NDAC 33.1-14-09-11
Feedwater connections
Cite as N.D. Admin. Code ยง 33.1-14-09-11
1.
Feedwater connections must be independent of any water gauge connections and be made to
the condensate return pipe or reservoir of the condensate return tank.
2.
Alternatively, makeup water or water treatment may be introduced through an independent
connection. The water flow from the independent connection may not discharge directly
against parts of the boiler exposed to direct radiant heat from the fire. Makeup water or water
treatment may not be introduced through openings or connections provided for inspection or
cleaning, safety valve, safety relief valve, blowoff, water column, water gauge glass, pressure
gauge, or temperature gauge.
3.
When there is more than one boiler connected to a system, each boiler must have an
independent feedwater line.
4.
There must be a stop valve and a check valve in the feedwater line at the boiler. For hot water
heating boilers, the check valve must be a backflow preventer approved by the state plumbing
board.
5.
Hot water heating boilers, not equipped with an approved low-water fuel cutoff, must be
equipped with an automatic feeding device or pressure-reducing valve method of feeding, in
addition to a manual bypass capable of feeding the boiler at a pressure of six percent above
safety relief valve setting.