15 MAC Pt. 10, R. 3.2.15
Stop Valves and Check Valves
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.2.15
Stop Valves and Check Valves
1.
If a boiler can be closed off from the heating system by closing a steam stop
valve, there shall be a check valve in the condensate return line between the boiler
and the system.
2.
If any part of a heating system can be closed off from the remainder of the system
by closing a steam stop valve, there shall be a check valve in the condensate
return pipe from that part of the system.