NDAC 33.1-14-05-20
Water columns, gauge glasses, and gauge cocks
Cite as N.D. Admin. Code ยง 33.1-14-05-20
1.
Outlet connections (except for damper regulator, feedwater regulator, low-water fuel cutoff,
drains, steam gauges, or such apparatus that does not permit the escape of an appreciable
amount of steam or water therefrom) may not be placed on the piping that connects the water
column to the boiler. The water column must be placed on the piping that connects the water
column to the boiler. The water column must be provided with a valved drain of at least
three-quarter inch [19.05 millimeter] pipe size, the drain to be piped to a safe location.
2.
Each boiler constructed prior to 1999 must have three or more gauge cocks located within the
visible length of the water glass, except when the boiler has two water glasses located on the
same horizontal lines. Boilers not over thirty-six inches [.914 meters] in diameter, in which the
heating surface does not exceed one hundred square feet [9.29 square meters] need have but
two gauge cocks.
3.
For all installations where the water gauge glass or glasses are more than thirty feet
[9.14 meters] from the boiler operating floor, it is recommended that water level indicating or
recording gauges be installed at eye height from the operating floor.