15 MAC Pt. 10, R. 3.2.14
Water Gauge Glasses
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.2.14
Water Gauge Glasses
1.
Each steam boiler shall have one or more water gauge glasses attached to the
water column or boiler by means of valved fittings. The lower fitting shall be
provided with a drain valve of the straightaway type with opening not less than
1/4 inch diameter to facilitate cleaning. Gauge glass replacement shall be
possible while the boiler is under pressure.
2.
Transparent material, other than glass, may be used for the water gauge provided
that the material has proved suitable for the pressure, temperature and corrosive
conditions encountered in service.