15 MAC Pt. 10, R. 2.11.2
If, upon inspection, a Special Inspector finds a boiler or pressure vessel to be
Cite as 15 Miss. Admin. Code Pt. 10, R. 2.11.2
If, upon inspection, a Special Inspector finds a boiler or pressure vessel to be
unsafe for further operation, he shall promptly notify the owner or user, stating
what repairs or other corrective measures are required to bring the object into
compliance with these rules and regulations. Unless the owner or user agrees to
make such repairs or adopt such other corrective measures promptly, the Special
Inspector shall immediately notify the Chief Inspector. Until such corrections
have been made, no further operation of the boiler or pressure vessel involved
shall be permitted. If an inspection certificate for the object is required and is in
force, it shall be suspended by the Chief Inspector. When reinspection establishes
that the necessary repairs have been made or corrective actions have been taken
and that the boiler or pressure vessel is safe to operate, the Chief Inspector shall
be notified. At that time a certificate of inspection, where applicable, will be
issued.