire Safety Criteria for Factory-Built Home
Installations, Sites and Communities, Section 4 2.1, entitled "Fire Safety Separation
Requirements," Sub section 4.2.1.1 as follows:
Any portion of a Factory-Built home, excluding the tongue, shall not be located closer than 10
ft. when placed side to side, 8 ft. when placed end to side, or 6 ft. end to end horizontally from
any other Factory-Built home, existing house structure, storage building, garage, shop or
community building not attached to the Factory-Built home unless the exposed composite walls
and roof of either structure are without openings and constructed of materials that will provide a
one hour fire rating or the structures are separated by a one hour fire rated barrier. Most
Factory-Built homes may be classified as "non-rated" construction. However, manufacturers
may, in some instances, construct one hour rated walls. Information regarding the fire rating of
the unit may be obtained from the manufacturer or third-party inspection agency identified on
the data plate.