NDAC 33.1-14-09-10
Stop valves and check valves
Cite as N.D. Admin. Code ยง 33.1-14-09-10
1.
If a steam boiler may be closed off from the heating system by closing a steam stop valve,
there must be a check valve in the condensate return line between the boiler and the system.
2.
If any part of a steam heating system may be closed off from the remainder of the system by
closing a steam stop valve, there must be a check valve in the condensate return pipe from
that part of the system.
3.
If more than one boiler is connected to a system, they must each be equipped with main stops
on the discharge and return side, in such a manner not affecting operation of any other boiler.
4.
When single boilers are located above the system and can be drained without draining the
system, stop valves are optional.