15 MAC Pt. 10, R. 3.4.13
Clearance: When boilers are replaced or new boilers are installed in either
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.4.13
Clearance: When boilers are replaced or new boilers are installed in either
existing or new buildings, a minimum height of at least three feet shall be
provided between the top of the boiler proper and the ceiling and at least three
feet between all sides of the boiler and adjacent walls or other structures. Boilers
and pressure vessels having manholes shall have five feet clearance from the
manhole opening and any wall, ceiling or piping that will prevent a person from
entering the boiler or vessel. All boilers and pressure vessels shall be so located
that adequate space will be provided for the proper operation of the boilers and
pressure vessels and their appurtenances, for the inspection of all surfaces, tubes,
waterwalls, economizers, piping, valves and other equipment, and for their
necessary maintenance and repair and replacement of tubes.