15 MAC Pt. 10, R. 3.1.7
Boiler Feeding
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.1.7
Boiler Feeding
1.
Each boiler shall have a feed supply which will permit it to be fed at any time
while under pressure.
2.
A boiler having more than 500 square feet of water-heating surface shall have
at least two means of feeding, one of which shall be an approved feed pump,
injector or inspirator. A source of feed directly from water mains at a pressure
six percent greater than the set pressure of the safety valve with the highest
setting may be considered one of the means. As provided for in the ASME
Power Boiler Code, Section I, boilers fired by gaseous, liquid, or solid fuel in
suspension may be equipped with a single means of feeding water provided
means are furnished for the immediate shutoff of heat input if the water feed is
interrupted.
3.
The feedwater shall be introduced into the boiler in such manner that it will
not be discharged close to riveted joints of shell or furnace sheets, or directly
against surfaces exposed to products of combustion, or to direct radiation from
the fire.
4.
The feed piping to the boiler shall be provided with a check valve near the
boiler and a valve or cock between the check valve and the boiler. When two
or more boilers are fed from a common source, there shall also be a valve on
the branch to each boiler between the check valve and source of supply.
Whenever a globe valve is used on feed piping, the inlet shall be under the
disk of the valve.
5.
In all cases where returns are fed back to the boiler by gravity, there shall be a
check valve and stop valve in each return line, the stop valve to be placed
between the boiler and the check valve, and both shall be located as close to
the boiler as is practicable. It is recommended that no stop valves be placed in
the supply and return pipe connections of a single boiler installation.
6.
Where deaerating heaters are not employed, it is recommended that the
temperature of the feedwater be not less than 120ø F to avoid the possibility of
setting up localized stress. Where deaerating heaters are employed, it is
recommended the minimum feedwater temperature be not less than 215ø F so
that dissolved gases may be thoroughly released.