NDAC 33.1-14-09-08
Steam pressure gauge
Cite as N.D. Admin. Code ยง 33.1-14-09-08
1.
Each steam boiler must have a steam gauge or a compound steam gauge connected to its
steam space or to its water column or to its steam connections. The gauge or connection must
contain a siphon or equivalent device that will develop and maintain a water seal that will
prevent steam from entering the gauge tube. The connection must be arranged so that the
gauge cannot be shut off from the boiler except by a cock placed in the pipe at the gauge and
provided with a tee or a lever handle arranged to be parallel to the millimeter] standard pipe
size, but where steel or wrought iron pipe or tubing is used, they must be not less than
one-half inch [12.7 millimeter] standard pipe size. The minimum size of a siphon, if used, must
be one-quarter inch [6.35 millimeters] inside diameter. Ferrous and nonferrous tubing having
inside diameters at least equal to that of standard pipe sizes listed above may be substituted
for pipe in which it is located when the cock is open. The connections to the boiler must be not
less than one-quarter inch [6.35 millimeter].
2.
The scale on the dial of a steam boiler gauge must be graduated to not less than thirty pounds
per square inch [206.84 kilopascals] nor more than sixty pounds per square inch
[413.69 kilopascals]. The gauge must be provided with effective stops for the indicating pointer
at the zero point and at the maximum pressure point. The travel of the pointer from zero to
thirty pounds per square inch [206.84 kilopascals] pressure must be at least three inches
[76.2 millimeters]. On a compound gauge, effective stops must be set at the limits of the
gauge readings on both the pressure and vacuum sides of the gauge.