15 MAC Pt. 10, R. 3.1.1
High Temperature Water Boilers - Age Limit of Existing Boilers
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.1.1
High Temperature Water Boilers - Age Limit of Existing Boilers
1.
The age limit of any boiler of nonstandard construction, installed prior to August
6, 1975, shall be 30 years except that, after a thorough internal and external
inspection, and a hydrostatic pressure test of 1 1/2 times these allowable working
pressure and held for a period of at least 30 minutes, during which time no
distress or leakage develops, any boiler having other than a riveted, longitudinal,
lap joint may be continued in operation without reduction in working pressure.
The age limit of any boiler having riveted, longitudinal, lap joints and operating at
a pressure in excess of 50 psi shall be 20 years. This type of boiler, when
removed from an existing setting, shall not be installed for a pressure in excess of
15 psig. A reasonable time for replacement, not to exceed one year, may be given
at the discretion of the Chief Inspector.
2.
The shell or drum of a boiler in which a typical "lap seam crack" is discovered
along a longitudinal riveted joint for either butt or lap joints shall be permanently
discontinued for use under steam pressure. By "lap seam crack" is meant the
typical crack frequently found in lap joints extending parallel to the longitudinal
joint and located either between or adjacent to rivet holes.
3.
The age limit of boilers of standard construction, installed prior to August 6,
1975, shall be determined from the results of a thorough internal and external
inspection by an authorized inspector and the application of an appropriate
pressure test. Hydrostatic test pressure shall be at 1 1/2 times the allowable
working pressure and maintained for 30 minutes. The boiler may be continued in
service at the same working pressure provided there is no evidence of leakage or
distress under these test conditions.
4.
The phenomenon of brittle fracture may result from stresses imposed during
hydrostatic testing below the Nil-Ductility Transition Temperature of the
materials. Where such data is unavailable on site, it is suggested that the
manufacturer be contacted for the recommended minimum temperature to be used
during hydrostatic testing.