NDAC 33.1-14-09-18
Low-water fuel cutoff
Cite as N.D. Admin. Code ยง 33.1-14-09-18
1.
Each automatically fired hot water heating boiler must have an automatic low-water fuel cutoff
that has been designed for hot water service and which can be tested without draining the
system or the boiler. It must be so located as to automatically cut off the fuel supply prior to
the surface of the water falling below the lowest safe water level as established by the boiler
manufacturer.
2.
A coil-type or watertube boiler requiring forced circulation to prevent overheating of the coils or
tubes must have a flow-sensing device installed in the boiler or piping in lieu of the required
low-water fuel cutoff that will cut off the fuel supply when the circulation flow is interrupted.
Functioning of the low-water fuel cutoff due to a low-water condition must cause safety
shutdown and lockout. Where a reset device is separate from the low-water fuel cutoff, a
means must be provided to indicate actuation of the low-water fuel cutoff. The manual reset
may be the instantaneous type or may include a time delay of not more than three minutes
after the fuel has been cut off.
3.
Low-water fuel cutoff requirements for steam boilers are addressed by section 33.1-14-03-07.