15 MAC Pt. 10, R. 3.2.5
Safety Valves
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.2.5
Safety Valves
1.
Each steam boiler shall have one or more officially rated safety valves of the
spring pop type adjusted to discharge at a pressure not to exceed 15 psig.
Seals may be attached in a manner to prevent the valve from being taken apart
without breaking the seal. The safety valves shall be arranged so that they
cannot be reset to relieve at a higher pressure than the maximum allowable
working pressure of the boiler. A body drain connection below seat level
shall be provided by the manufacturer, and this drain shall not be plugged
during or after field installation. For valves exceeding two inch pipe size, the
drain hole or holes shall be tapped not less than 3/8 inch pipe size. For valves
less than two inches, the drain hole shall not be less than 1/4 inch in diameter.
2.
No safety valve for a steam boiler shall be smaller than 1/2 inch unless the
boiler and radiating surfaces consist of a self-contained unit. No safety valve
shall be larger than 4 1/2 inches. The inlet opening shall have an inside
diameter equal to, or greater than, the seat diameter.
3.
The minimum relieving capacity of the valve or valves shall be governed by
the capacity marking on the boiler.
4.
The minimum valve capacity in pounds per hour shall be the greater of that
determined by dividing the maximum BTU output at the boiler nozzle
obtained by the firing of any fuel for which the unit is installed by 1,000, or
shall be determined on the basis of the pounds of steam generated per hour per
square foot of boiler heating surface as given in Table 2. In many cases, a
greater relieving capacity of valves will have to be provided than the
minimum specified by these rules. In every case, the requirements of (e)
below shall be met.
Table 3: Minimum pounds of steam per hour per square foot of heating surface
Boiler Heating Surface:
Firetube Boilers
Watertube Boilers
Hand Fired
Stoker Fired
Oil, gas, or pulverized fuel
fired
Waterwall Heating Surface:
Firetube Boilers
Watertube Boilers
Hand Fired
Stoker Fired
Oil, gas, or pulverized fuel
fired
Notes:
a.
When a boiler is fired only by a gas giving a heat value not in excess of
200 BTU per cubic foot, the minimum safety valve or safety relief valve
relieving capacity may be based on the value given for handfired boilers
above.
b.
The minimum safety valve or safety relief valve relieving capacity for
electric boilers shall be 3 1/2 pounds per hour per kilowatt input.
c.
For heating surface determination, see ASME Code, Section IV, para
HG-403.
5.
The safety valve capacity for each steam boiler shall be such that with the fuel
burning equipment installed, and operated at maximum capacity, the pressure
cannot rise more than 5 psi above the maximum allowable working pressure.
6.
When operating conditions are changed, or additional boiler surface is installed,
the valve capacity shall be increased, if necessary, to meet the new conditions and
be in accordance with (d) and (e). The additional valves required, on account of
changed conditions, may be installed on the outlet piping provided there is no
intervening valve.
7.
If there is any doubt as to the capacity of the safety valve, an accumulation test
shall be run (see ASME Code, Section VI, Care of Heating Boilers).
8.
No valve of any description shall be placed between the safety valve and the
boiler, nor on the discharge pipe between the safety valve and the atmosphere.
The discharge pipe shall be at least full size and be fitted with an open drain to
prevent water lodging in the upper part of the safety valve or in the discharge
pipe. When an elbow is placed on the safety valve discharge pipe, it shall be
located close to the safety valve outlet or the discharge pipe shall be securely
anchored and supported. All safety valve discharges shall be so located or piped
as not to endanger persons working in the area.