15 MAC Pt. 20, R. 1.12.3
Low Hazard Cross Connections
Cite as 15 Miss. Admin. Code Pt. 20, R. 1.12.3
Low Hazard Cross Connections. Backflow prevention assemblies recommended to
protect low hazard cross connections shall include reduced pressure principle
assemblies, pressure vacuum breaker assemblies, atmospheric vacuum breaker
assemblies, and double check valve assemblies. Pressure vacuum breaker assemblies
shall not be used in locations where the vacuum breaker may be subject to back
pressure and shall not be used in locations where the vacuum breaker is not higher
than all downstream connections. Atmospheric vacuum breakers shall not be
installed in locations that may be subject to back pressure, shall not be installed in
locations where the vacuum breaker is not higher than all downstream locations, shall
not be installed in locations with valves downstream and shall not be installed in
locations of continuous use.