Each patient room must meet the following requirements:
1.
A patient room may not be located on a floor unless a portion of the floor is at or above grade
level. A patient room may not have its floor more than thirty inches [.76 meter] below the
adjacent grade.
2.
Patient rooms must have adequate space to conveniently house necessary furniture and
equipment, to provide for efficient patient care, to provide for convenient movement of
stretchers, and for the transfer of patients to and from beds.
3.
The smallest dimension of a rectangular single patient room may not be less than ten feet
[3.05 meters] free of fixed obstructions and the floor area may not be less than one hundred
twenty-five square feet [11.61 square meters].
4.
The smallest dimension of a rectangular multiple patient room may not be less than eleven
feet six inches [3.51 meters] free of fixed obstructions, except in specially arranged
rectangular rooms such as toe-to-toe arrangements where the minimum clear width may not
be less than ten feet [3.05 meters] free of fixed obstructions.
5.
In other than rectangular-shaped rooms, the principles of space allocation specified by the
minimum dimensions and floor area requirements in rectangular-shaped rooms must be
adhered to.
6.
Each patient room must have an outside wall with natural light provided by a window. The
area of the glazing material in the window may not be less than one-tenth of the floor area of
the patient room.
7.
Multiple patient rooms must be designed to permit no more than two beds side by side parallel
to the window wall.
8.
A patient room may not be located more than one hundred twenty feet [36.58 meters] from the
nurses station, the clean workroom, and the soiled workroom.
9.
Patient toilet rooms must be functionally accessible and usable by the patients whom they
serve.