NDAC 33-07-02.1-06
Details
Cite as N.D. Admin. Code ยง 33-07-02.1-06
1.
At least one room must be provided for toilet training. It must be accessible from the corridor
and may also serve the bathing area, and must provide three feet [.91 meter] clearance at the
front and both sides of the water closet.
2.
Ceilings must be acoustically treated in patient area corridors, nurses stations, labor rooms,
dining areas, and dayrooms.
3.
All lavatories and sinks required in patient care areas must have the water supply spout
mounted so that its discharge point is a minimum distance of five inches [12.7 centimeters]
above the rim of the fixture.
4.
Flush valves installed on plumbing fixtures must be of quiet operating type equipped with
silencers.