Recommended Devices for High Hazard Cross Connections.
1.
Reduced Pressure Principle Backflow Prevention Assemblies. Backflow
prevention assemblies recommended to protect high hazard cross connections shall
include reduced pressure principle backflow prevention assemblies.
2.
Pressure Vacuum Breaker Assemblies. Backflow prevention assemblies
recommended to protect high hazard cross connections shall include pressure vacuum
breaker assemblies. Pressure vacuum breaker assemblies shall not be used in
locations where the vacuum breaker may be subject to back pressure and shall not be
used in locations where the vacuum breaker is not higher than all downstream
connections.
3.
Atmospheric Vacuum Breakers. Backflow prevention devices recommended to
protect high hazard cross connections shall include atmospheric vacuum breakers.
Atmospheric vacuum breakers shall not be installed in locations that may be subject
to back pressure, shall not be installed in locations where the vacuum breaker is not
higher than all downstream locations, shall not be installed in locations with valves
downstream and shall not be installed in locations of continuous use.