NDAC 33.1-14-05-21
Steam pressure gauge
Cite as N.D. Admin. Code ยง 33.1-14-05-21
1.
Each steam boiler must have a steam gauge, with dial range not less than one and one-half
times the pressure at which the safety valve is set, connected to the steam space or to the
steam connection to the water column. The steam gauge must be connected to a siphon or
equivalent device of sufficient capacity to keep the gauge tube filled with water and so
arranged that the gauge cannot be shut off from the boiler except by a cock placed near the
gauge and provided with a tee or lever handle arranged to be parallel to the pipe in which it is
located when the cock is open.
2.
When a steam pressure gauge connection longer than eight feet [2.44 meters] becomes
necessary, a shutoff valve may be used near the boiler provided the valve is of the
outside-screw-and-yoke type and is locked open. The line must be ample size with provision
for free blowing. Each boiler must be provided with a one-quarter inch [6.35 millimeter] nipple
and globe valve connected to the steam space for the exclusive purpose of attaching a test
gauge when the boiler is in service so that the accuracy of the boiler steam gauge may be
ascertained.