15 MAC Pt. 10, R. 3.1.9
Steam Gauges
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.1.9
Steam Gauges
1.
Each steam boiler shall have a steam gauge, with dial range not less than 1 1/2
times the maximum allowable working pressure, connected to the steam space
or to the steam connection to the water column. The steam gauge shall be
connected to a siphon or equivalent device of sufficient capacity to keep the
gauge tube filled with water and so arranged that the gauge cannot be shut off
from the boiler except by a cock placed near the gauge and provided with a
tee or lever handle arranged to be parallel to the pipe in which it is located
when the cock is open.
2.
When a steam gauge connection longer than eight feet becomes necessary, a
shutoff valve may be used near the boiler provided the valve is of the outside-
screw-and-yoke type and is locked open. The line shall be of ample size with
provision for free blowing.
3.
Each boiler shall be provided with a connection and suitable valving which
connects to the steam space of each boiler for the exclusive purposes of
attaching a test gauge when the boiler is in service so that the accuracy of the
boiler steam gauge may be ascertained.