15 MAC Pt. 10, R. 3.4.7
Pressure-Reducing Valves
Cite as 15 Miss. Admin. Code Pt. 10, R. 3.4.7
Pressure-Reducing Valves
1.
Where pressure-reducing valves are used, one or more relief or safety valves shall
be provided on the low-pressure side of the reducing valve when the piping or
equipment on the low-pressure side does not meet the requirements for the full
initial pressure. Proper protection shall be provided to prevent injury or damage
caused by the escaping fluid from the discharge of relief or safety valves if vented
to the atmosphere. The combined discharge capacity of the relief or safety valves
shall be such that the pressure rating of the lower pressure piping or equipment
shall not be exceeded in case the reducing valve sticks open. The use of hand-
controlled bypasses around reducing valves is permissible. If a bypass is used
around the reducing valve, the safety valve required on the low pressure side shall
be sufficient capacity to relieve all the fluid that can pass through the bypass
without overpressuring the low pressure side.
2.
It is mandatory that a pressure gauge be installed on the low-pressure side of a
reducing valve.