15 MAC Pt. 10, R. 3.1.10
Stop Valves
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.1.10
Stop Valves
1.
Except for a single-boiler, prime-mover installation, each steam outlet from a
boiler (except safety-valve and water column connections) shall be fitted with
a stop valve located as close as practicable to the boiler.
2.
In a single-boiler, prime-mover installation, the steam stop valve may be
omitted provided the prime-mover throttle valve is equipped with an indicator
to show whether the valve is open or closed and is designed to withstand the
required hydrostatic pressure test of the boiler.
3.
When a stop valve is so located that water can accumulate, ample drains shall
be provided. The drainage shall be piped to a safe location and shall not be
discharged on the top of the boiler or its setting.
4.
When boilers provided with manholes are connected to a common steam
main, the steam connection from each boiler shall be fitted with two stop
valves having an ample free-blow drain between them. The discharge of the
drain shall be visible to the operator while manipulating the valves and shall
be piped clear of the boiler setting. The stop valves shall consist preferably of
one automatic non-return valve (set next to the boiler) and a second valve of
the outside-screw-and-yoke type.