15 MAC Pt. 10, R. 3.2.6
Safety Relief Valve Requirements for Hot Water Boilers
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.2.6
Safety Relief Valve Requirements for Hot Water Boilers
1.
Each hot water heating boiler shall have at least one officially rated (ASME
approved and National Board rated) safety relief valve set to relieve at or below
the maximum allowable working pressure of the boiler. Each hot water supply
boiler shall have at least one officially rated safety relief valve of the automatic
reseating type set to relieve at or below maximum allowable working pressure of
the boiler. Safety relief valves officially rated as to capacity shall have pop action
when tested by steam. When more than one safety relief valve is used on either
hot water heating or hot water supply boilers, the additional valve or valves shall
be officially rated and may be set within a range not to exceed 6 psi above the
maximum allowable working pressure of the boiler up to and including 60 psig
and 10 percent for those having maximum allowable working pressure exceeding
60 psig. Safety relief valves shall be spring loaded. Safety relief valves shall be
so arranged that they cannot be reset at a higher pressure than the maximum
permitted by this paragraph.
2.
No materials liable to fail due to deterioration or vulcanization when subject to
saturated steam temperature corresponding to capacity test pressure shall be used
for any part.
3.
No safety relief valve shall be smaller than 3/4 inch nor larger than 4 1/2 inches
standard pipe size, except that boilers having a heat input not greater than 15,000
BTU per hour may be equipped with a rated safety relief valve of 1/2 inch
standard pipe size. The inlet opening shall have an inside diameter approximately
equal to or greater than, the seat diameter. In no case shall the minimum opening
through any part of the valve be less than 1/4 inch diameter or its equivalent area.
4.
The required steam relieving capacity, in pounds per hour, of the pressure
relieving device or devices on a boiler shall be the greater of that determined by
dividing the maximum output in BTU at the boiler outlet obtained by the firing of
any fuel for which the unit is installed by 1,000, or on the basis of pounds of
steam generated per hour per square foot of boiler heating surface as given in
Table 2. In many cases, a greater relieving capacity of valves will have to be
provided than the minimum specified by these rules. In every case, the
requirements of (f) shall be met.
5.
When operating conditions are changed, or additional boiler heating surface is
installed, the valve capacity shall be increased, if necessary, to meet the new
conditions and shall be in accordance with (f). The additional valves required, on
account of changed conditions, may be installed on the outlet piping provided
there is no intervening valve.
6.
Safety relief valve capacity for each boiler shall be such that, with the fuel
burning equipment installed and operated at maximum capacity, the pressure
cannot rise more than 6 psi above the maximum allowable working pressure for
pressure up to and including 60 psig and 10 percent of maximum allowable
working pressures over 60 psig.
7.
If there is any doubt as to the capacity of the safety relief valve, an accumulation
test shall be run (see ASME Code, Section VI, Care of Heating Boilers).
8.
No valve of any description shall be placed between the safety relief valve and the
boiler, nor on the discharge pipe between the safety relief valve and the
atmosphere. The discharge pipe shall be at least full size and fitted with an open
drain to prevent water lodging in the upper part of the safety relief valve or in the
discharge pipe. When an elbow is placed on the safety relief valve discharge
pipe, it shall be located close to the safety relief valve outlet or the discharge pipe
shall be securely anchored and supported. All safety relief valve discharges shall
be so located or piped as not to endanger persons working in the area.