15 MAC Pt. 10, R. 3.4.12
Boiler Door Latches
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.4.12
Boiler Door Latches
1.
A watertube toiler shall have the firing doors of the inward-opening type, unless
such doors are provided with substantial and effective latching or fastening
devices or otherwise so constructed as to prevent them, when closed, from being
blown open by pressure on the furnace side.
2.
These latches or fastenings shall be of the positive self-locking type. Friction
contacts, latches, or bolts actuated by springs shall not be used. The foregoing
requirements for latches or fastenings shall not apply to coal openings of
downdraft or similar furnaces.
3.
All other doors, except explosion doors, not used in the firing of the boiler, may
be provided with bolts or fastenings in lieu of self-locking latching devices.
Explosion doors, if used and if located in the setting walls within seven feet of the
firing floor or operating platform, shall be provided with substantial deflectors to
divert the blast.