NDAC 33.1-14-09-07
Pressure-relieving devices
Cite as N.D. Admin. Code ยง 33.1-14-09-07
1.
Safety valve requirements for steam boilers are:
a.
Each steam boiler must have one or more American Society of Mechanical Engineers
approved safety valves of the spring-pop type adjusted and sealed to discharge at a
pressure not to exceed fifteen pounds per square inch [103 kilopascals]. Seals must be
attached in a manner to prevent the valve from being taken apart without breaking the
seal. The safety valves must be arranged so that they cannot be reset to relieve at a
higher pressure than the maximum allowable working pressure of the boiler. For
iron-and-steel-bodied valves exceeding two inch [50.8 millimeter] pipe size, the drain
hole or holes must be tapped not less than three-eighths inch [9.53 millimeter] pipe size.
b.
Each safety valve three-quarter inch [10.05 millimeters] diameter or over, used on a
steam boiler, must have a substantial device that will positively lift the disk from its seat at
least one-sixteenth inch [1.59 millimeters] when there is no pressure in the boiler. The
seats and disks must be of suitable material to resist corrosion.
c.
A safety valve for a steam boiler may not be smaller than three-quarter inch
[19.05 millimeters] unless the boiler and radiating surfaces consist of a self-contained
unit. A safety valve may not be larger than four and one-half inches [114.3 millimeters].
The inlet opening must have an inside diameter equal to, or greater than, the seat
diameter.
d.
The minimum relieving capacity of valve or valves is governed by the capacity marking
on the boiler.
e.
The minimum valve capacity in pounds per hour is the greater of that determined by
dividing the maximum British thermal units output at the boiler nozzle obtained by the
firing of any fuel for which the unit is installed by one thousand, or is determined on the
basis of the pounds of steam generated per hour per square foot of boiler heating
surface. (One British thermal unit equals 1.055 x 10 to the third power joules.)
MINIMUM POUNDS OF STEAM PER HOUR
PER SQUARE FOOT OF HEATING SURFACE
Boiler Heating
Surface
Firetube
Boilers
Watertube
Boilers
Hand-fired
5
6
Stoker-fired
7
8
Oil, gas, or pulverized fuel-fired
8
10
f.
Safety valves must be installed with the valve spindle in the vertical position. Discharge
piping, to a safe location, may be required by the inspector.
2.
When a boiler is fired only by a gas having a heat value not in excess of two hundred British
thermal units per cubic feet [745.58 x 10 to the fourth power joules per cubic meter], the
minimum safety valve or safety relief valve relieving capacity may be based on the values
given for hand-fired boilers above.
3.
The safety valve or safety relief valve relieving capacity for electric boilers is three and
one-half pounds [3692.5 joules] per hour per kilowatt input.
a.
The safety valve capacity for each steam boiler must be such that with the fuel-burning
equipment installed and operated at maximum capacity the pressure cannot rise more
than five pounds per square inch [34.47 kilopascals] above the maximum allowable
working pressure.
b.
When operating conditions are changed, or additional boiler heating surface is installed,
the valve capacity must be increased, if necessary, to meet the new conditions, the
additional valves required, on account of changed conditions, may be installed on the
outlet piping provided there is no intervening valve.
4.
Safety relief valve requirements for hot water boilers are:
a.
Each hot water heating boiler must have at least one American society of mechanical
engineers approved pressure relief valve set to relieve at or below the maximum
allowable working pressure of the boiler. Each hot water supply boiler must have at least
one officially rated safety relief valve or at least one American society of mechanical
engineers approved pressure-temperature relief valve of the automatic-reseating type set
to relieve at or below the maximum allowable working pressure of the boiler. Pressure
relief valves officially rated as to capacity must have pop action when tested by steam.
When more than one safety relief valve is used on either hot water heating or hot water
supply boilers, the additional valve or valves must be officially rated and may be set
within a range not to exceed six pounds per square inch [41.47 kilopascals] above the
maximum allowable working pressure of the boiler up to and including sixty pounds per
square inch [413.69 kilopascals] and ten percent for those having a maximum allowable
working pressure exceeding sixty pounds per square inch [413.69 kilopascals]. Safety
relief valves must be spring loaded without disk guides on the pressure side of the valve.
Safety relief valves must be arranged so that they cannot be reset to relieve at a higher
pressure than the maximum permitted by this subdivision.
b.
Each safety relief valve must have a substantial device that will positively lift the disk
from its seat at least one-sixteenth inch [1.59 millimeters] when there is no pressure on
the boiler.
c.
Materials subject to deterioration or vulcanization when subject to saturated steam
temperature corresponding to capacity test pressure may not be used for any part.
d.
A safety relief valve may not be smaller than three-quarter inch [19.05 millimeters] nor
larger than four and one-half inch [114.3 millimeter] standard pipe size, except that
boilers having a heat input not greater than fifteen thousand British thermal units per hour
[15.38 x 10 to the seventh power joules] may be equipped with a rated safety relief valve
of one-half inch [12.7 millimeter] standard pipe size. The inlet opening must have an
inside diameter approximately equal to, or greater than, the seat diameter. The minimum
opening through any part of the valve may not be less than one-quarter inch
[6.35 millimeters] diameter or its equivalent area.
e.
The required steam-relieving capacity, in pounds per hour, of the pressure-relieving
device or devices on a boiler must be determined by dividing the maximum output in
British thermal units at the boiler nozzle obtained by the firing of any fuel for which the
unit is designed by one thousand or by multiplying the square feet of heating surface by
five. In every case, the requirements of subdivision g must be met. (One British thermal
unit equals 1.055 x 10 to the third power joules.)
f.
When operating conditions are changed, or additional boiler heating surface is installed,
the valve capacity must be increased, if necessary, to meet the new conditions and be in
accordance with subdivision g. The additional valves required, on account of changed
conditions, may be installed on the outlet piping provided there is no intervening valve.
g.
Safety relief valve capacity for each boiler must be such that with maximum heat input
the pressure cannot rise more than six pounds per square inch [41.37 kilopascals] above
the maximum allowable working pressure for pressures up to and including sixty pounds
per square inch [413.69 kilopascals] and ten percent for maximum allowable working
pressures over sixty pounds per square inch [413.69 kilopascals].
h.
Safety relief valves must be installed with the spindle in the vertical position. Discharge
piping, to a safe location, must be installed.