15 MAC Pt. 10, R. 3.4.6
Automatic Low-Water Fuel Cutoff and/or Water-Feeding Device
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.4.6
Automatic Low-Water Fuel Cutoff and/or Water-Feeding Device
1.
Each automatically fired and unattended steam or vapor system boiler shall be
equipped with an automatic low-water fuel cutoff so locates as to automatically
cut off the fuel supply when the surface of the water falls to the lowest safe water
line. If a water-feeding device is installed, it shall be so constructed that the water
inlet valves cannot feed water into the boiler through the float chamber and so
located as to supply requisite feedwater. The lowest safe water line should be not
lower than the lowest visible part of the water glass. Such fuel or feedwater
control device may be attached direct to a boiler or to the tapped openings
provided for attaching a water glass direct to a boiler provided that for low-
pressure boilers such connections from the boiler are nonferrous tees of Y's not
less than 1/2-inch pipe size between the boiler and the water glass, so that the
water glass is attached direct and as close as possible to the boiler; the
straightaway tapping of the Y or tee to take the water glass fittings, the side outlet
of the Y or tee to take the fuel cutoff or water-feeding device.
2.
The ends of all nipples shall be reamed to full-size diameter.
3.
Designs embodying a float and float bowl shall have a vertical straightaway valve
drain pipe at the lowest point in the water-equalizing pipe connections by which
the bowl and the equilizing pipe can be flushed and the device tested. A coil type
boiler or a water tube boiler with heat input greater than 400,000 BUT/HR
requiring forced circulation, to prevent overheating of the coils or tubes, shall
have a flow sensing device installed in the outlet piping, in lieu of the low water
fuel cutoff required in this item, to automatically cut off fuel supply when the
circulating flow is interrupted.